... ... @@ -573,6 +573,21 @@
573 573  * Delay before clearing the error, second;
574 574  * Lock – a flag to block the error until the device is restarted.
575 575  
576 -The "Critical error" signal is generated if at least one of the critical errors (see [[Errors>>doc:Battery management systems.Additional information.1\. Battery controllers\: signals and errors.WebHome||anchor="HErrors"]]) is generated during the “Delay before setting the error” time.
576 +The critical error flag is generated if at least one of the following errors is generated during the “Delay before setting the error” time:
577 577  
578 +* “Battery cover error”;
579 +* “Cell monitor offline”;
580 +* “Cell count error”;
581 +* “ADC error”;
582 +* “Current sensor error”;
583 +* “Shunt offline”;
584 +* “Shunt error”;
585 +* “No temp. sensors”;
586 +* “Temp. sensor is shorted”;
587 +* “Settings error”;
588 +* “WDT reset”;
589 +* “Stuck contactor”;
590 +* “Contactor feedback error”;
591 +* “Insulation fault”.
592 +
578 578  The “Critical error” is cleared if there are no errors from the list above during the “Delay before clearing the error” time.