Changes for page 3.4 Protections

Last modified by Admin on 2025/06/11 15:57

From version 8.2
edited by Admin
on 2025/02/28 15:22
Change comment: There is no comment for this version
To version 8.1
edited by Admin
on 2025/02/28 15:01
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -223,20 +223,19 @@
223 223  * Maximum current – a maximum allowable self-balancing current of battery modules, A;
224 224  * Delay before setting the error;
225 225  * Delay before clearing the error;
226 -* Check all the time (not only in the ‘Balancing’ state) – a flag to enable voltage check not only in “Balancing” state;
227 227  * Lock – a flag to block the error until the device is restarted.
228 228  
229 229  As a result of the operation of the current unbalance protection the errors “Current unbalance (CH)” and “Current unbalance (DCH)” are generated. Conditions for generating the error:
230 230  
231 -* the current of the battery module is greater than the "Maximum current" value during the "Delay before setting the error" time.
230 +* current of the battery module is greater than the "Maximum current" value during the "Delay before setting the error" time.
232 232  
233 233  Conditions for clearing the error:
234 234  
235 -* the current of the battery module is less than the "Maximum current" value during the "Delay before clearing the error" time.
234 +* current of the battery module is less than the "Maximum current" value during the "Delay before clearing the error" time.
236 236  
237 237  If there is the error "Current unbalance (CH)" ("Current unbalance (DCH)"), the charging (discharging) contactor of the battery module opens.
238 238  
239 -=== Charging current unbalance (in “Charging” state) ===
238 +=== Charging current unbalance ===
240 240  
241 241  During battery charging, the currents of the battery modules may vary. The BMS Main X device detects modules whose charging currents are significantly different from the currents of other modules and generates the “Charging current unbalance” errors for them.
242 242