Changes for page 3.4 Protections
Last modified by Admin on 2025/04/09 12:23
Summary
-
Page properties (1 modified, 0 added, 0 removed)
-
Attachments (0 modified, 0 added, 1 removed)
Details
- Page properties
-
- Content
-
... ... @@ -573,6 +573,21 @@ 573 573 * Delay before clearing the error, second; 574 574 * Lock – a flag to block the error until the device is restarted. 575 575 576 -The "Critical error"signal is generated if at least one of thecritical errors (see [[Errors>>doc:Battery management systems.Additional information.1\. Battery controllers\: signalsanderrors.WebHome||anchor="HErrors"]])is generated during the “Delay before setting the error” time.576 +The critical error flag is generated if at least one of the following errors is generated during the “Delay before setting the error” time: 577 577 578 +* “Battery cover error”; 579 +* “Cell monitor offline”; 580 +* “Cell count error”; 581 +* “ADC error”; 582 +* “Current sensor error”; 583 +* “Shunt offline”; 584 +* “Shunt error”; 585 +* “No temp. sensors”; 586 +* “Temp. sensor is shorted”; 587 +* “Settings error”; 588 +* “WDT reset”; 589 +* “Stuck contactor”; 590 +* “Contactor feedback error”; 591 +* “Insulation fault”. 592 + 578 578 The “Critical error” is cleared if there are no errors from the list above during the “Delay before clearing the error” time.
- 1740573914327-561.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.admin - Size
-
... ... @@ -1,1 +1,0 @@ 1 -19.6 KB - Content