... ... @@ -215,7 +215,7 @@
215 215  
216 216  Protection against current unbalance of battery modules is configured in the section "Protections - Current unbalance":
217 217  
218 -[[image:Battery management systems.BMS Main 3X.3\. Configuration.3\.4 Protections.WebHome@1734090244843-403.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="116" width="800"]]
218 +[[image:1734356793451-440.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="103" width="800"]]
219 219  
220 220  In this section:
221 221  
... ... @@ -223,25 +223,19 @@
223 223  * Maximum current – a maximum allowable self-balancing current of battery modules, A;
224 224  * Delay before setting the error;
225 225  * Delay before clearing the error;
226 -* Check all the time (not only in the ‘Balancing’ state) – a flag to enable voltage check not only in “Balancing” state;
227 227  * Lock – a flag to block the error until the device is restarted.
228 228  
229 -As a result of the operation of the current unbalance protection the errors “Current unbalance (CH)” and “Current unbalance (DCH)” are generated.
228 +As a result of the operation of the current unbalance protection the errors “Current unbalance (CH)” and “Current unbalance (DCH)” are generated. Conditions for generating the error:
230 230  
231 -Conditions for generating the error:
230 +* current of the battery module is greater than the "Maximum current" value during the "Delay before setting the error" time.
232 232  
233 -* the current of the battery module is greater than the "Maximum current" value during the "Delay before setting the error" time.
234 -
235 235  Conditions for clearing the error:
236 236  
237 -* the current of the battery module is less than the "Maximum current" value during the "Delay before clearing the error" time.
234 +* current of the battery module is less than the "Maximum current" value during the "Delay before clearing the error" time.
238 238  
239 -(% class="box infomessage" %)
240 -(((
241 -If there is the “Current unbalance (CH)” or "Current unbalance (DCH)" error, **corresponding battery module opens its charging or discharging contactor**.
242 -)))
236 +If there is the error "Current unbalance (CH)" ("Current unbalance (DCH)"), the charging (discharging) contactor of the battery module opens.
243 243  
244 -=== Charging current unbalance (in “Charging” state) ===
238 +=== Charging current unbalance ===
245 245  
246 246  During battery charging, the currents of the battery modules may vary. The BMS Main X device detects modules whose charging currents are significantly different from the currents of other modules and generates the “Charging current unbalance” errors for them.
247 247  
... ... @@ -257,10 +257,8 @@
257 257  * Delay before clearing the error;
258 258  * Lock – a flag to block the error until the device is restarted.
259 259  
260 -As a result of the operation of the protection the “Charging current unbalance” are generated.
254 +As a result of the operation of the protection the “Charging current unbalance” are generated. Conditions for generating the errors:
261 261  
262 -Conditions for generating the errors:
263 -
264 264  * battery module is not included in the largest group of modules whose charge currents differ from each other by no more than "Delta current" during the "Delay before setting the error" time.
265 265  
266 266  Conditions for clearing the error:
... ... @@ -267,10 +267,7 @@
267 267  
268 268  * battery module is included in the largest group of modules with similar charge currents during the “Delay before clearing the error” time.
269 269  
270 -(% class="box infomessage" %)
271 -(((
272 -If there is the “Charging current unbalance” error, **corresponding battery module opens its charging contactor**.
273 -)))
262 +If there is the “Charging current unbalance” error, the battery module charging contactor opens.
274 274  
275 275  === Discharging current unbalance ===
276 276  
... ... @@ -288,10 +288,8 @@
288 288  * Delay before clearing the error;
289 289  * Lock – a flag to block the error until the device is restarted.
290 290  
291 -As a result of the operation of the protection the “Discharging current unbalance” are generated.
280 +As a result of the operation of the protection the “Discharging current unbalance” are generated. Conditions for generating the errors:
292 292  
293 -Conditions for generating the errors:
294 -
295 295  * battery module is not included in the largest group of modules whose discharge currents differ from each other by no more than "Delta current" during the "Delay before setting the error" time.
296 296  
297 297  Conditions for clearing the error:
... ... @@ -298,51 +298,12 @@
298 298  
299 299  * battery module is included in the largest group of modules with similar discharge currents during the “Delay before clearing the error” time.
300 300  
301 -(% class="box infomessage" %)
302 -(((
303 -If there is the “Discharging current unbalance” error, **corresponding battery module opens its discharging contactor**.
304 -)))
288 +If there is the “Discharging current unbalance” error, the battery module discharging contactor opens.
305 305  
306 -=== High contactor temperature ===
307 -
308 -The BMS Main X device protects power contactors from overheating. To measure the temperature of the contactor, one of the thermistors connected to the X5 connector is used.
309 -
310 -To change the overheating protection parameters of power contactors, select the "Protections → High contactor temperature" section:
311 -
312 -[[image:1740756362809-292.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="161" width="800"]]
313 -
314 -In this section:
315 -
316 -* Enable – a flag to enable the protection;
317 -* Thermistor – a selection of which cell thermistor will be used as contactor temperature sensor;
318 -* Maximum contactor temperature, °C;
319 -* Tolerant contactor temperature, °C;
320 -* Delay before setting the error, second;
321 -* Delay before clearing the error, second;
322 -* Lock – a flag to block the error until the device is restarted.
323 -
324 -If there is a contactor overheat, the "High contactor temperature" error is generated.
325 -
326 -Error generation conditions:
327 -
328 -* the contactor temperature is greater than the “Maximum contactor temperature” value during the “Delay before setting the error” time.
329 -
330 -Conditions for removing the error:
331 -
332 -* the contactor temperature is lower than the “Tolerant contactor temperature” value during the “Delay before clearing the error” time.
333 -
334 -=== WDT reset ===
335 -
336 -If the BMS firmware hangs, the watchdog timer resets the device. The BMS can detect that the device was reset and generates the “WDT reset” error.
337 -
338 -To change the parameters of the watchdog protection, select the "Protections → WDT reset" section:
339 -
340 340  === Critical error ===
341 341  
342 -Some of the errors are system critical. A separate signal named "Critical error" indicates a BMS fault.
292 +Parameters for generating the critical error are configured in the "Protections - Critical error" section:
343 343  
344 -To change the critical error parameters, select the "Protections → Critical error" section:
345 -
346 346  [[image:1734356802719-477.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="69" width="600"]]
347 347  
348 348  In this section:
... ... @@ -352,6 +352,18 @@
352 352  * Delay before clearing the error;
353 353  * Lock – a flag to block the error until the device is restarted.
354 354  
355 -The "Critical error" signal is generated if at least one of the critical errors (see [[Errors>>doc:Battery management systems.Additional information.2\. Strings controllers\: signals and errors.WebHome||anchor="HErrors"]]) is generated during the Delay before setting the error time.
303 +The critical error flag is generated if at least one of the following errors persists during the "Delay before setting the error" time:
356 356  
357 -The “Critical error" signal is cleared if there are no errors from the list above during the “Delay before clearing the error” time.
305 +* «Battery cover»;
306 +* «Insulation fault»;
307 +* «CH contactor feedback error»;
308 +* «DCH contactor feedback error»;
309 +* «CH/DCH contactor feedback error»;
310 +* «Module offline».
311 +
312 +The critical error flag is cleared if there are no errors from the list above during the "Delay before clearing the error" time.
313 +
314 +(% class="box warningmessage" %)
315 +(((
316 +**When the critical error flag is present, all battery contactors open.**
317 +)))
1740756362809-292.png