Changes for page 3.4 Protections

Last modified by Admin on 2025/06/11 15:57

From version 8.3
edited by Admin
on 2025/02/28 15:23
Change comment: There is no comment for this version
To version 8.4
edited by Admin
on 2025/02/28 15:24
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -215,7 +215,7 @@
215 215  
216 216  Protection against current unbalance of battery modules is configured in the section "Protections - Current unbalance":
217 217  
218 -[[image:1734356793451-440.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="103" width="800"]]
218 +[[image:Battery management systems.BMS Main 3X.3\. Configuration.3\.4 Protections.WebHome@1734090244843-403.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="116" width="800"]]
219 219  
220 220  In this section:
221 221  
... ... @@ -234,9 +234,9 @@
234 234  
235 235  * the current of the battery module is less than the "Maximum current" value during the "Delay before clearing the error" time.
236 236  
237 -(% class="box warningmessage" %)
237 +(% class="box infomessage" %)
238 238  (((
239 -If there is the “Current unbalance” error, **corresponding battery module opens its discharging contactor**.
239 +If there is the “Current unbalance (CH)or "Current unbalance (DCH)" error, **corresponding battery module opens its charging or discharging contactor**.
240 240  )))
241 241  
242 242  === Charging current unbalance (in “Charging” state) ===
... ... @@ -297,6 +297,14 @@
297 297  If there is the “Discharging current unbalance” error, **corresponding battery module opens its discharging contactor**.
298 298  )))
299 299  
300 +=== ===
301 +
302 +=== WDT reset ===
303 +
304 +If the BMS firmware hangs, the watchdog timer resets the device. The BMS can detect that the device was reset and generates the “WDT reset” error.
305 +
306 +To change the parameters of the watchdog protection, select the "Protections → WDT reset" section:
307 +
300 300  === Critical error ===
301 301  
302 302  Parameters for generating the critical error are configured in the "Protections - Critical error" section: