Changes for page 3.3 Control

Last modified by Admin on 2025/06/11 15:52

From version 12.2
edited by Admin
on 2025/02/28 13:47
Change comment: There is no comment for this version
To version 14.1
edited by Admin
on 2025/02/28 13:50
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -322,20 +322,21 @@
322 322  * Join modules on the “Discharge request” signal – a flag to enable automatic modules joining if “Discharge request” signal appears;
323 323  * Maximum charge current limit – a maximum allowed charging current of all the battery, A;
324 324  * Maximum discharge current limit – a maximum allowed discharging current of all the battery, A;
325 -* Errors 1 (2) to disconnect all battery modules – errors that cause all battery modules to be disconnected from the common bus;
326 -* Errors 1 (2) to open the charging/discharging contactor – errors that cause the main charging/discharging contactor "Discharging" to open,
325 +* Errors to disconnect all battery modules – errors that cause all battery modules to be disconnected from the common bus;
326 +* Errors to open the charging/discharging contactor – errors that cause the main charging/discharging contactor "Discharging" to open,
327 327  * Switch of the charging/discharging contactor on errors without a delay – a flag that allows the main charging/discharging contactor to be opened without delay if errors are detected.
328 328  
329 329  === Module balancing ===
330 330  
331 331  The BMS Main X device supports active balancing of battery modules both in the process of charging and in the process of discharging the battery.
332 -\\When the battery is charging, balancing is performed by disconnecting the most charged battery modules from the common bus. Before disconnecting the modules, the BMS Main X sends a request to the upper-level system (charger) to reduce the charge current to zero, and after the current becomes zero, disconnects the most charged battery modules.
333 333  
333 +When the battery is charging, balancing is performed by disconnecting the most charged battery modules from the common bus. Before disconnecting the modules, the BMS Main X sends a request to the upper-level system (charger) to reduce the charge current to zero, and after the current becomes zero, disconnects the most charged battery modules.
334 +
334 334  When the battery is discharging, balancing is performed by disconnecting the most discharged battery modules from the common bus. Battery modules are disconnected only if the battery discharge current has dropped to the threshold value set in the device settings.
335 335  
336 336  Module balancing is configured in the “Control – Module balancing” section:
337 337  
338 -[[image:1734356572313-823.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="74" width="600"]]
339 +[[image:1740750509436-756.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="148" width="800"]]
339 339  
340 340  In this section:
341 341  
... ... @@ -342,6 +342,7 @@
342 342  * Balance on charging – a flag to enable module balancing when the battery is charging;
343 343  * Delta voltage – a voltage difference at which the most charged modules are switched off (those modules whose voltage exceeds the minimum voltage among the modules by the “Delta voltage” value are switched off), V;
344 344  * Delta current – a current difference at which the most charged modules are switched off (those modules are switched off, the charge current of which is less than the maximum charge current among the modules by the “Delta current” value), A;
345 -* Waiting time – a time the battery modules are in the disconnected state (after this time, the modules previously disconnected during the balancing process are reconnected to the common bus), s;
346 -* Balance on discharging – a flag to enable module balancing when the battery is discharging;
346 +* Detection time – a time for module to be estimated as unbalanced, millisecond;
347 +* Waiting time – a time the battery modules are in the disconnected state (after this time, the modules previously disconnected during the balancing process are reconnected to the common bus), second;
348 +* Balance on discharging – a flag to enable module balancing when the battery is discharging (if flag is enabled operation logic and settings are equal to balancing on charging);
347 347  * Required discharging current – a value of the discharge current at which the device switches off the most discharged battery modules, A.
1740750509436-756.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +19.8 KB
Content