... ... @@ -252,6 +252,32 @@ 252 252 If there is the "Battery cover error", the **“Critical error” **is generated. 253 253 ))) 254 254 255 +=== High board temperature === 256 + 257 +BMS Mini monitors its temperature and disables the cell balancing when it overheats. 258 + 259 +To change the overheating protection parameters of BMS Mini device, select the "Protections → High board temperature" section: 260 + 261 + 262 +In this section: 263 + 264 +* Enable – a flag to enable the protection; 265 +* Maximum temperature, °C; 266 +* Tolerant temperature, °C; 267 +* Delay before setting the error, second; 268 +* Delay before clearing the error, second; 269 +* Lock – lock the error until the device is reset. 270 + 271 +As a result of the operation of the protection from high temperatures of BMS Mini device, the "High board temperature" is generated. 272 + 273 +Error generation conditions: 274 + 275 +* a BMS Mini device temperature is higher than the “Maximum temperature” value. 276 + 277 +Conditions for removing the error: 278 + 279 +* a BMS Mini device temperature is less than the “Tolerant temperature” value. 280 + 255 255 === Cell monitor offline === 256 256 257 257 The BMS Mini device checks if there is connection with cell monitor and set an error if not.