Changes for page 3.4 Protections
Last modified by Admin on 2025/06/11 15:57
Summary
-
Page properties (1 modified, 0 added, 0 removed)
-
Attachments (0 modified, 0 added, 2 removed)
Details
- Page properties
-
- Content
-
... ... @@ -215,7 +215,7 @@ 215 215 216 216 Protection against current unbalance of battery modules is configured in the section "Protections - Current unbalance": 217 217 218 -[[image: Battery management systems.BMS Main 3X.3\. Configuration.3\.4 Protections.WebHome@1734090244843-403.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="116" width="800"]]218 +[[image:1734356793451-440.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="103" width="800"]] 219 219 220 220 In this section: 221 221 ... ... @@ -226,10 +226,8 @@ 226 226 * Check all the time (not only in the ‘Balancing’ state) – a flag to enable voltage check not only in “Balancing” state; 227 227 * Lock – a flag to block the error until the device is restarted. 228 228 229 -As a result of the operation of the current unbalance protection the errors “Current unbalance (CH)” and “Current unbalance (DCH)” are generated. 229 +As a result of the operation of the current unbalance protection the errors “Current unbalance (CH)” and “Current unbalance (DCH)” are generated. Conditions for generating the error: 230 230 231 -Conditions for generating the error: 232 - 233 233 * the current of the battery module is greater than the "Maximum current" value during the "Delay before setting the error" time. 234 234 235 235 Conditions for clearing the error: ... ... @@ -236,9 +236,9 @@ 236 236 237 237 * the current of the battery module is less than the "Maximum current" value during the "Delay before clearing the error" time. 238 238 239 -(% class="box in fomessage" %)237 +(% class="box warningmessage" %) 240 240 ((( 241 -If there is the “Current unbalance (CH)”or "Current unbalance (DCH)" error, **corresponding battery module opens itscharging ordischarging contactor**.239 +If there is the “Current unbalance” error, **corresponding battery module opens its discharging contactor**. 242 242 ))) 243 243 244 244 === Charging current unbalance (in “Charging” state) === ... ... @@ -257,10 +257,8 @@ 257 257 * Delay before clearing the error; 258 258 * Lock – a flag to block the error until the device is restarted. 259 259 260 -As a result of the operation of the protection the “Charging current unbalance” are generated. 258 +As a result of the operation of the protection the “Charging current unbalance” are generated. Conditions for generating the errors: 261 261 262 -Conditions for generating the errors: 263 - 264 264 * battery module is not included in the largest group of modules whose charge currents differ from each other by no more than "Delta current" during the "Delay before setting the error" time. 265 265 266 266 Conditions for clearing the error: ... ... @@ -288,10 +288,8 @@ 288 288 * Delay before clearing the error; 289 289 * Lock – a flag to block the error until the device is restarted. 290 290 291 -As a result of the operation of the protection the “Discharging current unbalance” are generated. 287 +As a result of the operation of the protection the “Discharging current unbalance” are generated. Conditions for generating the errors: 292 292 293 -Conditions for generating the errors: 294 - 295 295 * battery module is not included in the largest group of modules whose discharge currents differ from each other by no more than "Delta current" during the "Delay before setting the error" time. 296 296 297 297 Conditions for clearing the error: ... ... @@ -303,72 +303,31 @@ 303 303 If there is the “Discharging current unbalance” error, **corresponding battery module opens its discharging contactor**. 304 304 ))) 305 305 306 -=== High contactortemperature===300 +=== Critical error === 307 307 308 - The BMS Main X device protects powercontactors fromoverheating.To measurethe temperatureofthe contactor,oneofthe thermistorsconnectedtotheX5 connectorisused.302 +Parameters for generating the critical error are configured in the "Protections - Critical error" section: 309 309 310 - To changethe overheatingprotectionparameters of power contactors, selectthe"Protections → High contactortemperature"section:304 +[[image:1734356802719-477.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="69" width="600"]] 311 311 312 -[[image:1740756362809-292.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="161" width="800"]] 313 - 314 314 In this section: 315 315 316 -* Enable – a flag to enable the protection; 317 -* Thermistor – a selection of which cell thermistor will be used as contactor temperature sensor; 318 -* Maximum contactor temperature, °C; 319 -* Tolerant contactor temperature, °C; 320 -* Delay before setting the error, second; 321 -* Delay before clearing the error, second; 308 +* Enable – a flag to enable the protection; 309 +* Delay before setting the error; 310 +* Delay before clearing the error; 322 322 * Lock – a flag to block the error until the device is restarted. 323 323 324 - If there isa contactoroverheat,the"Highcontactortemperature" errorisgenerated.313 +The critical error flag is generated if at least one of the following errors persists during the "Delay before setting the error" time: 325 325 326 -Error generation conditions: 315 +* «Battery cover»; 316 +* «Insulation fault»; 317 +* «CH contactor feedback error»; 318 +* «DCH contactor feedback error»; 319 +* «CH/DCH contactor feedback error»; 320 +* «Module offline». 327 327 328 - * the contactortemperatureisgreaterthanthe“Maximumcontactortemperature”value during the“Delay beforesetting the error”time.322 +The critical error flag is cleared if there are no errors from the list above during the "Delay before clearing the error" time. 329 329 330 -Conditions for removing the error: 331 - 332 -* the contactor temperature is lower than the “Tolerant contactor temperature” value during the “Delay before clearing the error” time. 333 - 334 -=== WDT reset === 335 - 336 -If the BMS firmware hangs, the watchdog timer resets the device. The BMS can detect that the device was reset and generates the “WDT reset” error. 337 - 338 -To change the parameters of the watchdog protection, select the "Protections → WDT reset" section: 339 - 340 -[[image:Battery management systems.BMS Main 3X.3\. Configuration.3\.4 Protections.WebHome@1734090244845-157.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="93" width="800"]] 341 - 342 -In this section: 343 - 344 -* Enable – a flag to enable the protection; 345 -* Delay before clearing the error, second; 346 -* Lock – a flag to block the error until the device is restarted. 347 - 348 -Conditions for removing the error: 349 - 350 -* the “Delay before clearing the error” time has passed from the device startup. 351 - 352 352 (% class="box warningmessage" %) 353 353 ((( 354 - If thereisthe"WDTreset" error, **“Critical error”isgenerated.**326 +**When the critical error flag is present, all battery contactors open.** 355 355 ))) 356 - 357 -=== Critical error === 358 - 359 -Some of the errors are system critical. A separate signal named "Critical error" indicates a BMS fault. 360 - 361 -To change the critical error parameters, select the "Protections → Critical error" section: 362 - 363 -[[image:1740756532131-419.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="118" width="800"]] 364 - 365 -In this section: 366 - 367 -* Enable – a flag to enable the protection; 368 -* Delay before setting the error; 369 -* Delay before clearing the error; 370 -* Lock – a flag to block the error until the device is restarted. 371 - 372 -The "Critical error" signal is generated if at least one of the critical errors (see [[Errors>>doc:Battery management systems.Additional information.2\. Strings controllers\: signals and errors.WebHome||anchor="HErrors"]]) is generated during the “Delay before setting the error” time. 373 - 374 -The “Critical error" signal is cleared if there are no errors from the list above during the “Delay before clearing the error” time.
- 1740756362809-292.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.admin - Size
-
... ... @@ -1,1 +1,0 @@ 1 -20.4 KB - Content
- 1740756532131-419.png
-
- Author
-
... ... @@ -1,1 +1,0 @@ 1 -XWiki.admin - Size
-
... ... @@ -1,1 +1,0 @@ 1 -15.7 KB - Content