... ... @@ -301,7 +301,7 @@
301 301  
302 302  The charge/discharge contactor control is configured in the “Control → Charge/Discharge” section:
303 303  
304 -[[image:1749657114587-360.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="284" width="800"]]
304 +[[image:1749657114587-360.png]]
305 305  
306 306  In this section:
307 307  
... ... @@ -317,8 +317,7 @@
317 317  * Allowable battery current to rejoin modules – a battery current at which joining of battery modules is permitted, A;
318 318  * Allowable voltage difference to rejoin modules – a difference between the voltage of the disconnected module and the battery voltage at which its joining is permitted, V;
319 319  * Checking voltages time – a time of checking voltages of battery modules before starting joining modules, millisecond;
320 -* Module balancing time – a time of balancing battery modules after joining modules and before closing main discharging contactor, millisecond;
321 -* Interrupt balancing when modules are joined – a flag to break balancing time after all modules are joined;
320 +* Balancing modules time – a time of balancing battery modules after joining modules and before closing main discharging contactor, millisecond;
322 322  * Control the precharging contactor – a flag to control the main precharging contactor;
323 323  * Canceling discharging time – a delay before opening the main discharging contactor, millisecond;
324 324  * Disconnect modules that are not ready to charge – a flag for disconnecting modules that have the “Ready to charge” signal cleared;
... ... @@ -325,8 +325,6 @@
325 325  * Disconnect modules that are not ready to discharge – a flag for disconnecting modules that have the “Ready to discharge” signal cleared;
326 326  * Join modules on the “Charge request” signal – a flag to enable automatic modules joining if “Charge request” signal appears;
327 327  * Join modules on the “Discharge request” signal – a flag to enable automatic modules joining if “Discharge request” signal appears;
328 -* Regulator: Keep battery module currents below limits – a flag to enable regulation of module currents to be below module current limit;
329 -* Regulator: Gain – a gain of current regulator;
330 330  * Maximum charge current limit – a maximum allowed charging current of all the battery, A;
331 331  * Maximum discharge current limit – a maximum allowed discharging current of all the battery, A;
332 332  * Errors to disconnect all battery modules – errors that cause all battery modules to be disconnected from the common bus;