... ... @@ -209,7 +209,10 @@
209 209  * battery module is in the largest group of balanced modules during the "Delay before clearing the error" time;
210 210  * module is ready to charge or discharge.
211 211  
212 -If there is the “Voltage unbalance (CH)” or "Voltage unbalance (DCH)" error, **corresponding battery module opens its charging or discharging contactor**.
212 +(% class="box infomessage" %)
213 +(((
214 +If there is the “Voltage unbalance (CH)” or "Voltage unbalance (DCH)" error, **corresponding battery module do not close its contactors while joining  to charge of discharge**.
215 +)))
213 213  
214 214  === Current unbalance (in “Balancing” state) ===
215 215  
... ... @@ -274,7 +274,7 @@
274 274  If there is the “Charging current unbalance” error, **corresponding battery module opens its charging contactor**.
275 275  )))
276 276  
277 -=== Discharging current unbalance ===
280 +=== Discharging current unbalance (in “Discharging” state) ===
278 278  
279 279  During battery discharging, the currents of the battery modules may vary. The BMS Main X device detects modules whose discharging currents are significantly different from the currents of other modules and generates the “Discharging current unbalance” errors for them.