... ... @@ -43,11 +43,6 @@
43 43  * the current is positive (charging) or zero, and its modulo value is less than the “Tolerant charging current” value for the “Delay before clearing the error” time;
44 44  * the current is negative (discharging), and its modulo value is less than the “Tolerant discharging current” value for the “Delay before clearing the error” time.
45 45  
46 -(% class="box infomessage" %)
47 -(((
48 -If there is the "Overcurrent" error, the **charging **and **discharging **contactors open.
49 -)))
50 -
51 51  === Undervoltage ===
52 52  
53 53  The BMS Mini device implements battery protection from too low voltage on the cells.
... ... @@ -75,11 +75,6 @@
75 75  
76 76  * the minimum voltage among all cells of the battery is greater than the “Tolerant cell voltage” value for the “Delay before clearing the error” time.
77 77  
78 -(% class="box infomessage" %)
79 -(((
80 -If there is the "Undervoltage" error, the **discharging **contactor opens.
81 -)))
82 -
83 83  === Overvoltage ===
84 84  
85 85  The BMS Mini device implements battery protection from too high voltage on the cells.
... ... @@ -108,11 +108,6 @@
108 108  
109 109  * the maximum voltage among all cells of the battery is less than the “Tolerant cell voltage” value for the “Delay before clearing the error” time.
110 110  
111 -(% class="box infomessage" %)
112 -(((
113 -If there is the "Overvoltage" error, the **charging **contactor and **discharging **contactor open (if the “Switch off the discharging contactor on error” flag is set).
114 -)))
115 -
116 116  === Low temperature ===
117 117  
118 118  The BMS Mini device implements battery protection from too low temperature.
... ... @@ -142,11 +142,6 @@
142 142  
143 143  * the minimum temperature among all cells of the battery is greater than the “Tolerant charging (discharging) temperature” value for the “Delay before clearing the error” time.
144 144  
145 -(% class="box infomessage" %)
146 -(((
147 -If there is the "Low temperature (CH)" error, the **charging **contactor opens. If there is the "Low temperature (DCH)" error, the **discharging **contactor opens.
148 -)))
149 -
150 150  === High temperature ===
151 151  
152 152  The BMS Mini device implements battery protection from too high temperature.
... ... @@ -176,11 +176,6 @@
176 176  
177 177  * the maximum temperature among all cells of the battery is less than the “Tolerant charging (discharging) temperature” value for the “Delay before clearing the error” time.
178 178  
179 -(% class="box infomessage" %)
180 -(((
181 -If there is the "High temperature (CH)" error, the **charging **contactor opens. If there is the "High temperature (DCH)" error, the **discharging **contactor opens.
182 -)))
183 -
184 184  === Battery cover ===
185 185  
186 186  To change the protection parameters from opening the battery cover, select the "Protections → Battery cover" section:
... ... @@ -206,7 +206,7 @@
206 206  
207 207  (% class="box warningmessage" %)
208 208  (((
209 -If there is the "Battery cover error", the **“Critical error” **is generated **and all contactors open.**
184 +If there is the "Battery cover error", the **“Critical error” **is generated.
210 210  )))
211 211  
212 212  === Cell monitor offline ===
... ... @@ -234,7 +234,7 @@
234 234  
235 235  (% class="box warningmessage" %)
236 236  (((
237 -If there is the " Cell monitor offline error", the **“Critical error” **is generated and** all contactors open.**
212 +If there is the " Cell monitor offline error", the **“Critical error” **is generated.
238 238  )))
239 239  
240 240  === Cell count ===
... ... @@ -263,7 +263,7 @@
263 263  
264 264  (% class="box warningmessage" %)
265 265  (((
266 -If there is the "Cell count error", the **“Critical error” **is generated and **all contactors open.**
241 +If there is the "Cell count error", the **“Critical error” **is generated.
267 267  )))
268 268  
269 269  === Short circuit ===
... ... @@ -295,11 +295,6 @@
295 295  
296 296  * the current modulo is lower than the “Maximum current” values for all three protection levels during the “Delay before setting the error” time.
297 297  
298 -(% class="box infomessage" %)
299 -(((
300 -If there is the "Short circuit" error, the **charging **contactor opens (the “Switch off the charging contactor on error” flag is set) and the **discharging **contactor opens (the “Switch off the discharging contactor on error flag” is set).
301 -)))
302 -
303 303  === High contactor temperature ===
304 304  
305 305  The BMS Mini device protects power contactors from overheating. To measure the temperature of the contactor, one of the thermistors connected to the X6 connector is used.
... ... @@ -363,7 +363,7 @@
363 363  
364 364  (% class="box warningmessage" %)
365 365  (((
366 -If there is the “Current sensor error”, the **“Critical error” **is generated and** all contactors open.**
336 +If there is the “Current sensor error”, the **“Critical error” **is generated.
367 367  )))
368 368  
369 369  === Charge contactor cycles ===
... ... @@ -394,11 +394,6 @@
394 394  
395 395  * the “Delay before clearing the error” time has passed since the error was generated.
396 396  
397 -(% class="box infomessage" %)
398 -(((
399 -If there is the "CH contactor cycles error" error, the **charging** contactor opens.
400 -)))
401 -
402 402  === Discharge contactor cycles protection ===
403 403  
404 404  The BMS Mini device protects the discharging contactor against frequent switching.
... ... @@ -427,11 +427,6 @@
427 427  
428 428  * the “Delay before clearing the error” time has passed since the error was generated.
429 429  
430 -(% class="box infomessage" %)
431 -(((
432 -If there is the "DCH contactor cycles error" error, the **discharging **contactor opens.
433 -)))
434 -
435 435  === Temperature sensors ===
436 436  
437 437  The BMS Mini device checks the temperature sensors connection circuits. The circuits are checked for breakage and short-circuit.
... ... @@ -451,7 +451,7 @@
451 451  
452 452  (% class="box warningmessage" %)
453 453  (((
454 -If there is the “No temp. sensors” or “Temp. sensor is shorted” error, the **“Critical error” **is generated and **all contactors open.**
414 +If there is the “No temp. sensors” or “Temp. sensor is shorted” error, the **“Critical error” **is generated.
455 455  )))
456 456  
457 457  === WDT reset ===
... ... @@ -474,7 +474,7 @@
474 474  
475 475  (% class="box warningmessage" %)
476 476  (((
477 -If there is the "WDT reset" error, the **“Critical error” **is generated and **all contactors open.**
437 +If there is the "WDT reset" error, the **“Critical error” **is generated.
478 478  )))
479 479  
480 480  === Unallowable charging ===
... ... @@ -502,11 +502,6 @@
502 502  
503 503  * the battery current is zero during the “Delay before clearing the error” time.
504 504  
505 -(% class="box infomessage" %)
506 -(((
507 -If there is the "Unallowable charging" error, the **discharging **contactor opens.
508 -)))
509 -
510 510  === Stuck contactor ===
511 511  
512 512  The BMS Mini device protects contactors against sticking.
... ... @@ -522,7 +522,7 @@
522 522  * Delay before clearing the error, second;
523 523  * Lock – a flag to block the error until the device is restarted.
524 524  
525 -If there is a stuck contactor, the “Stuck contactor” error is generated Error generation conditions:
480 +If there is a stuck contactor, the “Stuck contactor” error is generated. Error generation conditions:
526 526  
527 527  * charging and discharging contactors are open, but the “Charging current present” or “Discharging current present” signal is set.
528 528  
... ... @@ -593,8 +593,3 @@
593 593  * “Insulation fault”.
594 594  
595 595  The “Critical error” is cleared if there are no errors from the list above during the “Delay before clearing the error” time.