Changes for page 3.4 Protections

Last modified by Admin on 2025/04/09 12:23

From version 1.5
edited by Admin
on 2025/02/24 14:08
Change comment: There is no comment for this version
To version 1.6
edited by Admin
on 2025/02/24 14:09
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -43,10 +43,6 @@
43 43  * the current is positive (charging) or zero, and its modulo value is less than the “Tolerant charging current” value for the “Delay before clearing the error” time;
44 44  * the current is negative (discharging), and its modulo value is less than the “Tolerant discharging current” value for the “Delay before clearing the error” time.
45 45  
46 -(% class="box infomessage" %)
47 -(((
48 -If there is the "Overcurrent" error, the **charging **and **discharging **contactors open.
49 -)))
50 50  
51 51  === Undervoltage ===
52 52  
... ... @@ -75,10 +75,6 @@
75 75  
76 76  * the minimum voltage among all cells of the battery is greater than the “Tolerant cell voltage” value for the “Delay before clearing the error” time.
77 77  
78 -(% class="box infomessage" %)
79 -(((
80 -If there is the "Undervoltage" error, the **discharging **contactor opens.
81 -)))
82 82  
83 83  === Overvoltage ===
84 84  
... ... @@ -108,11 +108,6 @@
108 108  
109 109  * the maximum voltage among all cells of the battery is less than the “Tolerant cell voltage” value for the “Delay before clearing the error” time.
110 110  
111 -(% class="box infomessage" %)
112 -(((
113 -If there is the "Overvoltage" error, the **charging **contactor and **discharging **contactor open (if the “Switch off the discharging contactor on error” flag is set).
114 -)))
115 -
116 116  === Low temperature ===
117 117  
118 118  The BMS Mini device implements battery protection from too low temperature.
... ... @@ -142,11 +142,6 @@
142 142  
143 143  * the minimum temperature among all cells of the battery is greater than the “Tolerant charging (discharging) temperature” value for the “Delay before clearing the error” time.
144 144  
145 -(% class="box infomessage" %)
146 -(((
147 -If there is the "Low temperature (CH)" error, the **charging **contactor opens. If there is the "Low temperature (DCH)" error, the **discharging **contactor opens.
148 -)))
149 -
150 150  === High temperature ===
151 151  
152 152  The BMS Mini device implements battery protection from too high temperature.
... ... @@ -176,11 +176,6 @@
176 176  
177 177  * the maximum temperature among all cells of the battery is less than the “Tolerant charging (discharging) temperature” value for the “Delay before clearing the error” time.
178 178  
179 -(% class="box infomessage" %)
180 -(((
181 -If there is the "High temperature (CH)" error, the **charging **contactor opens. If there is the "High temperature (DCH)" error, the **discharging **contactor opens.
182 -)))
183 -
184 184  === Battery cover ===
185 185  
186 186  To change the protection parameters from opening the battery cover, select the "Protections → Battery cover" section:
... ... @@ -206,7 +206,7 @@
206 206  
207 207  (% class="box warningmessage" %)
208 208  (((
209 -If there is the "Battery cover error", the **“Critical error” **is generated **and all contactors open.**
186 +If there is the "Battery cover error", the **“Critical error” **is generated.
210 210  )))
211 211  
212 212  === Cell monitor offline ===