... ... @@ -154,68 +154,61 @@
154 154  
155 155  Protection against loss of communication with battery modules is configured in the "Protections - Module offline" section:
156 156  
157 -[[image:1740754588971-137.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="118" width="800"]]
157 +[[image:1734356793441-881.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="75" width="600"]]
158 158  
159 159  In this section:
160 160  
161 -* Enable – a flag to enable the protection;
162 -* Number of offline modules to set the error;
163 -* Delay before setting the error, second;
164 -* Delay before clearing the error, second;
165 -* Lock – lock the error until the device is reset.
161 +* Enable – a flag to enable the protection;
162 +* Delay before setting the error;
163 +* Delay before clearing the error;
164 +* Lock – a flag to block the error until the device is restarted.
166 166  
167 -As a result of the protection from loss of communication with battery modules, the "Module offline" error is generated.
166 +As a result of the protection against loss of communication with the battery module, the Module offline error is generated. Conditions for generating the error:
168 168  
169 -Error generation conditions:
168 +* at least one of the battery modules does not respond to commands within the "Delay before setting the error" time.
170 170  
171 -* more than “Number of offline modules to set the error battery modules do not respond to the commands of the BMS Main 3X device within “Delay before setting the error” time.
170 +Conditions for clearing the error:
172 172  
173 -Conditions for removing the error:
172 +* all battery modules respond to commands within the "Delay before clearing the error" time.
174 174  
175 -* less than “Number of offline modules to set the error” battery modules do not respond to the commands of the BMS Main 3X device within “Delay before clearing the error” time.
176 -
177 177  (% class="box warningmessage" %)
178 178  (((
179 -If there is the "Module offline" error, **“Critical error is generated.**
176 +If there is the "Module offline" error, **the critical error flag is generated and all battery contactors open.**
180 180  )))
181 181  
182 -=== Voltage unbalance (in any state) ===
179 +=== Voltage unbalance ===
183 183  
184 184  Before closing the contactors for charging and discharging battery modules, the BMS Main X device detects those modules whose voltage is significantly different from the rest. For unbalanced modules, errors "Voltage unbalance (CH)" (charge circuit) and "Voltage unbalance (DCH)" (discharge circuit) are generated.
185 185  
186 -Protection against voltage unbalance of battery modules is configured in the section "Protections - Voltage unbalance (in any state)":
183 +Protection against voltage unbalance of battery modules is configured in the section "Protections - Voltage unbalance":
187 187  
188 -[[image:1740754732291-420.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="127" width="800"]]
185 +[[image:1734356793449-249.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="75" width="600"]]
189 189  
190 190  In this section:
191 191  
192 192  * Enable – a flag to enable the protection;
193 193  * Delta voltage – maximum allowable voltage difference of battery modules, V;
194 -* Use the open circuit voltage to detect the error – a flag to enable U,,ocv,, correction;
195 195  * Delay before setting the error;
196 196  * Delay before clearing the error;
197 -* Set the 'Voltage unbalance' error for the modules that are not ready to charge/discharge;
198 198  * Lock – a flag to block the error until the device is restarted.
199 199  
200 -As a result of the operation of the voltage unbalance protection the errors “Voltage unbalance (CH)” and “Voltage unbalance (DCH)” are generated.
195 +As a result of the operation of the voltage unbalance protection the errors “Voltage unbalance (CH)” and “Voltage unbalance (DCH)” are generated. Conditions for generating the error:
201 201  
202 -Conditions for generating the error:
197 +* battery module is not included in the largest group of modules whose voltages differ from each other by no more than "Delta voltage" during the "Delay before setting the error" time.
203 203  
204 -* battery module is not included in the largest group of modules whose voltages differ from each other by no more than "Delta voltage" during the "Delay before setting the error" time;
205 -* module is not ready to charge or discharge;
206 -
207 207  Conditions for clearing the error:
208 208  
209 -* battery module is in the largest group of balanced modules during the "Delay before clearing the error" time;
210 -* module is ready to charge or discharge.
201 +* battery module is in the largest group of balanced modules during the "Delay before clearing the error" time.
211 211  
212 -=== Current unbalance (in “Balancing state) ===
203 +If there is the error "Voltage unbalance (CH)" ("Voltage unbalance (DCH)"), the charging (discharging) contactor of the battery module opens.
213 213  
205 +=== Current unbalance ===
206 +
214 214  When battery modules are connected in parallel, the most charged modules transfer charge to the least charged modules. The process of charge transfer is accompanied by the flow of balancing currents. The BMS Main X device detects modules with high balancing currents and generates “Current unbalance (CH)” (charge circuit) and “Current unbalance (DCH)” (discharge circuit) errors for them.
215 215  
216 216  Protection against current unbalance of battery modules is configured in the section "Protections - Current unbalance":
217 217  
218 -[[image:Battery management systems.BMS Main 3X.3\. Configuration.3\.4 Protections.WebHome@1734090244843-403.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="116" width="800"]]
211 +[[image:1734356793451-440.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="77" width="600"]]
219 219  
220 220  In this section:
221 221  
... ... @@ -223,23 +223,19 @@
223 223  * Maximum current – a maximum allowable self-balancing current of battery modules, A;
224 224  * Delay before setting the error;
225 225  * Delay before clearing the error;
226 -* Check all the time (not only in the ‘Balancing’ state) – a flag to enable voltage check not only in “Balancing” state;
227 227  * Lock – a flag to block the error until the device is restarted.
228 228  
229 229  As a result of the operation of the current unbalance protection the errors “Current unbalance (CH)” and “Current unbalance (DCH)” are generated. Conditions for generating the error:
230 230  
231 -* the current of the battery module is greater than the "Maximum current" value during the "Delay before setting the error" time.
223 +* current of the battery module is greater than the "Maximum current" value during the "Delay before setting the error" time.
232 232  
233 233  Conditions for clearing the error:
234 234  
235 -* the current of the battery module is less than the "Maximum current" value during the "Delay before clearing the error" time.
227 +* current of the battery module is less than the "Maximum current" value during the "Delay before clearing the error" time.
236 236  
237 -(% class="box infomessage" %)
238 -(((
239 -If there is the “Current unbalance (CH)” or "Current unbalance (DCH)" error, **corresponding battery module opens its charging or discharging contactor**.
240 -)))
229 +If there is the error "Current unbalance (CH)" ("Current unbalance (DCH)"), the charging (discharging) contactor of the battery module opens.
241 241  
242 -=== Charging current unbalance (in “Charging” state) ===
231 +=== Charging current unbalance ===
243 243  
244 244  During battery charging, the currents of the battery modules may vary. The BMS Main X device detects modules whose charging currents are significantly different from the currents of other modules and generates the “Charging current unbalance” errors for them.
245 245  
... ... @@ -263,10 +263,7 @@
263 263  
264 264  * battery module is included in the largest group of modules with similar charge currents during the “Delay before clearing the error” time.
265 265  
266 -(% class="box infomessage" %)
267 -(((
268 -If there is the “Charging current unbalance” error, **corresponding battery module opens its charging contactor**.
269 -)))
255 +If there is the “Charging current unbalance” error, the battery module charging contactor opens.
270 270  
271 271  === Discharging current unbalance ===
272 272  
... ... @@ -292,19 +292,8 @@
292 292  
293 293  * battery module is included in the largest group of modules with similar discharge currents during the “Delay before clearing the error” time.
294 294  
295 -(% class="box infomessage" %)
296 -(((
297 -If there is the “Discharging current unbalance” error, **corresponding battery module opens its discharging contactor**.
298 -)))
281 +If there is the “Discharging current unbalance” error, the battery module discharging contactor opens.
299 299  
300 -=== High contactor temperature ===
301 -
302 -=== WDT reset ===
303 -
304 -If the BMS firmware hangs, the watchdog timer resets the device. The BMS can detect that the device was reset and generates the “WDT reset” error.
305 -
306 -To change the parameters of the watchdog protection, select the "Protections → WDT reset" section:
307 -
308 308  === Critical error ===
309 309  
310 310  Parameters for generating the critical error are configured in the "Protections - Critical error" section:
1740754732291-420.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.admin
Size
... ... @@ -1,1 +1,0 @@
1 -25.4 KB
Content
1740756362809-292.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.admin
Size
... ... @@ -1,1 +1,0 @@
1 -20.4 KB
Content