... ... @@ -398,5 +398,29 @@
398 398  
399 399  * the maximum temperature among all cells of the battery is less than the “Charge (Discharge): Tolerant cell temperature” value during the “Delay before stopping the cooler” time.
400 400  
401 +=== Coolant pump ===
401 401  
403 +To change the parameters of the coolant pump control algorithm, select the "Control → Coolant pump" section:
404 +
405 +[[image:1740750960467-987.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="154" width="800"]]
406 +
407 +In this section:
408 +
409 +* Enable – a flag to enable the coolant pump control;
410 +* Charge: Maximum cell temperature difference, °C;
411 +* Charge: Tolerant cell temperature difference, °C;
412 +* Discharge: Maximum cell temperature difference, °C;
413 +* Discharge: Tolerant cell temperature difference, °C;
414 +* Delay before starting the coolant pump, millisecond;
415 +* Delay before stopping the coolant pump, millisecond;
416 +* Errors 1 (2) to turn off the coolant pump – errors that cause the coolant pump to shut down.
417 +
418 +Conditions for signal generation:
419 +
420 +* the maximum temperature difference among all cells of the battery is greater than the “Charge (Discharge): Maximum cell temperature difference” value during the “Delay before starting the coolant pump” time.
421 +
422 +Conditions for clearing the signal:
423 +
424 +* the maximum temperature difference among all cells of the battery is less than the “Charge (Discharge): Tolerant cell temperature difference” value during the “Delay before stopping the coolant pump” time.
425 +
402 402