171 171  The battery charge management is configured in the "Control - Charge" section:
172 172  
173 -[[image:1749657043032-397.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="253" width="800"]]
173 +[[image:1740750130950-113.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="219" width="800"]]
174 174  
175 175  In this section:
176 176  
... ... @@ -183,15 +183,12 @@
183 183  * Allowable battery current to rejoin modules – a battery current at which joining of battery modules is permitted, A;
184 184  * Allowable voltage difference to rejoin modules – a difference between the voltage of the disconnected module and the battery voltage at which its joining is permitted, V;
185 185  * Checking voltages time – a time of checking voltages of battery modules before starting joining modules, millisecond;
186 -* Module balancing time – a time of balancing battery modules after joining modules and before closing main charging contactor, millisecond;
187 -* Interrupt balancing when modules are joined – a flag to break balancing time after all modules are joined;
186 +* Balancing modules time – a time of balancing battery modules after joining modules and before closing main charging contactor, millisecond;
188 188  * Control the precharging contactor – a flag to control the main precharging contactor;
189 189  * Canceling charging time – a delay before opening the main charging contactor, ms;
190 190  * Disconnect modules that are not ready to charge – a flag for disconnecting modules that have the “Ready to charge” signal cleared.
191 191  * Disconnect all modules if one is not ready to charge – a flag for disconnecting all modules if any of the modules have the “Ready to charge” signal cleared;
192 192  * Join modules on the “Charge request” signal – a flag to enable automatic modules joining if “Charge request” signal appears;
193 -* Regulator: Keep battery module currents below limits – a flag to enable regulation of module currents to be below module current limit;
194 -* Regulator: Gain – a gain of current regulator;
195 195  * Maximum charge current limit – a maximum allowed charging current of all battery, A;
196 196  * Errors to disconnect all battery modules – errors that cause all battery modules to be disconnected from the common bus;
197 197  * Errors to open the charging contactor – errors that cause the main charging contactor "Charging" to open;
... ... @@ -231,9 +231,8 @@
231 231  
232 232  The battery discharge management is configured in the "Control - Discharge" section:
233 233  
231 +[[image:1740750247231-926.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="218" width="800"]]
234 234  
235 -[[image:1749657087238-544.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="250" width="800"]]
236 -
237 237  In this section:
238 238  
239 239  * Enable – a flag to enable battery discharge controller;
... ... @@ -245,15 +245,12 @@
245 245  * Allowable battery current to rejoin modules – a battery current at which joining of battery modules is permitted, A;
246 246  * Allowable voltage difference to rejoin modules – a difference between the voltage of the disconnected module and the battery voltage at which its joining is permitted, V;
247 247  * Checking voltages time – a time of checking voltages of battery modules before starting joining modules, millisecond;
248 -* Module balancing time – a time of balancing battery modules after joining modules and before closing main discharging contactor, millisecond;
249 -* Interrupt balancing when modules are joined – a flag to break balancing time after all modules are joined;
244 +* Balancing modules time – a time of balancing battery modules after joining modules and before closing main discharging contactor, millisecond;
250 250  * Control the precharging contactor – a flag to control the main precharging contactor;
251 251  * Canceling discharging time – a delay before opening the main discharging contactor, millisecond;
252 252  * Disconnect modules that are not ready to discharge – a flag for disconnecting modules that have the “Ready to discharge” signal cleared.
253 253  * Disconnect all modules if one is not ready to discharge – a flag for disconnecting all modules if one of the modules have the “Ready to discharge” signal cleared;
254 254  * Join modules on the “Discharge request” signal – a flag to enable automatic modules joining if “Discharge request” signal appears;
255 -* Regulator: Keep battery module currents below limits – a flag to enable regulation of module currents to be below module current limit;
256 -* Regulator: Gain – a gain of current regulator;
257 257  * Maximum discharge current limit – a maximum allowed discharging current of all the battery, A;
258 258  * Errors to disconnect all battery modules – errors that cause all battery modules to be disconnected from the common bus;
259 259  * Errors to open the discharging contactor – errors that cause the main discharging contactor "Discharging" to open,
... ... @@ -301,7 +301,7 @@
301 301  
302 302  The charge/discharge contactor control is configured in the “Control → Charge/Discharge” section:
303 303  
304 -[[image:1749657114587-360.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="284" width="800"]]
297 +[[image:1740750424118-190.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="250" width="800"]]
305 305  
306 306  In this section:
307 307  
... ... @@ -317,8 +317,7 @@
317 317  * Allowable battery current to rejoin modules – a battery current at which joining of battery modules is permitted, A;
318 318  * Allowable voltage difference to rejoin modules – a difference between the voltage of the disconnected module and the battery voltage at which its joining is permitted, V;
319 319  * Checking voltages time – a time of checking voltages of battery modules before starting joining modules, millisecond;
320 -* Module balancing time – a time of balancing battery modules after joining modules and before closing main discharging contactor, millisecond;
321 -* Interrupt balancing when modules are joined – a flag to break balancing time after all modules are joined;
313 +* Balancing modules time – a time of balancing battery modules after joining modules and before closing main discharging contactor, millisecond;
322 322  * Control the precharging contactor – a flag to control the main precharging contactor;
323 323  * Canceling discharging time – a delay before opening the main discharging contactor, millisecond;
324 324  * Disconnect modules that are not ready to charge – a flag for disconnecting modules that have the “Ready to charge” signal cleared;
... ... @@ -325,8 +325,6 @@
325 325  * Disconnect modules that are not ready to discharge – a flag for disconnecting modules that have the “Ready to discharge” signal cleared;
326 326  * Join modules on the “Charge request” signal – a flag to enable automatic modules joining if “Charge request” signal appears;
327 327  * Join modules on the “Discharge request” signal – a flag to enable automatic modules joining if “Discharge request” signal appears;
328 -* Regulator: Keep battery module currents below limits – a flag to enable regulation of module currents to be below module current limit;
329 -* Regulator: Gain – a gain of current regulator;
330 330  * Maximum charge current limit – a maximum allowed charging current of all the battery, A;
331 331  * Maximum discharge current limit – a maximum allowed discharging current of all the battery, A;
332 332  * Errors to disconnect all battery modules – errors that cause all battery modules to be disconnected from the common bus;