... ... @@ -373,4 +373,30 @@
373 373  
374 374  * the minimum temperature among all cells of the battery is greater than the “Charge (Discharge): Tolerant cell temperature” value during the “Delay before stopping the heater” time.
375 375  
376 +=== Cooler ===
377 +
378 +To change the parameters of the cooler control algorithm, select the "Control → Cooler" section:
379 +
380 +[[image:1740750844486-213.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="158" width="800"]]
381 +
382 +In this section:
383 +
384 +* Enable – a flag to enable the cooler control;
385 +* Charge: Maximum module temperature, °C;
386 +* Charge: Tolerant module temperature, °C;
387 +* Discharge: Maximum module temperature, °C;
388 +* Discharge: Tolerant module temperature, °C;
389 +* Delay before starting the cooler, millisecond;
390 +* Delay before stopping the cooler, millisecond;
391 +* Errors 1 (2) to turn off the cooler – errors that cause the cooler to shut down.
392 +
393 +Conditions for signal generation:
394 +
395 +* the maximum temperature among all cells of the battery is greater than the “Charge (Discharge): Maximum cell temperature” value during the “Delay before starting the cooler” time.
396 +
397 +Conditions for clearing the signal:
398 +
399 +* the maximum temperature among all cells of the battery is less than the “Charge (Discharge): Tolerant cell temperature” value during the “Delay before stopping the cooler” time.
400 +
401 +