Changes for page 3.4 Protections

Last modified by Admin on 2025/06/11 15:57

From version 7.2
edited by Admin
on 2025/02/28 14:59
Change comment: There is no comment for this version
To version 9.1
edited by Admin
on 2025/02/28 15:26
Change comment: Загрузить новое вложение 1740756362809-292.png

Summary

Details

Page properties
Content
... ... @@ -191,10 +191,10 @@
191 191  
192 192  * Enable – a flag to enable the protection;
193 193  * Delta voltage – maximum allowable voltage difference of battery modules, V;
194 -* Use the open circuit voltage to detect the error – a flag to enable Uocv correction;
194 +* Use the open circuit voltage to detect the error – a flag to enable U,,ocv,, correction;
195 195  * Delay before setting the error;
196 196  * Delay before clearing the error;
197 -* Set the 'V'
197 +* Set the 'Voltage unbalance' error for the modules that are not ready to charge/discharge;
198 198  * Lock – a flag to block the error until the device is restarted.
199 199  
200 200  As a result of the operation of the voltage unbalance protection the errors “Voltage unbalance (CH)” and “Voltage unbalance (DCH)” are generated.
... ... @@ -201,11 +201,13 @@
201 201  
202 202  Conditions for generating the error:
203 203  
204 -* battery module is not included in the largest group of modules whose voltages differ from each other by no more than "Delta voltage" during the "Delay before setting the error" time.
204 +* battery module is not included in the largest group of modules whose voltages differ from each other by no more than "Delta voltage" during the "Delay before setting the error" time;
205 +* module is not ready to charge or discharge;
205 205  
206 206  Conditions for clearing the error:
207 207  
208 -* battery module is in the largest group of balanced modules during the "Delay before clearing the error" time.
209 +* battery module is in the largest group of balanced modules during the "Delay before clearing the error" time;
210 +* module is ready to charge or discharge.
209 209  
210 210  === Current unbalance (in “Balancing” state) ===
211 211  
... ... @@ -213,7 +213,7 @@
213 213  
214 214  Protection against current unbalance of battery modules is configured in the section "Protections - Current unbalance":
215 215  
216 -[[image:1734356793451-440.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="103" width="800"]]
218 +[[image:Battery management systems.BMS Main 3X.3\. Configuration.3\.4 Protections.WebHome@1734090244843-403.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="116" width="800"]]
217 217  
218 218  In this section:
219 219  
... ... @@ -221,19 +221,23 @@
221 221  * Maximum current – a maximum allowable self-balancing current of battery modules, A;
222 222  * Delay before setting the error;
223 223  * Delay before clearing the error;
226 +* Check all the time (not only in the ‘Balancing’ state) – a flag to enable voltage check not only in “Balancing” state;
224 224  * Lock – a flag to block the error until the device is restarted.
225 225  
226 226  As a result of the operation of the current unbalance protection the errors “Current unbalance (CH)” and “Current unbalance (DCH)” are generated. Conditions for generating the error:
227 227  
228 -* current of the battery module is greater than the "Maximum current" value during the "Delay before setting the error" time.
231 +* the current of the battery module is greater than the "Maximum current" value during the "Delay before setting the error" time.
229 229  
230 230  Conditions for clearing the error:
231 231  
232 -* current of the battery module is less than the "Maximum current" value during the "Delay before clearing the error" time.
235 +* the current of the battery module is less than the "Maximum current" value during the "Delay before clearing the error" time.
233 233  
234 -If there is the error "Current unbalance (CH)" ("Current unbalance (DCH)"), the charging (discharging) contactor of the battery module opens.
237 +(% class="box infomessage" %)
238 +(((
239 +If there is the “Current unbalance (CH)” or "Current unbalance (DCH)" error, **corresponding battery module opens its charging or discharging contactor**.
240 +)))
235 235  
236 -=== Charging current unbalance ===
242 +=== Charging current unbalance (in “Charging” state) ===
237 237  
238 238  During battery charging, the currents of the battery modules may vary. The BMS Main X device detects modules whose charging currents are significantly different from the currents of other modules and generates the “Charging current unbalance” errors for them.
239 239  
... ... @@ -257,7 +257,10 @@
257 257  
258 258  * battery module is included in the largest group of modules with similar charge currents during the “Delay before clearing the error” time.
259 259  
260 -If there is the “Charging current unbalance” error, the battery module charging contactor opens.
266 +(% class="box infomessage" %)
267 +(((
268 +If there is the “Charging current unbalance” error, **corresponding battery module opens its charging contactor**.
269 +)))
261 261  
262 262  === Discharging current unbalance ===
263 263  
... ... @@ -283,8 +283,19 @@
283 283  
284 284  * battery module is included in the largest group of modules with similar discharge currents during the “Delay before clearing the error” time.
285 285  
286 -If there is the “Discharging current unbalance” error, the battery module discharging contactor opens.
295 +(% class="box infomessage" %)
296 +(((
297 +If there is the “Discharging current unbalance” error, **corresponding battery module opens its discharging contactor**.
298 +)))
287 287  
300 +=== High contactor temperature ===
301 +
302 +=== WDT reset ===
303 +
304 +If the BMS firmware hangs, the watchdog timer resets the device. The BMS can detect that the device was reset and generates the “WDT reset” error.
305 +
306 +To change the parameters of the watchdog protection, select the "Protections → WDT reset" section:
307 +
288 288  === Critical error ===
289 289  
290 290  Parameters for generating the critical error are configured in the "Protections - Critical error" section:
1740756362809-292.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +20.4 KB
Content