... ... @@ -191,10 +191,10 @@
191 191  
192 192  * Enable – a flag to enable the protection;
193 193  * Delta voltage – maximum allowable voltage difference of battery modules, V;
194 -* Use the open circuit voltage to detect the error – a flag to enable Uocv correction;
194 +* Use the open circuit voltage to detect the error – a flag to enable U,,ocv,, correction;
195 195  * Delay before setting the error;
196 196  * Delay before clearing the error;
197 -* Set the 'V'
197 +* Set the 'Voltage unbalance' error for the modules that are not ready to charge/discharge;
198 198  * Lock – a flag to block the error until the device is restarted.
199 199  
200 200  As a result of the operation of the voltage unbalance protection the errors “Voltage unbalance (CH)” and “Voltage unbalance (DCH)” are generated.
... ... @@ -201,11 +201,13 @@
201 201  
202 202  Conditions for generating the error:
203 203  
204 -* battery module is not included in the largest group of modules whose voltages differ from each other by no more than "Delta voltage" during the "Delay before setting the error" time.
204 +* battery module is not included in the largest group of modules whose voltages differ from each other by no more than "Delta voltage" during the "Delay before setting the error" time;
205 +* module is not ready to charge or discharge;
205 205  
206 206  Conditions for clearing the error:
207 207  
208 -* battery module is in the largest group of balanced modules during the "Delay before clearing the error" time.
209 +* battery module is in the largest group of balanced modules during the "Delay before clearing the error" time;
210 +* module is ready to charge or discharge.
209 209  
210 210  === Current unbalance (in “Balancing” state) ===
211 211  
... ... @@ -213,7 +213,7 @@
213 213  
214 214  Protection against current unbalance of battery modules is configured in the section "Protections - Current unbalance":
215 215  
216 -[[image:1734356793451-440.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="103" width="800"]]
218 +[[image:Battery management systems.BMS Main 3X.3\. Configuration.3\.4 Protections.WebHome@1734090244843-403.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="116" width="800"]]
217 217  
218 218  In this section:
219 219  
... ... @@ -221,19 +221,25 @@
221 221  * Maximum current – a maximum allowable self-balancing current of battery modules, A;
222 222  * Delay before setting the error;
223 223  * Delay before clearing the error;
226 +* Check all the time (not only in the ‘Balancing’ state) – a flag to enable voltage check not only in “Balancing” state;
224 224  * Lock – a flag to block the error until the device is restarted.
225 225  
226 -As a result of the operation of the current unbalance protection the errors “Current unbalance (CH)” and “Current unbalance (DCH)” are generated. Conditions for generating the error:
229 +As a result of the operation of the current unbalance protection the errors “Current unbalance (CH)” and “Current unbalance (DCH)” are generated.
227 227  
228 -* current of the battery module is greater than the "Maximum current" value during the "Delay before setting the error" time.
231 +Conditions for generating the error:
229 229  
233 +* the current of the battery module is greater than the "Maximum current" value during the "Delay before setting the error" time.
234 +
230 230  Conditions for clearing the error:
231 231  
232 -* current of the battery module is less than the "Maximum current" value during the "Delay before clearing the error" time.
237 +* the current of the battery module is less than the "Maximum current" value during the "Delay before clearing the error" time.
233 233  
234 -If there is the error "Current unbalance (CH)" ("Current unbalance (DCH)"), the charging (discharging) contactor of the battery module opens.
239 +(% class="box infomessage" %)
240 +(((
241 +If there is the “Current unbalance (CH)” or "Current unbalance (DCH)" error, **corresponding battery module opens its charging or discharging contactor**.
242 +)))
235 235  
236 -=== Charging current unbalance ===
244 +=== Charging current unbalance (in “Charging” state) ===
237 237  
238 238  During battery charging, the currents of the battery modules may vary. The BMS Main X device detects modules whose charging currents are significantly different from the currents of other modules and generates the “Charging current unbalance” errors for them.
239 239  
... ... @@ -249,8 +249,10 @@
249 249  * Delay before clearing the error;
250 250  * Lock – a flag to block the error until the device is restarted.
251 251  
252 -As a result of the operation of the protection the “Charging current unbalance” are generated. Conditions for generating the errors:
260 +As a result of the operation of the protection the “Charging current unbalance” are generated.
253 253  
262 +Conditions for generating the errors:
263 +
254 254  * battery module is not included in the largest group of modules whose charge currents differ from each other by no more than "Delta current" during the "Delay before setting the error" time.
255 255  
256 256  Conditions for clearing the error:
... ... @@ -257,7 +257,10 @@
257 257  
258 258  * battery module is included in the largest group of modules with similar charge currents during the “Delay before clearing the error” time.
259 259  
260 -If there is the “Charging current unbalance” error, the battery module charging contactor opens.
270 +(% class="box infomessage" %)
271 +(((
272 +If there is the “Charging current unbalance” error, **corresponding battery module opens its charging contactor**.
273 +)))
261 261  
262 262  === Discharging current unbalance ===
263 263  
... ... @@ -275,8 +275,10 @@
275 275  * Delay before clearing the error;
276 276  * Lock – a flag to block the error until the device is restarted.
277 277  
278 -As a result of the operation of the protection the “Discharging current unbalance” are generated. Conditions for generating the errors:
291 +As a result of the operation of the protection the “Discharging current unbalance” are generated.
279 279  
293 +Conditions for generating the errors:
294 +
280 280  * battery module is not included in the largest group of modules whose discharge currents differ from each other by no more than "Delta current" during the "Delay before setting the error" time.
281 281  
282 282  Conditions for clearing the error:
... ... @@ -283,12 +283,51 @@
283 283  
284 284  * battery module is included in the largest group of modules with similar discharge currents during the “Delay before clearing the error” time.
285 285  
286 -If there is the “Discharging current unbalance” error, the battery module discharging contactor opens.
301 +(% class="box infomessage" %)
302 +(((
303 +If there is the “Discharging current unbalance” error, **corresponding battery module opens its discharging contactor**.
304 +)))
287 287  
306 +=== High contactor temperature ===
307 +
308 +The BMS Main X device protects power contactors from overheating. To measure the temperature of the contactor, one of the thermistors connected to the X5 connector is used.
309 +
310 +To change the overheating protection parameters of power contactors, select the "Protections → High contactor temperature" section:
311 +
312 +[[image:1740756362809-292.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="161" width="800"]]
313 +
314 +In this section:
315 +
316 +* Enable – a flag to enable the protection;
317 +* Thermistor – a selection of which cell thermistor will be used as contactor temperature sensor;
318 +* Maximum contactor temperature, °C;
319 +* Tolerant contactor temperature, °C;
320 +* Delay before setting the error, second;
321 +* Delay before clearing the error, second;
322 +* Lock – a flag to block the error until the device is restarted.
323 +
324 +If there is a contactor overheat, the "High contactor temperature" error is generated.
325 +
326 +Error generation conditions:
327 +
328 +* the contactor temperature is greater than the “Maximum contactor temperature” value during the “Delay before setting the error” time.
329 +
330 +Conditions for removing the error:
331 +
332 +* the contactor temperature is lower than the “Tolerant contactor temperature” value during the “Delay before clearing the error” time.
333 +
334 +=== WDT reset ===
335 +
336 +If the BMS firmware hangs, the watchdog timer resets the device. The BMS can detect that the device was reset and generates the “WDT reset” error.
337 +
338 +To change the parameters of the watchdog protection, select the "Protections → WDT reset" section:
339 +
288 288  === Critical error ===
289 289  
290 -Parameters for generating the critical error are configured in the "Protections - Critical error" section:
342 +Some of the errors are system critical. A separate signal named "Critical error" indicates a BMS fault.
291 291  
344 +To change the critical error parameters, select the "Protections → Critical error" section:
345 +
292 292  [[image:1734356802719-477.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="69" width="600"]]
293 293  
294 294  In this section:
... ... @@ -298,18 +298,6 @@
298 298  * Delay before clearing the error;
299 299  * Lock – a flag to block the error until the device is restarted.
300 300  
301 -The critical error flag is generated if at least one of the following errors persists during the "Delay before setting the error" time:
355 +The "Critical error" signal is generated if at least one of the critical errors (see [[Errors>>doc:Battery management systems.Additional information.2\. Strings controllers\: signals and errors.WebHome||anchor="HErrors"]]) is generated during the Delay before setting the error time.
302 302  
303 -* «Battery cover»;
304 -* «Insulation fault»;
305 -* «CH contactor feedback error»;
306 -* «DCH contactor feedback error»;
307 -* «CH/DCH contactor feedback error»;
308 -* «Module offline».
309 -
310 -The critical error flag is cleared if there are no errors from the list above during the "Delay before clearing the error" time.
311 -
312 -(% class="box warningmessage" %)
313 -(((
314 -**When the critical error flag is present, all battery contactors open.**
315 -)))
357 +The “Critical error" signal is cleared if there are no errors from the list above during the “Delay before clearing the error” time.