Changes for page 3.4 Protections
Last modified by Admin on 2025/06/11 15:57
Summary
-
Page properties (1 modified, 0 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -226,10 +226,8 @@ 226 226 * Check all the time (not only in the ‘Balancing’ state) – a flag to enable voltage check not only in “Balancing” state; 227 227 * Lock – a flag to block the error until the device is restarted. 228 228 229 -As a result of the operation of the current unbalance protection the errors “Current unbalance (CH)” and “Current unbalance (DCH)” are generated. 229 +As a result of the operation of the current unbalance protection the errors “Current unbalance (CH)” and “Current unbalance (DCH)” are generated. Conditions for generating the error: 230 230 231 -Conditions for generating the error: 232 - 233 233 * the current of the battery module is greater than the "Maximum current" value during the "Delay before setting the error" time. 234 234 235 235 Conditions for clearing the error: ... ... @@ -257,10 +257,8 @@ 257 257 * Delay before clearing the error; 258 258 * Lock – a flag to block the error until the device is restarted. 259 259 260 -As a result of the operation of the protection the “Charging current unbalance” are generated. 258 +As a result of the operation of the protection the “Charging current unbalance” are generated. Conditions for generating the errors: 261 261 262 -Conditions for generating the errors: 263 - 264 264 * battery module is not included in the largest group of modules whose charge currents differ from each other by no more than "Delta current" during the "Delay before setting the error" time. 265 265 266 266 Conditions for clearing the error: ... ... @@ -288,10 +288,8 @@ 288 288 * Delay before clearing the error; 289 289 * Lock – a flag to block the error until the device is restarted. 290 290 291 -As a result of the operation of the protection the “Discharging current unbalance” are generated. 287 +As a result of the operation of the protection the “Discharging current unbalance” are generated. Conditions for generating the errors: 292 292 293 -Conditions for generating the errors: 294 - 295 295 * battery module is not included in the largest group of modules whose discharge currents differ from each other by no more than "Delta current" during the "Delay before setting the error" time. 296 296 297 297 Conditions for clearing the error: ... ... @@ -305,32 +305,6 @@ 305 305 306 306 === High contactor temperature === 307 307 308 -The BMS Main X device protects power contactors from overheating. To measure the temperature of the contactor, one of the thermistors connected to the X5 connector is used. 309 - 310 -To change the overheating protection parameters of power contactors, select the "Protections → High contactor temperature" section: 311 - 312 -[[image:1740756362809-292.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="161" width="800"]] 313 - 314 -In this section: 315 - 316 -* Enable – a flag to enable the protection; 317 -* Thermistor – a selection of which cell thermistor will be used as contactor temperature sensor; 318 -* Maximum contactor temperature, °C; 319 -* Tolerant contactor temperature, °C; 320 -* Delay before setting the error, second; 321 -* Delay before clearing the error, second; 322 -* Lock – a flag to block the error until the device is restarted. 323 - 324 -If there is a contactor overheat, the "High contactor temperature" error is generated. 325 - 326 -Error generation conditions: 327 - 328 -* the contactor temperature is greater than the “Maximum contactor temperature” value during the “Delay before setting the error” time. 329 - 330 -Conditions for removing the error: 331 - 332 -* the contactor temperature is lower than the “Tolerant contactor temperature” value during the “Delay before clearing the error” time. 333 - 334 334 === WDT reset === 335 335 336 336 If the BMS firmware hangs, the watchdog timer resets the device. The BMS can detect that the device was reset and generates the “WDT reset” error.