... ... @@ -168,11 +168,11 @@
168 168  
169 169  Error generation conditions:
170 170  
171 -* more than “Number of offline modules to set the error” battery modules do not respond to the commands of the BMS Main 3X device within “Delay before setting the error” time.
171 +* more than “Number of offline modules to set the error” battery modules do not respond to the commands of the BMS Main X device within “Delay before setting the error” time.
172 172  
173 173  Conditions for removing the error:
174 174  
175 -* less than “Number of offline modules to set the error” battery modules do not respond to the commands of the BMS Main 3X device within “Delay before clearing the error” time.
175 +* less than “Number of offline modules to set the error” battery modules do not respond to the commands of the BMS Main X device within “Delay before clearing the error” time.
176 176  
177 177  (% class="box warningmessage" %)
178 178  (((
... ... @@ -209,6 +209,8 @@
209 209  * battery module is in the largest group of balanced modules during the "Delay before clearing the error" time;
210 210  * module is ready to charge or discharge.
211 211  
212 +If there is the “Voltage unbalance (CH)” or "Voltage unbalance (DCH)" error, **corresponding battery module opens its charging or discharging contactor**.
213 +
212 212  === Current unbalance (in “Balancing” state) ===
213 213  
214 214  When battery modules are connected in parallel, the most charged modules transfer charge to the least charged modules. The process of charge transfer is accompanied by the flow of balancing currents. The BMS Main X device detects modules with high balancing currents and generates “Current unbalance (CH)” (charge circuit) and “Current unbalance (DCH)” (discharge circuit) errors for them.
... ... @@ -337,12 +337,31 @@
337 337  
338 338  To change the parameters of the watchdog protection, select the "Protections → WDT reset" section:
339 339  
342 +[[image:Battery management systems.BMS Main 3X.3\. Configuration.3\.4 Protections.WebHome@1734090244845-157.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="93" width="800"]]
343 +
344 +In this section:
345 +
346 +* Enable – a flag to enable the protection;
347 +* Delay before clearing the error, second;
348 +* Lock – a flag to block the error until the device is restarted.
349 +
350 +Conditions for removing the error:
351 +
352 +* the “Delay before clearing the error” time has passed from the device startup.
353 +
354 +(% class="box warningmessage" %)
355 +(((
356 +If there is the "WDT reset" error, **“Critical error” is generated.**
357 +)))
358 +
340 340  === Critical error ===
341 341  
342 -Parameters for generating the critical error are configured in the "Protections - Critical error" section:
361 +Some of the errors are system critical. A separate signal named "Critical error" indicates a BMS fault.
343 343  
344 -[[image:1734356802719-477.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="69" width="600"]]
363 +To change the critical error parameters, select the "Protections → Critical error" section:
345 345  
365 +[[image:1740756532131-419.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="118" width="800"]]
366 +
346 346  In this section:
347 347  
348 348  * Enable – a flag to enable the protection;
... ... @@ -350,18 +350,6 @@
350 350  * Delay before clearing the error;
351 351  * Lock – a flag to block the error until the device is restarted.
352 352  
353 -The critical error flag is generated if at least one of the following errors persists during the "Delay before setting the error" time:
374 +The "Critical error" signal is generated if at least one of the critical errors (see [[Errors>>doc:Battery management systems.Additional information.2\. Strings controllers\: signals and errors.WebHome||anchor="HErrors"]]) is generated during the Delay before setting the error time.
354 354  
355 -* «Battery cover»;
356 -* «Insulation fault»;
357 -* «CH contactor feedback error»;
358 -* «DCH contactor feedback error»;
359 -* «CH/DCH contactor feedback error»;
360 -* «Module offline».
361 -
362 -The critical error flag is cleared if there are no errors from the list above during the "Delay before clearing the error" time.
363 -
364 -(% class="box warningmessage" %)
365 -(((
366 -**When the critical error flag is present, all battery contactors open.**
367 -)))
376 +The “Critical error" signal is cleared if there are no errors from the list above during the “Delay before clearing the error” time.
1740756532131-419.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +15.7 KB
Content