Changes for page 3.4 Protections

Last modified by Admin on 2025/06/11 15:57

From version 8.2
edited by Admin
on 2025/02/28 15:22
Change comment: There is no comment for this version
To version 8.3
edited by Admin
on 2025/02/28 15:23
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -234,7 +234,10 @@
234 234  
235 235  * the current of the battery module is less than the "Maximum current" value during the "Delay before clearing the error" time.
236 236  
237 -If there is the error "Current unbalance (CH)" ("Current unbalance (DCH)"), the charging (discharging) contactor of the battery module opens.
237 +(% class="box warningmessage" %)
238 +(((
239 +If there is the “Current unbalance” error, **corresponding battery module opens its discharging contactor**.
240 +)))
238 238  
239 239  === Charging current unbalance (in “Charging” state) ===
240 240  
... ... @@ -260,7 +260,10 @@
260 260  
261 261  * battery module is included in the largest group of modules with similar charge currents during the “Delay before clearing the error” time.
262 262  
263 -If there is the “Charging current unbalance” error, the battery module charging contactor opens.
266 +(% class="box infomessage" %)
267 +(((
268 +If there is the “Charging current unbalance” error, **corresponding battery module opens its charging contactor**.
269 +)))
264 264  
265 265  === Discharging current unbalance ===
266 266  
... ... @@ -286,7 +286,10 @@
286 286  
287 287  * battery module is included in the largest group of modules with similar discharge currents during the “Delay before clearing the error” time.
288 288  
289 -If there is the “Discharging current unbalance” error, the battery module discharging contactor opens.
295 +(% class="box infomessage" %)
296 +(((
297 +If there is the “Discharging current unbalance” error, **corresponding battery module opens its discharging contactor**.
298 +)))
290 290  
291 291  === Critical error ===
292 292