... ... @@ -209,6 +209,8 @@
209 209  * battery module is in the largest group of balanced modules during the "Delay before clearing the error" time;
210 210  * module is ready to charge or discharge.
211 211  
212 +If there is the “Voltage unbalance (CH)” or "Voltage unbalance (DCH)" error, **corresponding battery module opens its charging or discharging contactor**.
213 +
212 212  === Current unbalance (in “Balancing” state) ===
213 213  
214 214  When battery modules are connected in parallel, the most charged modules transfer charge to the least charged modules. The process of charge transfer is accompanied by the flow of balancing currents. The BMS Main X device detects modules with high balancing currents and generates “Current unbalance (CH)” (charge circuit) and “Current unbalance (DCH)” (discharge circuit) errors for them.