Changes for page 3.3 Control

Last modified by Admin on 2025/06/11 15:52

From version 28.1
edited by Admin
on 2025/06/11 15:51
Change comment: Uploaded new attachment "1749657087238-544.png", version {1}
To version 30.1
edited by Admin
on 2025/06/11 15:52
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -170,7 +170,7 @@
170 170  
171 171  The battery charge management is configured in the "Control - Charge" section:
172 172  
173 -[[image:1740750130950-113.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="219" width="800"]]
173 +[[image:1749657043032-397.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="253" width="800"]]
174 174  
175 175  In this section:
176 176  
... ... @@ -183,12 +183,15 @@
183 183  * Allowable battery current to rejoin modules – a battery current at which joining of battery modules is permitted, A;
184 184  * Allowable voltage difference to rejoin modules – a difference between the voltage of the disconnected module and the battery voltage at which its joining is permitted, V;
185 185  * Checking voltages time – a time of checking voltages of battery modules before starting joining modules, millisecond;
186 -* Balancing modules time – a time of balancing battery modules after joining modules and before closing main charging contactor, millisecond;
186 +* Module balancing time – a time of balancing battery modules after joining modules and before closing main charging contactor, millisecond;
187 +* Interrupt balancing when modules are joined – a flag to break balancing time after all modules are joined;
187 187  * Control the precharging contactor – a flag to control the main precharging contactor;
188 188  * Canceling charging time – a delay before opening the main charging contactor, ms;
189 189  * Disconnect modules that are not ready to charge – a flag for disconnecting modules that have the “Ready to charge” signal cleared.
190 190  * Disconnect all modules if one is not ready to charge – a flag for disconnecting all modules if any of the modules have the “Ready to charge” signal cleared;
191 191  * Join modules on the “Charge request” signal – a flag to enable automatic modules joining if “Charge request” signal appears;
193 +* Regulator: Keep battery module currents below limits – a flag to enable regulation of module currents to be below module current limit;
194 +* Regulator: Gain – a gain of current regulator;
192 192  * Maximum charge current limit – a maximum allowed charging current of all battery, A;
193 193  * Errors to disconnect all battery modules – errors that cause all battery modules to be disconnected from the common bus;
194 194  * Errors to open the charging contactor – errors that cause the main charging contactor "Charging" to open;
... ... @@ -228,8 +228,9 @@
228 228  
229 229  The battery discharge management is configured in the "Control - Discharge" section:
230 230  
231 -[[image:1740750247231-926.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="218" width="800"]]
232 232  
235 +[[image:1749657087238-544.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="250" width="800"]]
236 +
233 233  In this section:
234 234  
235 235  * Enable – a flag to enable battery discharge controller;
... ... @@ -241,12 +241,15 @@
241 241  * Allowable battery current to rejoin modules – a battery current at which joining of battery modules is permitted, A;
242 242  * Allowable voltage difference to rejoin modules – a difference between the voltage of the disconnected module and the battery voltage at which its joining is permitted, V;
243 243  * Checking voltages time – a time of checking voltages of battery modules before starting joining modules, millisecond;
244 -* Balancing modules time – a time of balancing battery modules after joining modules and before closing main discharging contactor, millisecond;
248 +* Module balancing time – a time of balancing battery modules after joining modules and before closing main discharging contactor, millisecond;
249 +* Interrupt balancing when modules are joined – a flag to break balancing time after all modules are joined;
245 245  * Control the precharging contactor – a flag to control the main precharging contactor;
246 246  * Canceling discharging time – a delay before opening the main discharging contactor, millisecond;
247 247  * Disconnect modules that are not ready to discharge – a flag for disconnecting modules that have the “Ready to discharge” signal cleared.
248 248  * Disconnect all modules if one is not ready to discharge – a flag for disconnecting all modules if one of the modules have the “Ready to discharge” signal cleared;
249 249  * Join modules on the “Discharge request” signal – a flag to enable automatic modules joining if “Discharge request” signal appears;
255 +* Regulator: Keep battery module currents below limits – a flag to enable regulation of module currents to be below module current limit;
256 +* Regulator: Gain – a gain of current regulator;
250 250  * Maximum discharge current limit – a maximum allowed discharging current of all the battery, A;
251 251  * Errors to disconnect all battery modules – errors that cause all battery modules to be disconnected from the common bus;
252 252  * Errors to open the discharging contactor – errors that cause the main discharging contactor "Discharging" to open,
... ... @@ -294,7 +294,7 @@
294 294  
295 295  The charge/discharge contactor control is configured in the “Control → Charge/Discharge” section:
296 296  
297 -[[image:1740750424118-190.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="250" width="800"]]
304 +[[image:1749657114587-360.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="284" width="800"]]
298 298  
299 299  In this section:
300 300  
... ... @@ -310,7 +310,8 @@
310 310  * Allowable battery current to rejoin modules – a battery current at which joining of battery modules is permitted, A;
311 311  * Allowable voltage difference to rejoin modules – a difference between the voltage of the disconnected module and the battery voltage at which its joining is permitted, V;
312 312  * Checking voltages time – a time of checking voltages of battery modules before starting joining modules, millisecond;
313 -* Balancing modules time – a time of balancing battery modules after joining modules and before closing main discharging contactor, millisecond;
320 +* Module balancing time – a time of balancing battery modules after joining modules and before closing main discharging contactor, millisecond;
321 +* Interrupt balancing when modules are joined – a flag to break balancing time after all modules are joined;
314 314  * Control the precharging contactor – a flag to control the main precharging contactor;
315 315  * Canceling discharging time – a delay before opening the main discharging contactor, millisecond;
316 316  * Disconnect modules that are not ready to charge – a flag for disconnecting modules that have the “Ready to charge” signal cleared;
... ... @@ -317,6 +317,8 @@
317 317  * Disconnect modules that are not ready to discharge – a flag for disconnecting modules that have the “Ready to discharge” signal cleared;
318 318  * Join modules on the “Charge request” signal – a flag to enable automatic modules joining if “Charge request” signal appears;
319 319  * Join modules on the “Discharge request” signal – a flag to enable automatic modules joining if “Discharge request” signal appears;
328 +* Regulator: Keep battery module currents below limits – a flag to enable regulation of module currents to be below module current limit;
329 +* Regulator: Gain – a gain of current regulator;
320 320  * Maximum charge current limit – a maximum allowed charging current of all the battery, A;
321 321  * Maximum discharge current limit – a maximum allowed discharging current of all the battery, A;
322 322  * Errors to disconnect all battery modules – errors that cause all battery modules to be disconnected from the common bus;
1749657114587-360.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +58.3 KB
Content