... ... @@ -62,12 +62,12 @@
62 62  In “Always on” mode main contactor closes if all the following is true:
63 63  
64 64  * Other contactors are open;
65 -* There are no errors from the "Errors ..." bitfiled.
65 +* There are no errors from the "Errors 1, 2 ..." bitfileds.
66 66  
67 67  In “Always on” mode main contactor opens if all the following is true:
68 68  
69 69  * Other contactors are open;
70 -* There is an error from the the "Errors ..." bitfiled.
70 +* There is an error from the the "Errors 1, 2 ..." bitfileds.
71 71  
72 72  In “Automatic” mode, the main contactor closes by internal algorithms at the same time with other contactors.
73 73  
... ... @@ -413,7 +413,7 @@
413 413  * Discharge: Tolerant cell temperature difference, °C;
414 414  * Delay before starting the coolant pump, millisecond;
415 415  * Delay before stopping the coolant pump, millisecond;
416 -* Errors to turn off the coolant pump – errors that cause the coolant pump to shut down.
416 +* Errors 1 (2) to turn off the coolant pump – errors that cause the coolant pump to shut down.
417 417  
418 418  Conditions for signal generation:
419 419