50 50  === ATIB charger ===
51 51  
52 52  To change the parameters of communication with an ATIB Elettronica charger, select the "External equipment → ATIB charger" section:
53 +
54 +[[image:1740996520416-882.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="120" width="800"]]
55 +
56 +In this section:
57 +
58 +* Enable – a flag to enable communication with the charger;
59 +* Receive timeout – a timeout for receiving packets from the charger (if there is no data being received from the charger for a given time, the connection loss flag is set), millisecond;
60 +* Output period - a period of sending commands to the charger, millisecond;
61 +* Charging voltage – maximum charging voltage, V;
62 +* Set “Charger connected” signal if the charger is online – a flag to generate the “Charger connected” signal if connection with the charger is established.
63 +
64 +(% class="box infomessage" %)
65 +(((
66 +After changing the settings, restart the BMS Main X device.
67 +)))
68 +
69 +=== BMS IMD ===
70 +
71 +To change communication parameters with an insulation monitoring device BMS IMD, select the "External equipment → BMD IMD " section:
72 +
73 +[[image:1740996567134-294.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="133" width="800"]]
74 +
75 +In this section:
76 +
77 +* Enable – a flag to enable communication with the IMD;
78 +* Node ID – a CANopen address of the BMS IMD device;
79 +* Configure IMD – a flag to override the IMD warning and alarm settings;
80 +* Allow work if battery modules are joined – a flag to allow the BMS IMD to work only if battery modules are joined;
81 +* Alarm threshold – a threshold resistance value to set insulation alarm, Ohm;
82 +* Warning threshold – a threshold resistance value to set insulation warning, Ohm.