... ... @@ -62,12 +62,12 @@
62 62  In “Always on” mode main contactor closes if all the following is true:
63 63  
64 64  * Other contactors are open;
65 -* There are no errors from the "Errors ..." bitfiled.
65 +* There are no errors from the "Errors 1, 2 ..." bitfileds.
66 66  
67 67  In “Always on” mode main contactor opens if all the following is true:
68 68  
69 69  * Other contactors are open;
70 -* There is an error from the the "Errors ..." bitfiled.
70 +* There is an error from the the "Errors 1, 2 ..." bitfileds.
71 71  
72 72  In “Automatic” mode, the main contactor closes by internal algorithms at the same time with other contactors.
73 73