Changes for page 3.3 Control

Last modified by Admin on 2025/06/11 15:52

From version 19.1
edited by Admin
on 2025/02/28 13:56
Change comment: There is no comment for this version
To version 19.2
edited by Admin
on 2025/02/28 14:03
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -62,12 +62,12 @@
62 62  In “Always on” mode main contactor closes if all the following is true:
63 63  
64 64  * Other contactors are open;
65 -* There are no errors from the "Errors 1, 2 ..." bitfileds.
65 +* There are no errors from the "Errors ..." bitfiled.
66 66  
67 67  In “Always on” mode main contactor opens if all the following is true:
68 68  
69 69  * Other contactors are open;
70 -* There is an error from the the "Errors 1, 2 ..." bitfileds.
70 +* There is an error from the the "Errors ..." bitfiled.
71 71  
72 72  In “Automatic” mode, the main contactor closes by internal algorithms at the same time with other contactors.
73 73