Changes for page 3.3 Control
Last modified by Admin on 2025/06/11 15:52
Summary
-
Page properties (1 modified, 0 added, 0 removed)
-
Attachments (0 modified, 1 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -373,4 +373,54 @@ 373 373 374 374 * the minimum temperature among all cells of the battery is greater than the “Charge (Discharge): Tolerant cell temperature” value during the “Delay before stopping the heater” time. 375 375 376 +=== Cooler === 377 + 378 +To change the parameters of the cooler control algorithm, select the "Control → Cooler" section: 379 + 380 +[[image:1740750844486-213.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="158" width="800"]] 381 + 382 +In this section: 383 + 384 +* Enable – a flag to enable the cooler control; 385 +* Charge: Maximum module temperature, °C; 386 +* Charge: Tolerant module temperature, °C; 387 +* Discharge: Maximum module temperature, °C; 388 +* Discharge: Tolerant module temperature, °C; 389 +* Delay before starting the cooler, millisecond; 390 +* Delay before stopping the cooler, millisecond; 391 +* Errors 1 (2) to turn off the cooler – errors that cause the cooler to shut down. 392 + 393 +Conditions for signal generation: 394 + 395 +* the maximum temperature among all cells of the battery is greater than the “Charge (Discharge): Maximum cell temperature” value during the “Delay before starting the cooler” time. 396 + 397 +Conditions for clearing the signal: 398 + 399 +* the maximum temperature among all cells of the battery is less than the “Charge (Discharge): Tolerant cell temperature” value during the “Delay before stopping the cooler” time. 400 + 401 +=== Coolant pump === 402 + 403 +To change the parameters of the coolant pump control algorithm, select the "Control → Coolant pump" section: 404 + 405 +[[image:1740750960467-987.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="154" width="800"]] 406 + 407 +In this section: 408 + 409 +* Enable – a flag to enable the coolant pump control; 410 +* Charge: Maximum cell temperature difference, °C; 411 +* Charge: Tolerant cell temperature difference, °C; 412 +* Discharge: Maximum cell temperature difference, °C; 413 +* Discharge: Tolerant cell temperature difference, °C; 414 +* Delay before starting the coolant pump, millisecond; 415 +* Delay before stopping the coolant pump, millisecond; 416 +* Errors to turn off the coolant pump – errors that cause the coolant pump to shut down. 417 + 418 +Conditions for signal generation: 419 + 420 +* the maximum temperature difference among all cells of the battery is greater than the “Charge (Discharge): Maximum cell temperature difference” value during the “Delay before starting the coolant pump” time. 421 + 422 +Conditions for clearing the signal: 423 + 424 +* the maximum temperature difference among all cells of the battery is less than the “Charge (Discharge): Tolerant cell temperature difference” value during the “Delay before stopping the coolant pump” time. 425 + 376 376
- 1740750960467-987.png
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.admin - Size
-
... ... @@ -1,0 +1,1 @@ 1 +23.8 KB - Content