Changes for page 3.4 Protections

Last modified by Admin on 2025/06/11 15:57

From version 17.1
edited by Admin
on 2025/04/04 11:59
Change comment: There is no comment for this version
To version 7.4
edited by Admin
on 2025/02/28 15:01
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -168,11 +168,11 @@
168 168  
169 169  Error generation conditions:
170 170  
171 -* more than “Number of offline modules to set the error” battery modules do not respond to the commands of the BMS Main X device within “Delay before setting the error” time.
171 +* more than “Number of offline modules to set the error” battery modules do not respond to the commands of the BMS Main 3X device within “Delay before setting the error” time.
172 172  
173 173  Conditions for removing the error:
174 174  
175 -* less than “Number of offline modules to set the error” battery modules do not respond to the commands of the BMS Main X device within “Delay before clearing the error” time.
175 +* less than “Number of offline modules to set the error” battery modules do not respond to the commands of the BMS Main 3X device within “Delay before clearing the error” time.
176 176  
177 177  (% class="box warningmessage" %)
178 178  (((
... ... @@ -209,11 +209,6 @@
209 209  * battery module is in the largest group of balanced modules during the "Delay before clearing the error" time;
210 210  * module is ready to charge or discharge.
211 211  
212 -(% class="box infomessage" %)
213 -(((
214 -If there is the “Voltage unbalance (CH)” or "Voltage unbalance (DCH)" error, **corresponding battery module do not close its contactors while joining  to charge of discharge**.
215 -)))
216 -
217 217  === Current unbalance (in “Balancing” state) ===
218 218  
219 219  When battery modules are connected in parallel, the most charged modules transfer charge to the least charged modules. The process of charge transfer is accompanied by the flow of balancing currents. The BMS Main X device detects modules with high balancing currents and generates “Current unbalance (CH)” (charge circuit) and “Current unbalance (DCH)” (discharge circuit) errors for them.
... ... @@ -220,7 +220,7 @@
220 220  
221 221  Protection against current unbalance of battery modules is configured in the section "Protections - Current unbalance":
222 222  
223 -[[image:Battery management systems.BMS Main 3X.3\. Configuration.3\.4 Protections.WebHome@1734090244843-403.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="116" width="800"]]
218 +[[image:1734356793451-440.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="103" width="800"]]
224 224  
225 225  In this section:
226 226  
... ... @@ -228,25 +228,19 @@
228 228  * Maximum current – a maximum allowable self-balancing current of battery modules, A;
229 229  * Delay before setting the error;
230 230  * Delay before clearing the error;
231 -* Check all the time (not only in the ‘Balancing’ state) – a flag to enable voltage check not only in “Balancing” state;
232 232  * Lock – a flag to block the error until the device is restarted.
233 233  
234 -As a result of the operation of the current unbalance protection the errors “Current unbalance (CH)” and “Current unbalance (DCH)” are generated.
228 +As a result of the operation of the current unbalance protection the errors “Current unbalance (CH)” and “Current unbalance (DCH)” are generated. Conditions for generating the error:
235 235  
236 -Conditions for generating the error:
230 +* current of the battery module is greater than the "Maximum current" value during the "Delay before setting the error" time.
237 237  
238 -* the current of the battery module is greater than the "Maximum current" value during the "Delay before setting the error" time.
239 -
240 240  Conditions for clearing the error:
241 241  
242 -* the current of the battery module is less than the "Maximum current" value during the "Delay before clearing the error" time.
234 +* current of the battery module is less than the "Maximum current" value during the "Delay before clearing the error" time.
243 243  
244 -(% class="box infomessage" %)
245 -(((
246 -If there is the “Current unbalance (CH)” or "Current unbalance (DCH)" error, **corresponding battery module opens its charging or discharging contactor**.
247 -)))
236 +If there is the error "Current unbalance (CH)" ("Current unbalance (DCH)"), the charging (discharging) contactor of the battery module opens.
248 248  
249 -=== Charging current unbalance (in “Charging” state) ===
238 +=== Charging current unbalance ===
250 250  
251 251  During battery charging, the currents of the battery modules may vary. The BMS Main X device detects modules whose charging currents are significantly different from the currents of other modules and generates the “Charging current unbalance” errors for them.
252 252  
... ... @@ -262,10 +262,8 @@
262 262  * Delay before clearing the error;
263 263  * Lock – a flag to block the error until the device is restarted.
264 264  
265 -As a result of the operation of the protection the “Charging current unbalance” are generated.
254 +As a result of the operation of the protection the “Charging current unbalance” are generated. Conditions for generating the errors:
266 266  
267 -Conditions for generating the errors:
268 -
269 269  * battery module is not included in the largest group of modules whose charge currents differ from each other by no more than "Delta current" during the "Delay before setting the error" time.
270 270  
271 271  Conditions for clearing the error:
... ... @@ -272,10 +272,7 @@
272 272  
273 273  * battery module is included in the largest group of modules with similar charge currents during the “Delay before clearing the error” time.
274 274  
275 -(% class="box infomessage" %)
276 -(((
277 -If there is the “Charging current unbalance” error, **corresponding battery module opens its charging contactor**.
278 -)))
262 +If there is the “Charging current unbalance” error, the battery module charging contactor opens.
279 279  
280 280  === Discharging current unbalance ===
281 281  
... ... @@ -293,10 +293,8 @@
293 293  * Delay before clearing the error;
294 294  * Lock – a flag to block the error until the device is restarted.
295 295  
296 -As a result of the operation of the protection the “Discharging current unbalance” are generated.
280 +As a result of the operation of the protection the “Discharging current unbalance” are generated. Conditions for generating the errors:
297 297  
298 -Conditions for generating the errors:
299 -
300 300  * battery module is not included in the largest group of modules whose discharge currents differ from each other by no more than "Delta current" during the "Delay before setting the error" time.
301 301  
302 302  Conditions for clearing the error:
... ... @@ -303,77 +303,33 @@
303 303  
304 304  * battery module is included in the largest group of modules with similar discharge currents during the “Delay before clearing the error” time.
305 305  
306 -(% class="box infomessage" %)
307 -(((
308 -If there is the “Discharging current unbalance” error, **corresponding battery module opens its discharging contactor**.
309 -)))
288 +If there is the “Discharging current unbalance” error, the battery module discharging contactor opens.
310 310  
311 -=== High contactor temperature ===
290 +=== Critical error ===
312 312  
313 -The BMS Main X device protects power contactors from overheating. To measure the temperature of the contactor, one of the thermistors connected to the X5 connector is used.
292 +Parameters for generating the critical error are configured in the "Protections - Critical error" section:
314 314  
315 -To change the overheating protection parameters of power contactors, select the "Protections → High contactor temperature" section:
294 +[[image:1734356802719-477.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="69" width="600"]]
316 316  
317 -[[image:1740756362809-292.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="161" width="800"]]
318 -
319 319  In this section:
320 320  
321 -* Enable – a flag to enable the protection;
322 -* Thermistor – a selection of which cell thermistor will be used as contactor temperature sensor;
323 -* Maximum contactor temperature, °C;
324 -* Tolerant contactor temperature, °C;
325 -* Delay before setting the error, second;
326 -* Delay before clearing the error, second;
298 +* Enable – a flag to enable the protection;
299 +* Delay before setting the error;
300 +* Delay before clearing the error;
327 327  * Lock – a flag to block the error until the device is restarted.
328 328  
329 -If there is a contactor overheat, the "High contactor temperature" error is generated.
303 +The critical error flag is generated if at least one of the following errors persists during the "Delay before setting the error" time:
330 330  
331 -Error generation conditions:
305 +* «Battery cover»;
306 +* «Insulation fault»;
307 +* «CH contactor feedback error»;
308 +* «DCH contactor feedback error»;
309 +* «CH/DCH contactor feedback error»;
310 +* «Module offline».
332 332  
333 -* the contactor temperature is greater than the “Maximum contactor temperature value during the Delay before setting the error time.
312 +The critical error flag is cleared if there are no errors from the list above during the "Delay before clearing the error" time.
334 334  
335 -Conditions for removing the error:
336 -
337 -* the contactor temperature is lower than the “Tolerant contactor temperature” value during the “Delay before clearing the error” time.
338 -
339 -=== WDT reset ===
340 -
341 -If the BMS firmware hangs, the watchdog timer resets the device. The BMS can detect that the device was reset and generates the “WDT reset” error.
342 -
343 -To change the parameters of the watchdog protection, select the "Protections → WDT reset" section:
344 -
345 -[[image:Battery management systems.BMS Main 3X.3\. Configuration.3\.4 Protections.WebHome@1734090244845-157.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="93" width="800"]]
346 -
347 -In this section:
348 -
349 -* Enable – a flag to enable the protection;
350 -* Delay before clearing the error, second;
351 -* Lock – a flag to block the error until the device is restarted.
352 -
353 -Conditions for removing the error:
354 -
355 -* the “Delay before clearing the error” time has passed from the device startup.
356 -
357 357  (% class="box warningmessage" %)
358 358  (((
359 -If there is the "WDT reset" error, **“Critical error is generated.**
316 +**When the critical error flag is present, all battery contactors open.**
360 360  )))
361 -
362 -=== Critical error ===
363 -
364 -Some of the errors are system critical. A separate signal named "Critical error" indicates a BMS fault.
365 -
366 -To change the critical error parameters, select the "Protections → Critical error" section:
367 -
368 -[[image:1740756532131-419.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="118" width="800"]]
369 -
370 -In this section:
371 -
372 -* Enable – a flag to enable the protection;
373 -* Delay before setting the error;
374 -* Delay before clearing the error;
375 -* Lock – a flag to block the error until the device is restarted.
376 -
377 -The "Critical error" signal is generated if at least one of the critical errors (see [[Errors>>doc:Battery management systems.Additional information.2\. Strings controllers\: signals and errors.WebHome||anchor="HErrors"]]) is generated during the “Delay before setting the error” time.
378 -
379 -The “Critical error" signal is cleared if there are no errors from the list above during the “Delay before clearing the error” time.
1740756362809-292.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.admin
Size
... ... @@ -1,1 +1,0 @@
1 -20.4 KB
Content
1740756532131-419.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.admin
Size
... ... @@ -1,1 +1,0 @@
1 -15.7 KB
Content