... ... @@ -115,8 +115,6 @@
115 115  In this section:
116 116  
117 117  * Precharge current threshold to close the discharging contactor – a current value to ensure that precharge process has finished and it is allowed to close the discharging contactor, A;
118 -* Check voltages before and after contactors to finish precharging – a flag to check the voltages before and after contactors to ensure that precharge process has finished and it is allowed to close the discharging contactor;
119 -* Minimum voltage difference before and after contactors to finish precharging – a minimum voltage difference before and after contactors to ensure precharge process finished, V;
120 120  * Number of precharging attempts – maximum number of precharging attempts before setting the "Precharge error";
121 121  * Delay before current measurement – a delay before first current measurement after closing precharge, millisecond;
122 122  * Precharge time – a duration of closing the precharge contactor before closing the discharging contactor, millisecond;
... ... @@ -134,7 +134,10 @@
134 134  * voltages before and after contactors are not equal during the "Precharge time" after "Number of precharging attempts";
135 135  * power dissipated on the precharge resistor is above the maximum value during the “Delay before setting the 'Precharge error' when checking power” time.
136 136  
135 +(% class="box warningmessage" %)
136 +(((
137 137  Behavior of contactors at “Precharge error” is configured in corresponding contactor settings!
138 +)))
138 138  
139 139  === Charge ===
140 140  
... ... @@ -167,10 +167,8 @@
167 167  
168 168  The command to turn on the main charging contactor (“Charging”) can be issued both to the upper-level system via the CAN bus (external), and on the opto-relay of the device that serves to directly control the main charging contactor.
169 169  
170 -
171 171  In addition to controlling the charging contactors, the charge controller calculates and transmits to the upper-level system the value of the maximum allowable current, which can be used to charge the modular battery (“Charge current limit”). The calculation of the charging current of the entire battery is performed based on the number of battery modules operating per charge and the values of the current limits transmitted by them.
172 172  
173 -
174 174  The battery charge management is configured in the "Control - Charge" section:
175 175  
176 176  [[image:1734356553573-447.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="146" width="600"]]
1740750130950-113.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +46.3 KB
Content