Wiki source code of BMS Main 3

Version 6.1 by Admin on 2024/12/11 12:48

Show last authors
1 (% class="wikigeneratedid" %)
2 BMS Main 3 firmware upgrade procedure is described [[here>>doc:Battery management systems.BMS Main 3.5\. Firmware update.WebHome]].
3
4 = v2.1.1 =
5
6 [[BMS_Main_3_v2.1.1.bin>>FileManager.BMS_Main_3_v2\.1\.1\.bin]]
7
8 == Improvements ==
9
10 * new balancing strategy that attempts to keep the temperature of BMS Logic devices below a set value by discharging cells with higher voltages first than others (see the "Control - Cell balancing" section)
11
12 == Fixes ==
13
14 * resolving the possible problem of saving device parameters
15 * resolving the problem of writing the device's working time to a non-volatile memory very often
16
17 = v2.1.0 =
18
19 [[BMS_Main_3_v2.1.0.bin>>FileManager.BMS_Main_3_v2\.1\.0\.bin]]
20
21 == Features ==
22
23 * new algorithms in the Charging/Discharging controller that allow to control the Charging/Discharging contactor independently from the Charging and Discharging signals (see the "Control - Charge/Discharge" section). The new "Independent" algorithms are preferred in the battery systems with one contactor.
24 * selection of errors that cause reset of contactor control signals (see the "Control - Main contactor", "Control - Charge", "Control - Discharge", "Control - Charge/Discharge", "Control - Discharge (AUX)", "Control - Heater", "Control - Cooler", "Protections - General error", "Control - Charging status", "Control - Discharging status" sections)
25 * new "Current limit error" which is set if the battery current exceeds the charging or discharging current limits (see the "Protections - Charge current limit" and "Protections - Discharge current limit" sections)
26 * new parameter to select the method of calculating the battery voltage: sum the cell voltages or use the measured voltage before contactors (see the "Control - Common settings" section)
27 * clearing the Discharging (AUX) signal if the cell voltage is too low (see the "Control - Discharge (AUX)" section)
28 * new assignment "Close External 1" for the discrete inputs (see the "Signals - Input discrete signals - Assignments" section)
29 * new assignment "External 1" for the discrete outputs and power switches (see the "Signals - Output discrete signals - Assignments" and "Signals - Power switches - Assignments" sections). The "External 1" output is directly controlled by the "Close External 1" command.
30
31 == Improvements ==
32
33 * rearrangements in the settings sections, which are made to simplify the setup process