... ... @@ -62,12 +62,12 @@
62 62  In “Always on” mode main contactor closes if all the following is true:
63 63  
64 64  * Other contactors are open;
65 -* There are no errors from the "Errors ..." bitfiled.
65 +* There are no errors from the "Errors 1, 2 ..." bitfileds.
66 66  
67 67  In “Always on” mode main contactor opens if all the following is true:
68 68  
69 69  * Other contactors are open;
70 -* There is an error from the the "Errors ..." bitfiled.
70 +* There is an error from the the "Errors 1, 2 ..." bitfileds.
71 71  
72 72  In “Automatic” mode, the main contactor closes by internal algorithms at the same time with other contactors.
73 73  
... ... @@ -398,29 +398,5 @@
398 398  
399 399  * the maximum temperature among all cells of the battery is less than the “Charge (Discharge): Tolerant cell temperature” value during the “Delay before stopping the cooler” time.
400 400  
401 -=== Coolant pump ===
402 402  
403 -To change the parameters of the coolant pump control algorithm, select the "Control → Coolant pump" section:
404 -
405 -[[image:1740750960467-987.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="154" width="800"]]
406 -
407 -In this section:
408 -
409 -* Enable – a flag to enable the coolant pump control;
410 -* Charge: Maximum cell temperature difference, °C;
411 -* Charge: Tolerant cell temperature difference, °C;
412 -* Discharge: Maximum cell temperature difference, °C;
413 -* Discharge: Tolerant cell temperature difference, °C;
414 -* Delay before starting the coolant pump, millisecond;
415 -* Delay before stopping the coolant pump, millisecond;
416 -* Errors to turn off the coolant pump – errors that cause the coolant pump to shut down.
417 -
418 -Conditions for signal generation:
419 -
420 -* the maximum temperature difference among all cells of the battery is greater than the “Charge (Discharge): Maximum cell temperature difference” value during the “Delay before starting the coolant pump” time.
421 -
422 -Conditions for clearing the signal:
423 -
424 -* the maximum temperature difference among all cells of the battery is less than the “Charge (Discharge): Tolerant cell temperature difference” value during the “Delay before stopping the coolant pump” time.
425 -
426 426