Changes for page 3.4 Protections
Last modified by Admin on 2025/04/09 12:23
Summary
-
Page properties (1 modified, 0 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -43,7 +43,6 @@ 43 43 * the current is positive (charging) or zero, and its modulo value is less than the “Tolerant charging current” value for the “Delay before clearing the error” time; 44 44 * the current is negative (discharging), and its modulo value is less than the “Tolerant discharging current” value for the “Delay before clearing the error” time. 45 45 46 - 47 47 === Undervoltage === 48 48 49 49 The BMS Mini device implements battery protection from too low voltage on the cells. ... ... @@ -71,7 +71,6 @@ 71 71 72 72 * the minimum voltage among all cells of the battery is greater than the “Tolerant cell voltage” value for the “Delay before clearing the error” time. 73 73 74 - 75 75 === Overvoltage === 76 76 77 77 The BMS Mini device implements battery protection from too high voltage on the cells. ... ... @@ -211,7 +211,7 @@ 211 211 212 212 (% class="box warningmessage" %) 213 213 ((( 214 -If there is the " Cell monitor offline error", the **“Critical error” **is generated and** all contactors open.**212 +If there is the " Cell monitor offline error", the **“Critical error” **is generated. 215 215 ))) 216 216 217 217 === Cell count === ... ... @@ -240,7 +240,7 @@ 240 240 241 241 (% class="box warningmessage" %) 242 242 ((( 243 -If there is the "Cell count error", the **“Critical error” **is generated and **all contactors open.**241 +If there is the "Cell count error", the **“Critical error” **is generated. 244 244 ))) 245 245 246 246 === Short circuit === ... ... @@ -272,11 +272,6 @@ 272 272 273 273 * the current modulo is lower than the “Maximum current” values for all three protection levels during the “Delay before setting the error” time. 274 274 275 -(% class="box infomessage" %) 276 -((( 277 -If there is the "Short circuit" error, the **charging **contactor opens (the “Switch off the charging contactor on error” flag is set) and the **discharging **contactor opens (the “Switch off the discharging contactor on error flag” is set). 278 -))) 279 - 280 280 === High contactor temperature === 281 281 282 282 The BMS Mini device protects power contactors from overheating. To measure the temperature of the contactor, one of the thermistors connected to the X6 connector is used. ... ... @@ -340,7 +340,7 @@ 340 340 341 341 (% class="box warningmessage" %) 342 342 ((( 343 -If there is the “Current sensor error”, the **“Critical error” **is generated and** all contactors open.**336 +If there is the “Current sensor error”, the **“Critical error” **is generated. 344 344 ))) 345 345 346 346 === Charge contactor cycles === ... ... @@ -371,11 +371,6 @@ 371 371 372 372 * the “Delay before clearing the error” time has passed since the error was generated. 373 373 374 -(% class="box infomessage" %) 375 -((( 376 -If there is the "CH contactor cycles error" error, the **charging** contactor opens. 377 -))) 378 - 379 379 === Discharge contactor cycles protection === 380 380 381 381 The BMS Mini device protects the discharging contactor against frequent switching. ... ... @@ -404,11 +404,6 @@ 404 404 405 405 * the “Delay before clearing the error” time has passed since the error was generated. 406 406 407 -(% class="box infomessage" %) 408 -((( 409 -If there is the "DCH contactor cycles error" error, the **discharging **contactor opens. 410 -))) 411 - 412 412 === Temperature sensors === 413 413 414 414 The BMS Mini device checks the temperature sensors connection circuits. The circuits are checked for breakage and short-circuit. ... ... @@ -428,7 +428,7 @@ 428 428 429 429 (% class="box warningmessage" %) 430 430 ((( 431 -If there is the “No temp. sensors” or “Temp. sensor is shorted” error, the **“Critical error” **is generated and **all contactors open.**414 +If there is the “No temp. sensors” or “Temp. sensor is shorted” error, the **“Critical error” **is generated. 432 432 ))) 433 433 434 434 === WDT reset === ... ... @@ -451,7 +451,7 @@ 451 451 452 452 (% class="box warningmessage" %) 453 453 ((( 454 -If there is the "WDT reset" error, the **“Critical error” **is generated and **all contactors open.**437 +If there is the "WDT reset" error, the **“Critical error” **is generated. 455 455 ))) 456 456 457 457 === Unallowable charging === ... ... @@ -479,11 +479,6 @@ 479 479 480 480 * the battery current is zero during the “Delay before clearing the error” time. 481 481 482 -(% class="box infomessage" %) 483 -((( 484 -If there is the "Unallowable charging" error, the **discharging **contactor opens. 485 -))) 486 - 487 487 === Stuck contactor === 488 488 489 489 The BMS Mini device protects contactors against sticking. ... ... @@ -499,7 +499,7 @@ 499 499 * Delay before clearing the error, second; 500 500 * Lock – a flag to block the error until the device is restarted. 501 501 502 -If there is a stuck contactor, the “Stuck contactor” error is generated Error generation conditions: 480 +If there is a stuck contactor, the “Stuck contactor” error is generated. Error generation conditions: 503 503 504 504 * charging and discharging contactors are open, but the “Charging current present” or “Discharging current present” signal is set. 505 505 ... ... @@ -570,8 +570,3 @@ 570 570 * “Insulation fault”. 571 571 572 572 The “Critical error” is cleared if there are no errors from the list above during the “Delay before clearing the error” time. 573 - 574 -(% class="box warningmessage" %) 575 -((( 576 -If there is the “Critical error”, **all contactors open.** 577 -)))