215 215  
216 216  Protection against current unbalance of battery modules is configured in the section "Protections - Current unbalance":
217 217  
218 -[[image:1734356793451-440.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="103" width="800"]]
218 +[[image:Battery management systems.BMS Main 3X.3\. Configuration.3\.4 Protections.WebHome@1734090244843-403.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="116" width="800"]]
219 219  
220 220  In this section:
221 221  
... ... @@ -226,8 +226,10 @@
226 226  * Check all the time (not only in the ‘Balancing’ state) – a flag to enable voltage check not only in “Balancing” state;
227 227  * Lock – a flag to block the error until the device is restarted.
228 228  
229 -As a result of the operation of the current unbalance protection the errors “Current unbalance (CH)” and “Current unbalance (DCH)” are generated. Conditions for generating the error:
229 +As a result of the operation of the current unbalance protection the errors “Current unbalance (CH)” and “Current unbalance (DCH)” are generated.
230 230  
231 +Conditions for generating the error:
232 +
231 231  * the current of the battery module is greater than the "Maximum current" value during the "Delay before setting the error" time.
232 232  
233 233  Conditions for clearing the error:
... ... @@ -234,7 +234,10 @@
234 234  
235 235  * the current of the battery module is less than the "Maximum current" value during the "Delay before clearing the error" time.
236 236  
237 -If there is the error "Current unbalance (CH)" ("Current unbalance (DCH)"), the charging (discharging) contactor of the battery module opens.
239 +(% class="box infomessage" %)
240 +(((
241 +If there is the “Current unbalance (CH)” or "Current unbalance (DCH)" error, **corresponding battery module opens its charging or discharging contactor**.
242 +)))
238 238  
239 239  === Charging current unbalance (in “Charging” state) ===
240 240  
... ... @@ -252,8 +252,10 @@
252 252  * Delay before clearing the error;
253 253  * Lock – a flag to block the error until the device is restarted.
254 254  
255 -As a result of the operation of the protection the “Charging current unbalance” are generated. Conditions for generating the errors:
260 +As a result of the operation of the protection the “Charging current unbalance” are generated.
256 256  
262 +Conditions for generating the errors:
263 +
257 257  * battery module is not included in the largest group of modules whose charge currents differ from each other by no more than "Delta current" during the "Delay before setting the error" time.
258 258  
259 259  Conditions for clearing the error:
... ... @@ -260,7 +260,10 @@
260 260  
261 261  * battery module is included in the largest group of modules with similar charge currents during the “Delay before clearing the error” time.
262 262  
263 -If there is the “Charging current unbalance” error, the battery module charging contactor opens.
270 +(% class="box infomessage" %)
271 +(((
272 +If there is the “Charging current unbalance” error, **corresponding battery module opens its charging contactor**.
273 +)))
264 264  
265 265  === Discharging current unbalance ===
266 266  
... ... @@ -278,8 +278,10 @@
278 278  * Delay before clearing the error;
279 279  * Lock – a flag to block the error until the device is restarted.
280 280  
281 -As a result of the operation of the protection the “Discharging current unbalance” are generated. Conditions for generating the errors:
291 +As a result of the operation of the protection the “Discharging current unbalance” are generated.
282 282  
293 +Conditions for generating the errors:
294 +
283 283  * battery module is not included in the largest group of modules whose discharge currents differ from each other by no more than "Delta current" during the "Delay before setting the error" time.
284 284  
285 285  Conditions for clearing the error:
... ... @@ -286,12 +286,51 @@
286 286  
287 287  * battery module is included in the largest group of modules with similar discharge currents during the “Delay before clearing the error” time.
288 288  
289 -If there is the “Discharging current unbalance” error, the battery module discharging contactor opens.
301 +(% class="box infomessage" %)
302 +(((
303 +If there is the “Discharging current unbalance” error, **corresponding battery module opens its discharging contactor**.
304 +)))
290 290  
306 +=== High contactor temperature ===
307 +
308 +The BMS Main X device protects power contactors from overheating. To measure the temperature of the contactor, one of the thermistors connected to the X5 connector is used.
309 +
310 +To change the overheating protection parameters of power contactors, select the "Protections → High contactor temperature" section:
311 +
312 +[[image:1740756362809-292.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="161" width="800"]]
313 +
314 +In this section:
315 +
316 +* Enable – a flag to enable the protection;
317 +* Thermistor – a selection of which cell thermistor will be used as contactor temperature sensor;
318 +* Maximum contactor temperature, °C;
319 +* Tolerant contactor temperature, °C;
320 +* Delay before setting the error, second;
321 +* Delay before clearing the error, second;
322 +* Lock – a flag to block the error until the device is restarted.
323 +
324 +If there is a contactor overheat, the "High contactor temperature" error is generated.
325 +
326 +Error generation conditions:
327 +
328 +* the contactor temperature is greater than the “Maximum contactor temperature” value during the “Delay before setting the error” time.
329 +
330 +Conditions for removing the error:
331 +
332 +* the contactor temperature is lower than the “Tolerant contactor temperature” value during the “Delay before clearing the error” time.
333 +
334 +=== WDT reset ===
335 +
336 +If the BMS firmware hangs, the watchdog timer resets the device. The BMS can detect that the device was reset and generates the “WDT reset” error.
337 +
338 +To change the parameters of the watchdog protection, select the "Protections → WDT reset" section:
339 +
291 291  === Critical error ===
292 292  
293 -Parameters for generating the critical error are configured in the "Protections - Critical error" section:
342 +Some of the errors are system critical. A separate signal named "Critical error" indicates a BMS fault.
294 294  
344 +To change the critical error parameters, select the "Protections → Critical error" section:
345 +
295 295  [[image:1734356802719-477.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="69" width="600"]]
296 296  
297 297  In this section:
... ... @@ -301,18 +301,6 @@
301 301  * Delay before clearing the error;
302 302  * Lock – a flag to block the error until the device is restarted.
303 303  
304 -The critical error flag is generated if at least one of the following errors persists during the "Delay before setting the error" time:
355 +The "Critical error" signal is generated if at least one of the critical errors (see [[Errors>>doc:Battery management systems.Additional information.2\. Strings controllers\: signals and errors.WebHome||anchor="HErrors"]]) is generated during the Delay before setting the error time.
305 305  
306 -* «Battery cover»;
307 -* «Insulation fault»;
308 -* «CH contactor feedback error»;
309 -* «DCH contactor feedback error»;
310 -* «CH/DCH contactor feedback error»;
311 -* «Module offline».
312 -
313 -The critical error flag is cleared if there are no errors from the list above during the "Delay before clearing the error" time.
314 -
315 -(% class="box warningmessage" %)
316 -(((
317 -**When the critical error flag is present, all battery contactors open.**
318 -)))
357 +The “Critical error" signal is cleared if there are no errors from the list above during the “Delay before clearing the error” time.