Wiki source code of 1. Technical specifications
Last modified by Admin on 2025/05/13 17:17
Hide last authors
author | version | line-number | content |
---|---|---|---|
![]() |
1.1 | 1 | (% data-numbered-headings-start="1" style="--numbered-headings-start: 0;font-size: 0px;color: rgba(0, 0, 0, 0.0);margin-bottom: 0px; margin-top: 0px;" %) |
![]() |
2.1 | 2 | = Technical specifications = |
![]() |
1.1 | 3 | |
![]() |
4.1 | 4 | [[image:1734098550308-137.png||data-xwiki-image-style-alignment="center" height="251" width="450"]]BMS Mini is a miniature full-featured centralized BMS for high-capacity lithium-ion batteries. It has many communication interfaces, an ability to collect information during the entire battery lifetime and an integrated DC/DC converter. |
![]() |
1.1 | 5 | |
6 | == Specifications == | ||
7 | |||
![]() |
11.1 | 8 | (% style="width:642px" %) |
9 | |(% style="width:402px" %)**Parameter**|(% style="width:237px" %)**Value** | ||
![]() |
16.1 | 10 | |(% style="width:402px" %)Battery voltage, V|(% style="width:237px" %)16 to 78 |
![]() |
11.1 | 11 | |(% style="width:402px" %)((( |
![]() |
1.1 | 12 | Current consumption @48 V, mA (maximum): |
![]() |
6.1 | 13 | |
14 | * work (no load) | ||
15 | * standby | ||
![]() |
11.1 | 16 | )))|(% style="width:237px" %)((( |
![]() |
6.1 | 17 | |
![]() |
1.1 | 18 | |
19 | 30 | ||
20 | 0.2 | ||
21 | ))) | ||
![]() |
11.1 | 22 | |(% style="width:402px" %)Number of cells|(% style="width:237px" %)6 to 18 |
23 | |(% style="width:402px" %)Cell balancing type|(% style="width:237px" %)Passive | ||
24 | |(% style="width:402px" %)Cell balancing current, mA, @ 4.2 V|(% style="width:237px" %)220 | ||
![]() |
17.1 | 25 | |(% style="width:402px" %)Cell voltage measurement error, V|(% style="width:237px" %)±0.004 |
26 | |(% style="width:402px" %)Cell temperature measurement error, °С|(% style="width:237px" %)±2 | ||
![]() |
11.1 | 27 | |(% style="width:402px" %)Output voltage of the internal DC/DC converter, V|(% style="width:237px" %)12 ± 1 |
28 | |(% style="width:402px" %)Output current of the internal DC/DC converter, A (maximum)|(% style="width:237px" %)3 | ||
![]() |
16.1 | 29 | |(% style="width:402px" %)Number of programmable MOSFETs for contactors (40V, 5A)|(% style="width:237px" %)4 |
![]() |
11.1 | 30 | |(% style="width:402px" %)Number of programmable discrete inputs (dry contact)|(% style="width:237px" %)4 |
![]() |
16.1 | 31 | |(% style="width:402px" %)Number of programmable discrete outputs (5V, total 200mA)|(% style="width:237px" %)4 |
![]() |
11.1 | 32 | |(% style="width:402px" %)Type of the current sensor|(% style="width:237px" %)Hall-Effect sensor, bidirectional, (LEM series: HASS, HTFS, DHAB) |
33 | |(% style="width:402px" %)Wired interfaces|(% style="width:237px" %)1xCAN / 1xRS-485 / 1xUSB | ||
![]() |
12.1 | 34 | |CAN output voltage, V|5.0 ± 0.5 |
35 | |CAN output current, mA (maximum)|400 | ||
![]() |
11.1 | 36 | |(% style="width:402px" %)Dimensions (length × width × height), mm|(% style="width:237px" %)140 × 117 × 17 |
![]() |
16.1 | 37 | |(% style="width:402px" %)Weight, g|(% style="width:237px" %)240 ± 20 |
![]() |
11.1 | 38 | |(% style="width:402px" %)Operating temperature range, °С|(% style="width:237px" %)-40 to +85 |
39 | |(% style="width:402px" %)Headers X1, X3-X9 type|(% style="width:237px" %)Molex series Micro-Fit | ||
![]() |
1.1 | 40 | |
![]() |
2.1 | 41 | == Overall and mounting dimensions == |
![]() |
1.1 | 42 | |
![]() |
20.1 | 43 | [[image:1747156650558-343.png||data-xwiki-image-style-alignment="center" height="487" width="450"]] |
![]() |
1.1 | 44 | |
45 | == Typical battery system == | ||
46 | |||
![]() |
4.1 | 47 | Typical battery system based on the BMS Mini is shown on figure below. |
![]() |
1.1 | 48 | |
49 | [[image:1733738121167-480.png]] | ||
50 | |||
51 |