Changes for page 3.4 Protections
Last modified by Admin on 2025/06/11 15:57
Summary
-
Page properties (1 modified, 0 added, 0 removed)
-
Attachments (0 modified, 1 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -168,11 +168,11 @@ 168 168 169 169 Error generation conditions: 170 170 171 -* more than “Number of offline modules to set the error” battery modules do not respond to the commands of the BMS Main 3X device within “Delay before setting the error” time.171 +* more than “Number of offline modules to set the error” battery modules do not respond to the commands of the BMS Main X device within “Delay before setting the error” time. 172 172 173 173 Conditions for removing the error: 174 174 175 -* less than “Number of offline modules to set the error” battery modules do not respond to the commands of the BMS Main 3X device within “Delay before clearing the error” time.175 +* less than “Number of offline modules to set the error” battery modules do not respond to the commands of the BMS Main X device within “Delay before clearing the error” time. 176 176 177 177 (% class="box warningmessage" %) 178 178 ((( ... ... @@ -191,7 +191,7 @@ 191 191 192 192 * Enable – a flag to enable the protection; 193 193 * Delta voltage – maximum allowable voltage difference of battery modules, V; 194 -* Use the open circuit voltage to detect the error – a flag to e nable U,,ocv,,ion;194 +* Use the open circuit voltage to detect the error – a flag to use the U,,ocv,, (corrected due to current and module resistance) module voltage; 195 195 * Delay before setting the error; 196 196 * Delay before clearing the error; 197 197 * Set the 'Voltage unbalance' error for the modules that are not ready to charge/discharge; ... ... @@ -209,7 +209,10 @@ 209 209 * battery module is in the largest group of balanced modules during the "Delay before clearing the error" time; 210 210 * module is ready to charge or discharge. 211 211 212 -If there is the “Voltage unbalance (CH)” or "Voltage unbalance (DCH)" error, **corresponding battery module opens its charging or discharging contactor**. 212 +(% class="box infomessage" %) 213 +((( 214 +If there is the “Voltage unbalance (CH)” or "Voltage unbalance (DCH)" error, **corresponding battery module do not close its contactors while joining to charge of discharge**. 215 +))) 213 213 214 214 === Current unbalance (in “Balancing” state) === 215 215 ... ... @@ -217,7 +217,7 @@ 217 217 218 218 Protection against current unbalance of battery modules is configured in the section "Protections - Current unbalance": 219 219 220 -[[image: Battery management systems.BMS Main 3X.3\. Configuration.3\.4 Protections.WebHome@1734090244843-403.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="116" width="800"]]223 +[[image:1749657225475-323.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="91" width="600"]] 221 221 222 222 In this section: 223 223 ... ... @@ -274,7 +274,7 @@ 274 274 If there is the “Charging current unbalance” error, **corresponding battery module opens its charging contactor**. 275 275 ))) 276 276 277 -=== Discharging current unbalance === 280 +=== Discharging current unbalance (in “Discharging” state) === 278 278 279 279 During battery discharging, the currents of the battery modules may vary. The BMS Main X device detects modules whose discharging currents are significantly different from the currents of other modules and generates the “Discharging current unbalance” errors for them. 280 280
- 1749657225475-323.png
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.admin - Size
-
... ... @@ -1,0 +1,1 @@ 1 +25.6 KB - Content