... ... @@ -74,9 +74,8 @@
74 74  * Invert – a flag to invert current values;
75 75  * Receive timeout – a timeout for receiving messages from BMS Current Sensor (if no data is being received from the current sensor during this time, the “Shunt offline” flag is set), millisecond;
76 76  * Mean value threshold – T,,M,, level, A (if module of instantaneous current (I,,I,,) which is received from the shunt sensor is between T,,M,, and T,,0,,, the BMS will use mean value of current I,,M,,; if I,,I,, is greater than T,,M,,, the BMS will use instantaneous value of current I,,I,,);
77 +* Zero threshold – T,,0,, level, A (if module of instantaneous current (I,,I,,) which is received from the shunt sensor is lower than T,,0,,, the BMS will assume that current flowing through the battery is zero);
77 77  
78 -Zero threshold – T,,0,, level, A (if module of instantaneous current (I,,I,,) which is received from the shunt sensor is lower than T,,0,,, the BMS will assume that current flowing through the battery is zero);
79 -
80 80  === Temperature sensor ===
81 81  
82 82  Temperature sensors settings are configured in the "Signals → Temperature sensors" section: