Wiki source code of 3.4 Protections

Version 4.2 by Admin on 2025/02/28 14:54

Show last authors
1 (% data-numbered-headings-start="3" style="--numbered-headings-start: 2;font-size: 0px;color: rgba(0, 0, 0, 0.0);margin-bottom: 0px; margin-top: 0px;" %)
2 = Settings =
3
4 (% data-numbered-headings-start="4" style="--numbered-headings-start: 3;font-size: 0px;color: rgba(0, 0, 0, 0.0);margin-bottom: 0px; margin-top: 0px;" %)
5 == Protections ==
6
7 The BMS Main X monitors the battery modules, compares the voltages and currents of the modules, and protects the battery system from damage.
8
9 (% class="box errormessage" %)
10 (((
11 **Attention!**
12 Behavior of contactors at different errors is configured in **corresponding contactor settings**!
13 )))
14
15 === Charging current limit ===
16
17 The BMS Main X device protects the battery from charging current higher than estimated current limit.
18
19 To configure parameters of the charge current limit, select the "Protections → Charge current limit" section:
20
21 [[image:1740754371437-635.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="142" width="800"]]
22
23 In this section:
24
25 * Enable – a flag to enable the protection;
26 * Threshold to switch from Region 1 to Region 2 – a threshold current value, dividing regions 1 and 2 with their error generation conditions, A;
27 * Region 1: Current difference – an absolute difference of measured battery current and calculated value “Charge current limit”, at which error is generated (condition for Region 1), A;
28 * Region 2: Current difference – a relative difference of measured battery current and calculated value “Charge current limit”, at which error is generated (conditions for Region 2), %;
29 * Delay before setting the error, millisecond;
30 * Delay before clearing the error, second;
31 * Lock – a flag to block the error until the device is restarted.
32
33 As a result of the operation of the charging current limit protection, the “Current limit error (CH)” is generated.
34
35 Error generation conditions:
36
37 * if the current is positive, less than “Threshold to switch from Region 1 to Region 2” value and exceeds “Charge current limit” by the “Region 1: Current difference” value during the “Delay before setting the error” time;
38 * if the current is positive, more than “Threshold to switch from Region 1 to Region 2” value and exceeds “Charge current limit” by the (“Region 2: Current difference” × “Charge current limit”) / 100 value during the “Delay before setting the error” time.
39
40 Error is cleared if conditions for generating an error do not apply during the “Delay before clearing the error” time.
41
42 === Discharging current limit ===
43
44 The BMS Main X device protects the battery from discharging current higher than estimated current limit.
45
46 To configure parameters of the charge current limit, select the "Protections → Discharge current limit " section:
47
48 [[image:1740754420820-767.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="138" width="800"]]
49
50 In this section:
51
52 * Enable – a flag to enable the protection;
53 * Threshold to switch from Region 1 to Region 2 – a threshold current value, dividing regions 1 and 2 with their error generation conditions, A;
54 * Region 1: Current difference – an absolute difference of measured battery current and calculated value “Discharge current limit”, at which error is generated (condition for Region 1), A;
55 * Region 2: Current difference – a relative difference of measured battery current and calculated value “Discharge current limit”, at which error is generated (conditions for Region 2), %;
56 * Delay before setting the error, millisecond;
57 * Delay before clearing the error, second;
58 * Lock – a flag to block the error until the device is restarted.
59
60 As a result of the operation of the charging current limit protection, the “Current limit error (DCH)” is generated.
61
62 Error generation conditions:
63
64 * if the current is negative, and the current modulus is less than “Threshold to switch from Region 1 to Region 2” value and exceeds “Discharge current limit” by the “Region 1: Current difference” value during the “Delay before setting the error” time;
65 * if the current is negative, and the current modulus is more than “Threshold to switch from Region 1 to Region 2” value and exceeds “Discharge current limit” by the (“Region 2: Current difference” × “Discharge current limit”) / 100 value during the “Delay before setting the error” time.
66
67 Error is cleared if conditions for generating an error do not apply during the “Delay before clearing the error” time.
68
69 === Battery cover ===
70
71 The BMS Main X device detects the opening of the battery cover and performs a protective opening of the contactors.
72
73 Battery cover protection is configured in the "Protections - Battery cover" section:
74
75 [[image:1734356776691-451.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="88" width="800"]]
76
77 In this section:
78
79 * Enable – a flag to enable the protection;
80 * Delay before setting the error;
81 * Delay before clearing the error;
82 * Lock – a flag to block the error until the device is restarted.
83
84 As a result of the protection against opening the battery cover, the “Battery cover” error is generated. Conditions for generating the error:
85
86 * presence of the “Battery cover” signal during the “Delay before setting the error” time.
87
88 Conditions for clearing the error:
89
90 * no “Battery cover” signal during the “Delay before clearing the error” time.
91
92 (% class="box warningmessage" %)
93 (((
94 If there is the "Battery cover" error, the **"Critical error flag" is generated.**
95 )))
96
97 === Insulation ===
98
99 The BMS Main X device detects a signal from an external insulation monitoring device (e.g., Bender IR155) and performs a protective opening of the contactors.
100
101 Insulation protection is configured in the "Protections - Insulation" section:
102
103 [[image:1734356776694-257.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="68" width="600"]]
104
105 In this section:
106
107 * Enable – a flag to enable the protection;
108 * Delay before setting the error;
109 * Delay before clearing the error;
110 * Lock – a flag to block the error until the device is restarted.
111
112 As a result of the operation of the insulation fault protection, the error “Insulation fault” is generated. Conditions for generating the error:
113
114 * presence of the “Insulation status” signal during the “Delay before setting the error” time.
115
116 Conditions for clearing the error:
117
118 * no “Insulation status” signal during the “Delay before clearing the error” time.
119
120 (% class="box warningmessage" %)
121 (((
122 If there is the "Insulation fault" error, **the critical error flag is generated and all battery contactors open.**
123 )))
124
125 === Contactor feedback ===
126
127 The BMS Main X device detects the feedback signals from the main contactors and, in the event of a discrepancy between the feedback signals from the control signals, performs a protective opening of the contactors.
128
129 Contactor feedback protection is configured in the “Protections – Contactor feedback” section:
130
131 [[image:1734356776695-557.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="67" width="600"]]
132
133 In this section:
134
135 * Enable – a flag to enable the protection;
136 * Delay before setting the error;
137 * Delay before clearing the error;
138 * Lock – a flag to block the error until the device is restarted.
139
140 As a result of the protection against contactor failures, the errors "CH contactor feedback error", "DCH contactor feedback error", "CH/DCH contactor feedback error" are generated. Conditions for generating the errors:
141
142 * feedback signal from the contactor differs from the contactor control signal for the time "Delay before setting the error".
143
144 Conditions for clearing the error:
145
146 * feedback signal from the contactor repeats the contactor control signal for the time "Delay before clearing the error".
147
148 (% class="box warningmessage" %)
149 (((
150 If there is the “CH contactor feedback error”, “DCH contactor feedback error”, or “CH/DCH contactor feedback error”, **the critical error flag is generated and all battery contactors open.**
151 )))
152
153 === Module offline ===
154
155 The BMS Main X device detects the loss of communication with the battery modules and performs a protective opening of the contactors.
156
157 Protection against loss of communication with battery modules is configured in the "Protections - Module offline" section:
158
159 [[image:1734356793441-881.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="75" width="600"]]
160
161 In this section:
162
163 * Enable – a flag to enable the protection;
164 * Delay before setting the error;
165 * Delay before clearing the error;
166 * Lock – a flag to block the error until the device is restarted.
167
168 As a result of the protection against loss of communication with the battery module, the “Module offline” error is generated. Conditions for generating the error:
169
170 * at least one of the battery modules does not respond to commands within the "Delay before setting the error" time.
171
172 Conditions for clearing the error:
173
174 * all battery modules respond to commands within the "Delay before clearing the error" time.
175
176 (% class="box warningmessage" %)
177 (((
178 If there is the "Module offline" error, **the critical error flag is generated and all battery contactors open.**
179 )))
180
181 === Voltage unbalance ===
182
183 Before closing the contactors for charging and discharging battery modules, the BMS Main X device detects those modules whose voltage is significantly different from the rest. For unbalanced modules, errors "Voltage unbalance (CH)" (charge circuit) and "Voltage unbalance (DCH)" (discharge circuit) are generated.
184
185 Protection against voltage unbalance of battery modules is configured in the section "Protections - Voltage unbalance":
186
187 [[image:1734356793449-249.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="75" width="600"]]
188
189 In this section:
190
191 * Enable – a flag to enable the protection;
192 * Delta voltage – maximum allowable voltage difference of battery modules, V;
193 * Delay before setting the error;
194 * Delay before clearing the error;
195 * Lock – a flag to block the error until the device is restarted.
196
197 As a result of the operation of the voltage unbalance protection the errors “Voltage unbalance (CH)” and “Voltage unbalance (DCH)” are generated. Conditions for generating the error:
198
199 * battery module is not included in the largest group of modules whose voltages differ from each other by no more than "Delta voltage" during the "Delay before setting the error" time.
200
201 Conditions for clearing the error:
202
203 * battery module is in the largest group of balanced modules during the "Delay before clearing the error" time.
204
205 If there is the error "Voltage unbalance (CH)" ("Voltage unbalance (DCH)"), the charging (discharging) contactor of the battery module opens.
206
207 === Current unbalance ===
208
209 When battery modules are connected in parallel, the most charged modules transfer charge to the least charged modules. The process of charge transfer is accompanied by the flow of balancing currents. The BMS Main X device detects modules with high balancing currents and generates “Current unbalance (CH)” (charge circuit) and “Current unbalance (DCH)” (discharge circuit) errors for them.
210
211 Protection against current unbalance of battery modules is configured in the section "Protections - Current unbalance":
212
213 [[image:1734356793451-440.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="77" width="600"]]
214
215 In this section:
216
217 * Enable – a flag to enable the protection;
218 * Maximum current – a maximum allowable self-balancing current of battery modules, A;
219 * Delay before setting the error;
220 * Delay before clearing the error;
221 * Lock – a flag to block the error until the device is restarted.
222
223 As a result of the operation of the current unbalance protection the errors “Current unbalance (CH)” and “Current unbalance (DCH)” are generated. Conditions for generating the error:
224
225 * current of the battery module is greater than the "Maximum current" value during the "Delay before setting the error" time.
226
227 Conditions for clearing the error:
228
229 * current of the battery module is less than the "Maximum current" value during the "Delay before clearing the error" time.
230
231 If there is the error "Current unbalance (CH)" ("Current unbalance (DCH)"), the charging (discharging) contactor of the battery module opens.
232
233 === Charging current unbalance ===
234
235 During battery charging, the currents of the battery modules may vary. The BMS Main X device detects modules whose charging currents are significantly different from the currents of other modules and generates the “Charging current unbalance” errors for them.
236
237 Protection against different charge currents is configured in the "Protections – Charging current unbalance" section:
238
239 [[image:1734356802715-364.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="75" width="600"]]
240
241 In this section:
242
243 * Enable – a flag to enable the protection;
244 * Delta current – maximum allowable charge current difference, A;
245 * Delay before setting the error;
246 * Delay before clearing the error;
247 * Lock – a flag to block the error until the device is restarted.
248
249 As a result of the operation of the protection the “Charging current unbalance” are generated. Conditions for generating the errors:
250
251 * battery module is not included in the largest group of modules whose charge currents differ from each other by no more than "Delta current" during the "Delay before setting the error" time.
252
253 Conditions for clearing the error:
254
255 * battery module is included in the largest group of modules with similar charge currents during the “Delay before clearing the error” time.
256
257 If there is the “Charging current unbalance” error, the battery module charging contactor opens.
258
259 === Discharging current unbalance ===
260
261 During battery discharging, the currents of the battery modules may vary. The BMS Main X device detects modules whose discharging currents are significantly different from the currents of other modules and generates the “Discharging current unbalance” errors for them.
262
263 Protection against different discharge currents is configured in the "Protections – Discharging current unbalance" section:
264
265 [[image:1734356802717-812.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="75" width="600"]]
266
267 In this section:
268
269 * Enable – a flag to enable the protection;
270 * Delta current – maximum allowable discharge current difference, A;
271 * Delay before setting the error;
272 * Delay before clearing the error;
273 * Lock – a flag to block the error until the device is restarted.
274
275 As a result of the operation of the protection the “Discharging current unbalance” are generated. Conditions for generating the errors:
276
277 * battery module is not included in the largest group of modules whose discharge currents differ from each other by no more than "Delta current" during the "Delay before setting the error" time.
278
279 Conditions for clearing the error:
280
281 * battery module is included in the largest group of modules with similar discharge currents during the “Delay before clearing the error” time.
282
283 If there is the “Discharging current unbalance” error, the battery module discharging contactor opens.
284
285 === Critical error ===
286
287 Parameters for generating the critical error are configured in the "Protections - Critical error" section:
288
289 [[image:1734356802719-477.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="69" width="600"]]
290
291 In this section:
292
293 * Enable – a flag to enable the protection;
294 * Delay before setting the error;
295 * Delay before clearing the error;
296 * Lock – a flag to block the error until the device is restarted.
297
298 The critical error flag is generated if at least one of the following errors persists during the "Delay before setting the error" time:
299
300 * «Battery cover»;
301 * «Insulation fault»;
302 * «CH contactor feedback error»;
303 * «DCH contactor feedback error»;
304 * «CH/DCH contactor feedback error»;
305 * «Module offline».
306
307 The critical error flag is cleared if there are no errors from the list above during the "Delay before clearing the error" time.
308
309 (% class="box warningmessage" %)
310 (((
311 **When the critical error flag is present, all battery contactors open.**
312 )))