Changes for page BMS Main 3X

Last modified by Admin on 2025/02/18 14:58

From version 6.1
edited by Admin
on 2024/12/13 12:26
Change comment: There is no comment for this version
To version 8.1
edited by Admin
on 2024/12/25 14:04
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -1,6 +1,28 @@
1 +(% class="box infomessage" %)
2 +(((
3 +BMS Main 3X firmware update procedure is described [[here>>doc:Battery management systems.BMS Main 3.5\. Firmware update.WebHome]].
4 +)))
5 +
6 += v3.2.0 =
7 +
1 1  (% class="wikigeneratedid" %)
2 -BMS Main 3X firmware update procedure is described [[here>>url:https://docs.movicomelectric.com/bin/view/Battery%20management%20systems/BMS%20Main%203/5.%20Firmware%20update/]].
9 +[[BMS_Main_3X_v3.2.0.bin>>FileManager.BMS_Main_3X_v3\.2\.0\.bin]]
3 3  
11 +== Features ==
12 +
13 +* new algorithm in the Charging/Discharging controller that allow to control the Charging/Discharging contactor independently from the Charging and Discharging signals (see the "Control - Charge/Discharge" section). The new "Independent" algorithm is preferred in the battery systems with one contactor
14 +* new "Need acknowledge" warning signal that is set when a new record is created in the errors journal. The signal can be cleared in the "Service - Errors journal" section
15 +* new Max-Min algorithm for calculating the final battery SOC in the "Control - Calculation" section
16 +* improved control of the precharging contactor, which can precharge capacitive load using multiple attempts and detect high power dissipated in the precharge resistor (see the "Control - Precharge" section)
17 +* ability to select errors that the device saves in the errors journal (see the "Service - Errors journal" section)
18 +
19 +== Improvements ==
20 +
21 +* ability to finish device initialization even if the number of battery modules found is less than the number of modules enabled
22 +* ability to configure and monitor the device via the CAN1 (ext) bus
23 +* placing the device input signals to the "Battery" section and adding raw discrete inputs to the "Signals" section
24 +* Unibat: support for functional description v3.5 (protocol v1.5)
25 +
4 4  = v3.1.1 =
5 5  
6 6  [[BMS_Main_3X_v3.1.1.bin>>FileManager.BMS_Main_3X_v3\.1\.1\.bin]]