author | version | line-number | content |
---|---|---|---|
1 | (% class="box infomessage" %) | ||
2 | ((( | ||
3 | BMS Main 3 firmware update procedure is described [[here>>doc:Battery management systems.BMS Main 3.5\. Firmware update.WebHome]]. | ||
4 | ))) | ||
5 | |||
6 | = v2.2.1 = | ||
7 | |||
8 | ... | ||
9 | |||
10 | == Improvements == | ||
11 | |||
12 | * increasing the smoothness of changing the current limit values | ||
13 | * ability to exclude errors from being saved in the error journal (see the "Service - Errors journal" section) | ||
14 | * extension of the CANopen dictionary to provide additional information for the BMS Display (device serial number, battery serial number, battery address, Wi-Fi and LAN addresses, SOH, capacity, etc.) | ||
15 | |||
16 | == Fixes == | ||
17 | |||
18 | * resolving the issue of working with the Fronius charger over the CAN1 interface | ||
19 | * small internal fixes | ||
20 | |||
21 | = v2.2.0 = | ||
22 | |||
23 | [[BMS_Main_3_v2.2.0.bin>>FileManager.BMS_Main_3_v2\.2\.0\.bin]] | ||
24 | |||
25 | == Features == | ||
26 | |||
27 | * support for the HYG Global CAN protocol version 2 (June 13, 2024) | ||
28 | * calculation of regenerated energy | ||
29 | * calculation of new lifetime parameters: average temperature, average charge/discharge currents, etc. See the counters in the "Service - Counters" section | ||
30 | * new "Need acknowledge" warning signal that is set when a new record is created in the errors journal. The signal can be cleared in the "Service - Errors journal" section | ||
31 | * new parameter for setting the condition for starting balancing: automatically (regardless of the command) or on the balancing request (see the "Control - Cell balancing" section) | ||
32 | * new option to start balancing if the cell voltage exceeds the "Voltage for forced balancing" value (see the "Control - Cell balancing" section) | ||
33 | * new Max-Min algorithm for calculating the final battery SOC in the "Control - SOC estimation" section | ||
34 | * new flags in the "Protections - Undervoltage" and "Protections - Overvoltage" sections which allow using the calculated open circuit cell voltage instead of the actual voltage to detect the "Undervoltage" and "Overvoltage" errors, respectively | ||
35 | * ability to check the "Ready to charge" and "Ready to discharge" signals to control the charging and discharging contactors (see the "Control - Charge" and "Control - Discharge" sections) | ||
36 | * improved control of the precharging contactor, which can precharge capacitive load using multiple attempts and detect high power dissipated in the precharge resistor (see the "Control - Precharge" section) | ||
37 | * ability to select errors that the device saves in the errors journal (see the "Service - Errors journal" section) | ||
38 | |||
39 | == Improvements == | ||
40 | |||
41 | * ability to configure and monitor the device via the CAN1 (ext) bus | ||
42 | * placing the device input signals to the "Battery" section and adding raw discrete inputs to the "Signals" section | ||
43 | |||
44 | == Fixes == | ||
45 | |||
46 | * using the calculated open circuit voltage to set/clear the "Ready to charge" and "Ready to discharge" signals | ||
47 | |||
48 | = v2.1.1 = | ||
49 | |||
50 | [[BMS_Main_3_v2.1.1.bin>>FileManager.BMS_Main_3_v2\.1\.1\.bin]] | ||
51 | |||
52 | == Improvements == | ||
53 | |||
54 | * new balancing strategy that attempts to keep the temperature of BMS Logic devices below a set value by discharging cells with higher voltages first than others (see the "Control - Cell balancing" section) | ||
55 | |||
56 | == Fixes == | ||
57 | |||
58 | * resolving the possible problem of saving device parameters | ||
59 | * resolving the problem of writing the device's working time to a non-volatile memory very often | ||
60 | |||
61 | = v2.1.0 = | ||
62 | |||
63 | [[BMS_Main_3_v2.1.0.bin>>FileManager.BMS_Main_3_v2\.1\.0\.bin]] | ||
64 | |||
65 | == Features == | ||
66 | |||
67 | * new algorithms in the Charging/Discharging controller that allow to control the Charging/Discharging contactor independently from the Charging and Discharging signals (see the "Control - Charge/Discharge" section). The new "Independent" algorithms are preferred in the battery systems with one contactor. | ||
68 | * selection of errors that cause reset of contactor control signals (see the "Control - Main contactor", "Control - Charge", "Control - Discharge", "Control - Charge/Discharge", "Control - Discharge (AUX)", "Control - Heater", "Control - Cooler", "Protections - General error", "Control - Charging status", "Control - Discharging status" sections) | ||
69 | * new "Current limit error" which is set if the battery current exceeds the charging or discharging current limits (see the "Protections - Charge current limit" and "Protections - Discharge current limit" sections) | ||
70 | * new parameter to select the method of calculating the battery voltage: sum the cell voltages or use the measured voltage before contactors (see the "Control - Common settings" section) | ||
71 | * clearing the Discharging (AUX) signal if the cell voltage is too low (see the "Control - Discharge (AUX)" section) | ||
72 | * new assignment "Close External 1" for the discrete inputs (see the "Signals - Input discrete signals - Assignments" section) | ||
73 | * new assignment "External 1" for the discrete outputs and power switches (see the "Signals - Output discrete signals - Assignments" and "Signals - Power switches - Assignments" sections). The "External 1" output is directly controlled by the "Close External 1" command. | ||
74 | |||