Changes for page 3.3 Control
Last modified by Admin on 2025/06/11 15:52
Summary
-
Page properties (1 modified, 0 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -62,12 +62,12 @@ 62 62 In “Always on” mode main contactor closes if all the following is true: 63 63 64 64 * Other contactors are open; 65 -* There are no errors from the "Errors ..." bitfiled. 65 +* There are no errors from the "Errors 1, 2 ..." bitfileds. 66 66 67 67 In “Always on” mode main contactor opens if all the following is true: 68 68 69 69 * Other contactors are open; 70 -* There is an error from the the "Errors ..." bitfiled. 70 +* There is an error from the the "Errors 1, 2 ..." bitfileds. 71 71 72 72 In “Automatic” mode, the main contactor closes by internal algorithms at the same time with other contactors. 73 73 ... ... @@ -413,7 +413,7 @@ 413 413 * Discharge: Tolerant cell temperature difference, °C; 414 414 * Delay before starting the coolant pump, millisecond; 415 415 * Delay before stopping the coolant pump, millisecond; 416 -* Errors to turn off the coolant pump – errors that cause the coolant pump to shut down. 416 +* Errors 1 (2) to turn off the coolant pump – errors that cause the coolant pump to shut down. 417 417 418 418 Conditions for signal generation: 419 419