Changes for page 3.3 Control
Last modified by Admin on 2025/06/11 15:52
Summary
-
Page properties (1 modified, 0 added, 0 removed)
-
Attachments (0 modified, 14 added, 0 removed)
- 1740749922669-238.png
- 1740750130950-113.png
- 1740750247231-926.png
- 1740750424118-190.png
- 1740750509436-756.png
- 1740750795356-352.png
- 1740750844486-213.png
- 1740750960467-987.png
- 1749656740041-432.png
- 1749656910340-570.png
- 1749657005161-877.png
- 1749657043032-397.png
- 1749657087238-544.png
- 1749657114587-360.png
Details
- Page properties
-
- Content
-
... ... @@ -62,12 +62,12 @@ 62 62 In “Always on” mode main contactor closes if all the following is true: 63 63 64 64 * Other contactors are open; 65 -* There are no errors from the "Errors 1, 2..." bitfileds.65 +* There are no errors from the "Errors ..." bitfiled. 66 66 67 67 In “Always on” mode main contactor opens if all the following is true: 68 68 69 69 * Other contactors are open; 70 -* There is an error from the the "Errors 1, 2..." bitfileds.70 +* There is an error from the the "Errors ..." bitfiled. 71 71 72 72 In “Automatic” mode, the main contactor closes by internal algorithms at the same time with other contactors. 73 73 ... ... @@ -101,8 +101,41 @@ 101 101 102 102 To change the parameters for generating status signals when discharging the battery, select the section “Control → Discharging status”: 103 103 104 -[[image:1740749862820-455.png]] 104 +[[image:1740749862820-455.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="95" width="800"]]In this section: 105 105 106 +* Current corresponding to discharging – a current level to set the "Discharging current present" signal, A; 107 +* Current corresponding to no discharging – a current level to clear the "Discharging current present" signal, A. 108 + 109 +=== Precharge === 110 + 111 +To change the precharge parameters, select the section “Control → Precharge”: 112 + 113 +[[image:1740749922669-238.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="165" width="800"]] 114 + 115 +In this section: 116 + 117 +* Precharge current threshold to close the discharging contactor – a current value to ensure that precharge process has finished and it is allowed to close the discharging contactor, A; 118 +* Number of precharging attempts – maximum number of precharging attempts before setting the "Precharge error"; 119 +* Delay before current measurement – a delay before first current measurement after closing precharge, millisecond; 120 +* Precharge time – a duration of closing the precharge contactor before closing the discharging contactor, millisecond; 121 +* Relaxation between attempts – a duration between precharge attempts, millisecond; 122 +* Check the power dissipated in the preacharge resistor - a flag to enable the calculation of power dissipated in precharge resistor; 123 +* Precharge resistor resistance, Ohm; 124 +* Maximum allowable power dissipated in the resistor, W; 125 +* Delay before setting the "Precharge error" when checking power, millisecond; 126 +* Delay before clearing the "Precharge error", second; 127 +* Lock – a flag to block the error until the device is restarted. 128 + 129 +“Precharge error” generation conditions if any of the following is true: 130 + 131 +* the precharge current does not decrease during the "Precharge time" after "Number of precharging attempts"; 132 +* power dissipated on the precharge resistor is above the maximum value during the “Delay before setting the 'Precharge error' when checking power” time. 133 + 134 +(% class="box warningmessage" %) 135 +((( 136 +Behavior of contactors at “Precharge error” is configured in corresponding contactor settings! 137 +))) 138 + 106 106 === Charge === 107 107 108 108 The BMS Main X device manages the parallel connection of the battery modules and the connection of the battery to the charging circuit. ... ... @@ -113,11 +113,10 @@ 113 113 1. Charging is allowed provided that all battery modules are balanced (Balanced). 114 114 1. Charging is allowed for most balanced battery modules (Partially balanced). Unbalanced modules are disconnected from the common bus and do not participate in the charging. 115 115 116 -The device controls two processes: joining battery modules and closing the main charging contactor. 149 +The device controls two processes: **joining battery modules **and **closing the main charging contactor.** 117 117 151 +The operation of the **joining battery modules** is described by the following steps: 118 118 119 -The operation of the joining battery modules is described by the following steps: 120 - 121 121 1. Battery modules are disabled. When the “Join to charge” request is received and the voltage and current unbalance errors (Voltage unbalance (CH), Current unbalance (CH), Charging current unbalance) are cleared, go to step 2. 122 122 1. Checking the voltage unbalance of battery modules (the duration of the check is set in the settings). If there is no imbalance or errors are ignored (“Always on” and “Partially balanced”), go to step 3, otherwise open all charging contactors, and go to step 1. 123 123 1. Closing the precharging contactors of the battery modules (optional). Go to step 4. ... ... @@ -125,9 +125,9 @@ 125 125 1. Checking intermodular balancing currents (the duration of the check is set in the settings). If there is no current unbalance (“Current unbalance (CH)”) or errors are ignored (“Always on”), go to step 6, otherwise open all charging contactors, and go to step 1. 126 126 1. The battery modules are joined. If the “Join to charge” request is cleared or the "Charging current unbalance" and "Critical error" errors occur, go to step 1. 127 127 128 -The operation of the main charging contactor is described in the following steps: 160 +The operation of **closing the main charging contactor** is described in the following steps: 129 129 130 -1. The main charging contactor is open. When the “Charge request” is received, the voltage and currentunbalanceerrors(“Voltageunbalance (CH)”, “Currentunbalance(CH)”, “Charging currentunbalance”) are cleared, and the battery modules are joined, go to step 2.162 +1. The main charging contactor is open. When the “Charge request” is received, there are no errors from the "Errors ..." bitfield, and the battery modules are joined, go to step 2. 131 131 1. Closing the main precharging contactor (optional). Go to step 3. 132 132 1. Closing the main charging contactor ("Charging" signal). Go to step 4. 133 133 1. The main charging contactor is closed. If the "Charge request" is cleared, the battery modules are disconnected, or the "Critical error" occurs, go to step 1. ... ... @@ -134,13 +134,11 @@ 134 134 135 135 The command to turn on the main charging contactor (“Charging”) can be issued both to the upper-level system via the CAN bus (external), and on the opto-relay of the device that serves to directly control the main charging contactor. 136 136 137 - 138 138 In addition to controlling the charging contactors, the charge controller calculates and transmits to the upper-level system the value of the maximum allowable current, which can be used to charge the modular battery (“Charge current limit”). The calculation of the charging current of the entire battery is performed based on the number of battery modules operating per charge and the values of the current limits transmitted by them. 139 139 140 - 141 141 The battery charge management is configured in the "Control - Charge" section: 142 142 143 -[[image:17 34356553573-447.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="146" width="600"]]173 +[[image:1749657043032-397.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="253" width="800"]] 144 144 145 145 In this section: 146 146 ... ... @@ -149,19 +149,23 @@ 149 149 ** Always on – charging is always allowed; 150 150 ** Balanced – charging is allowed provided that all battery modules are balanced; 151 151 ** Partially balanced – charging is allowed for most balanced battery modules; 152 -* Current corresponding to charging – a current level to set the "Charging current present" signal, A; 153 -* Current corresponding to no charging – a current level to clear the "Charging current present" signal, A; 154 -* Maximum current to rejoin modules – a maximum allowable current at which rejoining of battery modules is allowed, A; 155 -* Checking voltages time – a time of checking voltages of battery modules, ms; 156 -* Pre-balancing modules time – a time of pre-charging battery modules, ms; 157 -* Balancing modules time – a time of balancing battery modules, ms; 158 -* Control the precharging relay – a flag to control the main precharging contactor; 159 -* Precharging time – a time of precharging, ms; 160 -* Cancel charging without a delay; 182 +* Minimum number of modules allowed to join – a minimum number of battery modules that can be connected in parallel; 183 +* Allowable battery current to rejoin modules – a battery current at which joining of battery modules is permitted, A; 184 +* Allowable voltage difference to rejoin modules – a difference between the voltage of the disconnected module and the battery voltage at which its joining is permitted, V; 185 +* Checking voltages time – a time of checking voltages of battery modules before starting joining modules, millisecond; 186 +* Module balancing time – a time of balancing battery modules after joining modules and before closing main charging contactor, millisecond; 187 +* Interrupt balancing when modules are joined – a flag to break balancing time after all modules are joined; 188 +* Control the precharging contactor – a flag to control the main precharging contactor; 161 161 * Canceling charging time – a delay before opening the main charging contactor, ms; 162 -* Limit charging current – a flag that allows to limit the charging current of a modular battery so that the current of each battery module does not exceed its maximum allowable charge current; 163 -* Slew rate – a rate of change of the charge current limit when the “Limit charging current” flag is set, А/s; 164 -* Disconnect modules not ready to charge – a flag for disconnecting modules that have the “Ready to charge” signal cleared. 190 +* Disconnect modules that are not ready to charge – a flag for disconnecting modules that have the “Ready to charge” signal cleared. 191 +* Disconnect all modules if one is not ready to charge – a flag for disconnecting all modules if any of the modules have the “Ready to charge” signal cleared; 192 +* Join modules on the “Charge request” signal – a flag to enable automatic modules joining if “Charge request” signal appears; 193 +* Regulator: Keep battery module currents below limits – a flag to enable regulation of module currents to be below module current limit; 194 +* Regulator: Gain – a gain of current regulator; 195 +* Maximum charge current limit – a maximum allowed charging current of all battery, A; 196 +* Errors to disconnect all battery modules – errors that cause all battery modules to be disconnected from the common bus; 197 +* Errors to open the charging contactor – errors that cause the main charging contactor "Charging" to open; 198 +* Switch of the charging contactor on errors without a delay – a flag that allows the main charging contactor “Charging” to be opened without delay if errors are detected. 165 165 166 166 === Discharge === 167 167 ... ... @@ -173,11 +173,10 @@ 173 173 1. Discharging is allowed provided that all battery modules are balanced (Balanced). 174 174 1. Discharging is allowed for most balanced battery modules (Partially balanced). Unbalanced modules are disconnected from the common bus and do not participate in the discharging. 175 175 176 -The device controls two processes: joining battery modules and closing the main discharging contactor. 210 +The device controls two processes: **joining battery modules** and **closing the main discharging contactor**. 177 177 212 +The operation of the** joining battery modules** is described by the following steps: 178 178 179 -The operation of the joining battery modules is described by the following steps: 180 - 181 181 1. Battery modules are disabled. When the “Join to discharge” request is received and the voltage and current unbalance errors (Voltage unbalance (DCH), Current unbalance (DCH), Discharging current unbalance) are cleared, go to step 2. 182 182 1. Checking the voltage unbalance of battery modules (the duration of the check is set in the settings). If there is no imbalance or errors are ignored (“Always on” and “Partially balanced”), go to step 3, otherwise open all discharging contactors, and go to step 1. 183 183 1. Closing the precharging contactors of the battery modules (optional). Go to step 4. ... ... @@ -185,9 +185,9 @@ 185 185 1. Checking intermodular balancing currents (the duration of the check is set in the settings). If there is no current unbalance (“Current unbalance (DCH)”) or errors are ignored (“Always on”), go to step 6, otherwise open all discharging contactors, and go to step 1. 186 186 1. The battery modules are joined. If the “Join to discharge” request is cleared or "Discharging current unbalance" and "Critical error" errors occur, go to step 1. 187 187 188 -The operation of the main discharging contactor is described in the following steps: 221 +The operation of **closing the main discharging contactor **is described in the following steps: 189 189 190 -1. The main discharging contactor is open. When the “Discharge request” is received, the voltage and currentunbalanceerrors(“Voltageunbalance (DCH)”, “Currentunbalance(DCH)”, “Discharging current unbalance”) are cleared, and the battery modules are joined, go to step 2.223 +1. The main discharging contactor is open. When the “Discharge request” is received, there are no errors from the "Errors ..." bitfield, and the battery modules are joined, go to step 2. 191 191 1. Closing the main precharging contactor (optional). Go to step 3. 192 192 1. Closing the main discharging contactor ("Discharging" signal). Go to step 4. 193 193 1. The main discharging contactor is closed. If the "Discharge request" is cleared, the battery modules are disconnected, or the "Critical error" occurs, go to step 1. ... ... @@ -194,14 +194,13 @@ 194 194 195 195 The command to turn on the main discharging contactor (“Discharging”) can be issued both to the upper-level system via the CAN bus (external), and on the opto-relay of the device that serves to directly control the main discharging contactor. 196 196 197 - 198 198 In addition to controlling the discharging contactors, the discharge controller calculates and transmits to the upper-level system the value of the maximum allowable current, which can be used to discharge the modular battery (“Discharge current limit”). The calculation of the discharging current of the entire battery is performed based on the number of battery modules operating per discharge and the values of the current limits transmitted by them. 199 199 200 - 201 201 The battery discharge management is configured in the "Control - Discharge" section: 202 202 203 -[[image:1734356572308-630.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="139" width="600"]] 204 204 235 +[[image:1749657087238-544.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="250" width="800"]] 236 + 205 205 In this section: 206 206 207 207 * Enable – a flag to enable battery discharge controller; ... ... @@ -209,44 +209,106 @@ 209 209 ** Always on – discharging is always allowed; 210 210 ** Balanced – discharging is allowed provided that all battery modules are balanced; 211 211 ** Partially balanced – discharging is allowed for most balanced battery modules; 212 -* Current corresponding to discharging – a current level to set the "Discharging current present" signal, A; 213 -* Current corresponding to no discharging – a current level to clear the "Discharging current present" signal, A; 214 -* Maximum current to rejoin modules – a maximum allowable current at which rejoining of battery modules is allowed, A; 215 -* Checking voltages time – a time of checking voltages of battery modules, ms; 216 -* Pre-balancing modules time – a time of precharging battery modules, ms; 217 -* Balancing modules time – a time of balancing battery modules, ms; 218 -* Control the precharging relay – a flag to control the main precharging contactor; 219 -* Precharging time – a time of precharging, ms; 220 -* Cancel discharging without a delay; 221 -* Canceling discharging time – a delay before opening the main discharging contactor, ms; 222 -* Limit module current – a flag that allows to limit the discharging current of a modular battery so that the current of each battery module does not exceed its maximum allowable discharge current; 223 -* Slew rate – a rate of change of the discharge current limit when the “Limit module current” flag is set, А/s; 224 -* Disconnect modules not ready to discharge – a flag for disconnecting modules that have the “Ready to discharge” signal cleared. 244 +* Minimum number of modules allowed to join – a minimum number of battery modules that can be connected in parallel; 245 +* Allowable battery current to rejoin modules – a battery current at which joining of battery modules is permitted, A; 246 +* Allowable voltage difference to rejoin modules – a difference between the voltage of the disconnected module and the battery voltage at which its joining is permitted, V; 247 +* Checking voltages time – a time of checking voltages of battery modules before starting joining modules, millisecond; 248 +* Module balancing time – a time of balancing battery modules after joining modules and before closing main discharging contactor, millisecond; 249 +* Interrupt balancing when modules are joined – a flag to break balancing time after all modules are joined; 250 +* Control the precharging contactor – a flag to control the main precharging contactor; 251 +* Canceling discharging time – a delay before opening the main discharging contactor, millisecond; 252 +* Disconnect modules that are not ready to discharge – a flag for disconnecting modules that have the “Ready to discharge” signal cleared. 253 +* Disconnect all modules if one is not ready to discharge – a flag for disconnecting all modules if one of the modules have the “Ready to discharge” signal cleared; 254 +* Join modules on the “Discharge request” signal – a flag to enable automatic modules joining if “Discharge request” signal appears; 255 +* Regulator: Keep battery module currents below limits – a flag to enable regulation of module currents to be below module current limit; 256 +* Regulator: Gain – a gain of current regulator; 257 +* Maximum discharge current limit – a maximum allowed discharging current of all the battery, A; 258 +* Errors to disconnect all battery modules – errors that cause all battery modules to be disconnected from the common bus; 259 +* Errors to open the discharging contactor – errors that cause the main discharging contactor "Discharging" to open, 260 +* Switch of the discharging contactor on errors without a delay – a flag that allows the main discharging contactor “Discharging” to be opened without delay if errors are detected. 225 225 226 226 === Charge/Discharge === 227 227 228 228 The BMS Main X can control the charging/discharging contactor that is used to both charge and discharge the battery. 229 229 230 - The charge/discharge contactor(“Charging/Discharging”signal)receivesa“Charging” signal(generated by the charge controller)if a “Charge request” signal is received from the upper-level system. In all other cases,the "Discharging" signal isoutputtothecontactor(generated by the discharge controller).266 +Charge/Discharge contactor has two algorithms of operation: 231 231 232 -The charge/discharge contactor control is configured in the “Control – Charge/Discharge” section: 268 +* Dependent - Charge/Discharge contactor depends on Charge and Discharge algorithms and their signals and behaves as Charging contactor if "Charging" signal is set, otherwise – as Discharging contactor; 269 +* Independent - Charge/Discharge contactor is based on its own controller. 233 233 234 -[[image:1734356572312-596.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="58" width="600"]] 271 +(% class="box warningmessage" %) 272 +((( 273 +**Warning!** 274 +Charge/Discharge algorithms on BMS Main X and on battery modules controllers must **be the same**! 275 +))) 235 235 277 +The charging/discharging controller supports the following modes: 278 + 279 +1. Charging/Discharging is always allowed (Always on) – the device ignores voltage and current unbalance of the battery modules and commands to close the discharging contactors of the battery modules and the main discharging contactor. 280 +1. Charging/Discharging is allowed if all battery modules are balanced (Balanced). 281 +1. Charging/Discharging is allowed for most balanced battery modules (Partially balanced). Unbalanced modules are disconnected from the common bus and do not participate in the discharging. 282 + 283 +The device controls two processes: **joining battery modules** and **closing the main charging/discharging contactor**. 284 + 285 +The operation of the **joining battery modules** depends on the signal received: 286 + 287 +* If "Join to charge" is received, joining procedure is done as described in [[Charge>>doc:||anchor="HCharge"]] section; 288 +* If "Join to discharge" is received, joining procedure is done as described in [[Discharge>>doc:||anchor="HDischarge"]] section; 289 +* If both signals received, "Join to charge" has a priority. 290 + 291 +The operation of **closing main charging/discharging contactor **depends on the signal received: 292 + 293 +* If "Charge request" is received, procedure is done as described in [[Charge>>doc:||anchor="HCharge"]] section; 294 +* If "Discharge request" is received, procedure is done as described in [[Discharge>>doc:||anchor="HDischarge"]] section; 295 +* If both signals received, "Charge request" has a priority. 296 + 297 +In addition, the charge/discharge controller calculates and transmits to the upper-level system the maximum allowable current value with which the modular battery can be charged ("Charge current limit") and discharged ("Discharge current limit"), as well as the maximum regeneration current value with which the modular battery can be charged during operation under load ("Regeneration current limit"). The calculation of the charge, discharge and regeneration currents of the entire battery is performed based on the number of battery modules operating for charge or discharge and the maximum charge and discharge current values transmitted by them: 298 + 299 +* "Charge current limit" and "Regeneration current limit" are calculated only if there is "Charge request"; 300 +* "Discharge current limit" is calculated only if there is "Discharge request". 301 + 302 +The charge/discharge contactor control is configured in the “Control → Charge/Discharge” section: 303 + 304 +[[image:1749657114587-360.png]] 305 + 236 236 In this section: 237 237 238 -* Enable – a flag to enable the charge/discharge controller. 308 +* Enable – a flag to enable battery charge/discharge controller; 309 +* Mode: 310 +** Dependent - Charge/Discharge contactor depends on Charge and Discharge algorithms and their signals; 311 +** Independent - Charge/Discharge contactor is based on its own controller. 312 +* Algorithm: 313 +** Always on – discharging is always allowed; 314 +** Balanced – discharging is allowed provided that all battery modules are balanced; 315 +** Partially balanced – discharging is allowed for most balanced battery modules; 316 +* Minimum number of modules allowed to join – a minimum number of battery modules that can be connected in parallel; 317 +* Allowable battery current to rejoin modules – a battery current at which joining of battery modules is permitted, A; 318 +* Allowable voltage difference to rejoin modules – a difference between the voltage of the disconnected module and the battery voltage at which its joining is permitted, V; 319 +* Checking voltages time – a time of checking voltages of battery modules before starting joining modules, millisecond; 320 +* Balancing modules time – a time of balancing battery modules after joining modules and before closing main discharging contactor, millisecond; 321 +* Control the precharging contactor – a flag to control the main precharging contactor; 322 +* Canceling discharging time – a delay before opening the main discharging contactor, millisecond; 323 +* Disconnect modules that are not ready to charge – a flag for disconnecting modules that have the “Ready to charge” signal cleared; 324 +* Disconnect modules that are not ready to discharge – a flag for disconnecting modules that have the “Ready to discharge” signal cleared; 325 +* Join modules on the “Charge request” signal – a flag to enable automatic modules joining if “Charge request” signal appears; 326 +* Join modules on the “Discharge request” signal – a flag to enable automatic modules joining if “Discharge request” signal appears; 327 +* Maximum charge current limit – a maximum allowed charging current of all the battery, A; 328 +* Maximum discharge current limit – a maximum allowed discharging current of all the battery, A; 329 +* Errors to disconnect all battery modules – errors that cause all battery modules to be disconnected from the common bus; 330 +* Errors to open the charging/discharging contactor – errors that cause the main charging/discharging contactor "Discharging" to open, 331 +* Switch of the charging/discharging contactor on errors without a delay – a flag that allows the main charging/discharging contactor to be opened without delay if errors are detected. 239 239 240 240 === Module balancing === 241 241 242 242 The BMS Main X device supports active balancing of battery modules both in the process of charging and in the process of discharging the battery. 243 -\\When the battery is charging, balancing is performed by disconnecting the most charged battery modules from the common bus. Before disconnecting the modules, the BMS Main X sends a request to the upper-level system (charger) to reduce the charge current to zero, and after the current becomes zero, disconnects the most charged battery modules. 244 244 337 +When the battery is charging, balancing is performed by disconnecting the most charged battery modules from the common bus. Before disconnecting the modules, the BMS Main X sends a request to the upper-level system (charger) to reduce the charge current to zero, and after the current becomes zero, disconnects the most charged battery modules. 338 + 245 245 When the battery is discharging, balancing is performed by disconnecting the most discharged battery modules from the common bus. Battery modules are disconnected only if the battery discharge current has dropped to the threshold value set in the device settings. 246 246 247 247 Module balancing is configured in the “Control – Module balancing” section: 248 248 249 -[[image:17 34356572313-823.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="74" width="600"]]343 +[[image:1740750509436-756.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="148" width="800"]] 250 250 251 251 In this section: 252 252 ... ... @@ -253,6 +253,84 @@ 253 253 * Balance on charging – a flag to enable module balancing when the battery is charging; 254 254 * Delta voltage – a voltage difference at which the most charged modules are switched off (those modules whose voltage exceeds the minimum voltage among the modules by the “Delta voltage” value are switched off), V; 255 255 * Delta current – a current difference at which the most charged modules are switched off (those modules are switched off, the charge current of which is less than the maximum charge current among the modules by the “Delta current” value), A; 256 -* Waiting time – a time the battery modules are in the disconnected state (after this time, the modules previously disconnected during the balancing process are reconnected to the common bus), s; 257 -* Balance on discharging – a flag to enable module balancing when the battery is discharging; 350 +* Detection time – a time for module to be estimated as unbalanced, millisecond; 351 +* Waiting time – a time the battery modules are in the disconnected state (after this time, the modules previously disconnected during the balancing process are reconnected to the common bus), second; 352 +* Balance on discharging – a flag to enable module balancing when the battery is discharging (if flag is enabled operation logic and settings are equal to balancing on charging); 258 258 * Required discharging current – a value of the discharge current at which the device switches off the most discharged battery modules, A. 354 + 355 +=== Heater === 356 + 357 +To change the parameters of the heater control algorithm, select the "Control → Heater" section: 358 + 359 +[[image:1740750795356-352.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="161" width="800"]] 360 + 361 +In this section: 362 + 363 +* Enable – a flag to enable the heater control; 364 +* Charge: Minimum module temperature, °C; 365 +* Charge: Tolerant module temperature, °C; 366 +* Discharge: Minimum module, °C; 367 +* Discharge: Tolerant module temperature, °C; 368 +* Delay before starting the heater, millisecond; 369 +* Delay before stopping the heater, millisecond; 370 +* Errors to turn off the heater – errors that cause the heater to shut down. 371 + 372 +Conditions for signal generation: 373 + 374 +* the minimum temperature among all cells of the battery is less than the “Charge (Discharge): Minimum cell temperature” value during the “Delay before starting the heater” time. 375 + 376 +Conditions for clearing the signal: 377 + 378 +* the minimum temperature among all cells of the battery is greater than the “Charge (Discharge): Tolerant cell temperature” value during the “Delay before stopping the heater” time. 379 + 380 +=== Cooler === 381 + 382 +To change the parameters of the cooler control algorithm, select the "Control → Cooler" section: 383 + 384 +[[image:1740750844486-213.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="158" width="800"]] 385 + 386 +In this section: 387 + 388 +* Enable – a flag to enable the cooler control; 389 +* Charge: Maximum module temperature, °C; 390 +* Charge: Tolerant module temperature, °C; 391 +* Discharge: Maximum module temperature, °C; 392 +* Discharge: Tolerant module temperature, °C; 393 +* Delay before starting the cooler, millisecond; 394 +* Delay before stopping the cooler, millisecond; 395 +* Errors 1 (2) to turn off the cooler – errors that cause the cooler to shut down. 396 + 397 +Conditions for signal generation: 398 + 399 +* the maximum temperature among all cells of the battery is greater than the “Charge (Discharge): Maximum cell temperature” value during the “Delay before starting the cooler” time. 400 + 401 +Conditions for clearing the signal: 402 + 403 +* the maximum temperature among all cells of the battery is less than the “Charge (Discharge): Tolerant cell temperature” value during the “Delay before stopping the cooler” time. 404 + 405 +=== Coolant pump === 406 + 407 +To change the parameters of the coolant pump control algorithm, select the "Control → Coolant pump" section: 408 + 409 +[[image:1740750960467-987.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="154" width="800"]] 410 + 411 +In this section: 412 + 413 +* Enable – a flag to enable the coolant pump control; 414 +* Charge: Maximum cell temperature difference, °C; 415 +* Charge: Tolerant cell temperature difference, °C; 416 +* Discharge: Maximum cell temperature difference, °C; 417 +* Discharge: Tolerant cell temperature difference, °C; 418 +* Delay before starting the coolant pump, millisecond; 419 +* Delay before stopping the coolant pump, millisecond; 420 +* Errors to turn off the coolant pump – errors that cause the coolant pump to shut down. 421 + 422 +Conditions for signal generation: 423 + 424 +* the maximum temperature difference among all cells of the battery is greater than the “Charge (Discharge): Maximum cell temperature difference” value during the “Delay before starting the coolant pump” time. 425 + 426 +Conditions for clearing the signal: 427 + 428 +* the maximum temperature difference among all cells of the battery is less than the “Charge (Discharge): Tolerant cell temperature difference” value during the “Delay before stopping the coolant pump” time. 429 + 430 +
- 1740749922669-238.png
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.admin - Size
-
... ... @@ -1,0 +1,1 @@ 1 +34.6 KB - Content
- 1740750130950-113.png
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.admin - Size
-
... ... @@ -1,0 +1,1 @@ 1 +46.3 KB - Content
- 1740750247231-926.png
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.admin - Size
-
... ... @@ -1,0 +1,1 @@ 1 +44.5 KB - Content
- 1740750424118-190.png
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.admin - Size
-
... ... @@ -1,0 +1,1 @@ 1 +51.7 KB - Content
- 1740750509436-756.png
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.admin - Size
-
... ... @@ -1,0 +1,1 @@ 1 +19.8 KB - Content
- 1740750795356-352.png
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.admin - Size
-
... ... @@ -1,0 +1,1 @@ 1 +21.9 KB - Content
- 1740750844486-213.png
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.admin - Size
-
... ... @@ -1,0 +1,1 @@ 1 +22.3 KB - Content
- 1740750960467-987.png
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.admin - Size
-
... ... @@ -1,0 +1,1 @@ 1 +23.8 KB - Content
- 1749656740041-432.png
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.admin - Size
-
... ... @@ -1,0 +1,1 @@ 1 +52.8 KB - Content
- 1749656910340-570.png
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.admin - Size
-
... ... @@ -1,0 +1,1 @@ 1 +52.0 KB - Content
- 1749657005161-877.png
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.admin - Size
-
... ... @@ -1,0 +1,1 @@ 1 +58.3 KB - Content
- 1749657043032-397.png
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.admin - Size
-
... ... @@ -1,0 +1,1 @@ 1 +52.8 KB - Content
- 1749657087238-544.png
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.admin - Size
-
... ... @@ -1,0 +1,1 @@ 1 +52.0 KB - Content
- 1749657114587-360.png
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.admin - Size
-
... ... @@ -1,0 +1,1 @@ 1 +58.3 KB - Content