Wiki source code of BMS Main 2.1

Last modified by Admin on 2025/04/14 10:35

Hide last authors
Admin 7.1 1 (% class="box infomessage" %)
2 (((
Admin 5.1 3 BMS Main 2.1 firmware update procedure is described [[here>>doc:Battery management systems.BMS Main 2\.1.4\. Firmware update.WebHome]].
Admin 7.1 4 )))
Admin 4.1 5
Admin 12.1 6 = v1.70.1 =
7
8 [[BMS_Main_2.1_v1.70.1.srec>>FileManager.BMS_Main_2\.1_v1\.70\.1\.srec]]
9
10 == Improvements ==
11
12 * new assignments "Low SOC" and "High charging current" for relays
13
14 == Fixes ==
15
16 * resolving the issue of ill-considered reduction of the battery SOC level when the cell voltage is close to the level corresponding to SOC=0% (due to the flow of a large discharge current leading to the high voltage drop on the cells)
17
Admin 10.1 18 = v1.70.0 =
19
20 [[BMS_Main_2.1_v1.70.0.srec>>FileManager.BMS_Main_2\.1_v1\.70\.0\.srec]]
21
22 == Features ==
23
Admin 11.1 24 * new parameters allowing to set different delays for battery discharge mode to detect the overcurrent error (see the "Protections - Overcurrent protection" section)
Admin 10.1 25 * new flag that sets whether the BMS should wait for confirmation messages from the Combilift truck to start charging or not (see the "External equipment - Combilift truck" section)
26
27 == Fixes ==
28
29 * optimization of the logging process, minimizing the time to open the next log file if the current one is full
30
Admin 9.1 31 = v1.69.1 =
32
33 [[BMS_Main_2.1_v1.69.1.srec>>FileManager.BMS_Main_2\.1_v1\.69\.1\.srec]]
34
35 == Fixes ==
36
37 * check the HYG and Combilift confirmation flags only if the truck offline error is not set
38 * small internal fixes
39
Admin 8.1 40 = v1.69.0 =
41
42 [[BMS_Main_2.1_v1.69.0.srec>>FileManager.BMS_Main_2\.1_v1\.69\.0\.srec]]
43
44 == Features ==
45
46 * new parameter for setting the condition for starting balancing: automatically (regardless of the command) or on the balancing request (see the "Cells - Cell balancing" section)
47 * new option to start balancing if the cell voltage exceeds the "Voltage for forced balancing" value (see the "Cells - Cell balancing" section)
48 * new assignment "Balancing request" for the discrete inputs (see the "Signals - Input signals" section)
49 * new Max-Min algorithm for calculating the final battery SOC in the "Cells - SOC estimation" section
50 * new algorithms "Automatic" and "On command" for the main contactor (see the "Cells - Main contactor" section)
51 * new assignment "Close Main contactor" for the discrete inputs to close the main contactor by a command
52 * new assignment "Close External 1" for the discrete inputs (see the "Signals - Input signals" section)
53 * new assignment "External 1" for the discrete outputs and relays (see the "Signals - Output signals" section). The "External 1" output is directly controlled by the "Close External 1" command.
54 * new "Precharge error" flag that is set when precharging cannot be completed
55 * new flags in the "Protections - Undervoltage protection" and "Protections - Overvoltage protection" sections which allow using the calculated open circuit cell voltage instead of the actual voltage to detect the "Undervoltage" and "Overvoltage" errors, respectively
56 * ability to check the "Ready to charge" and "Ready to discharge" signals to control the charging and discharging contactors (see the "Cells - Charging control" and "Cells - Discharging control" sections)
57
58 == Improvements ==
59
60 * ignoring the "Need acknowledge" flag when generating Modbus input register 0x2128 ("Error")
61 * explicit flags to enable the use of the charging current limit for fast and/or normal charging when using the CCS Fast charge controller (see the "External equipment - CCS Fast charge controller" section)
62 * improving resistance calculation
63
64 == Fixes ==
65
66 * resolving the issue where the "Need acknowledge" signal is not set if any of the device errors are not acknowledged in the error journal
67 * using the calculated open circuit voltage to set/clear the "Ready to charge" and "Ready to discharge" signals
68
Admin 6.1 69 = v1.68.0 =
70
71 [[BMS_Main_2.1_v1.68.0.srec>>FileManager.BMS_Main_2\.1_v1\.68\.0\.srec]]
72
73 == Features ==
74
75 - support for charge/discharge cycling using XD Discharger (see the sections "External equipment - Battery cycling" and "External equipment - XD Discharger (cycling)")
76
Admin 3.1 77 = v1.67.0 =
78
79 [[BMS_Main_2.1_v1.67.0.srec>>FileManager.BMS_Main_2\.1_v1\.67\.0\.srec]]
80
81 == Features ==
82
83 * new additional heater controller (see the "Protections - Heater (AUX) control" section), which generates the "Heater (AUX)" signal, which can be assigned to a discrete output or relay
84
85 == Improvements ==
86
87 * new balancing strategy that attempts to keep the temperature of BMS Logic devices below a set value by discharging cells with higher voltages first than others (see the "Cells - Cell balancing" section)
88
89 = v1.66.1 =
90
91 [[BMS_Main_2.1_v1.66.1.srec>>FileManager.BMS_Main_2\.1_v1\.66\.1\.srec]]
92
93 == Improvements ==
94
95 * closing all TCP connections over Ethernet if the interface link is down
96
Admin 2.1 97 = v1.66.0 =
Admin 1.2 98
99 [[BMS_Main_2.1_v1.66.0.srec>>FileManager.BMS_Main_2\.1_v1\.66\.0\.srec]]
100
Admin 2.1 101 == Features ==
102
103 * support for the insulation monitoring device BMS IMD (see the section "External equipment - BMS IMD device")
104