Changes for page 3.3 Control

Last modified by Admin on 2025/06/11 15:52

From version 10.1
edited by Admin
on 2025/02/28 13:42
Change comment: Загрузить новое вложение 1740750130950-113.png
To version 10.2
edited by Admin
on 2025/02/28 13:42
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -147,10 +147,10 @@
147 147  1. Charging is allowed provided that all battery modules are balanced (Balanced).
148 148  1. Charging is allowed for most balanced battery modules (Partially balanced). Unbalanced modules are disconnected from the common bus and do not participate in the charging.
149 149  
150 -The device controls two processes: joining battery modules and closing the main charging contactor.
150 +The device controls two processes: **joining battery modules **and **closing the main charging contactor.**
151 151  
152 152  
153 -The operation of the joining battery modules is described by the following steps:
153 +The operation of the **joining battery modules** is described by the following steps:
154 154  
155 155  1. Battery modules are disabled. When the “Join to charge” request is received and the voltage and current unbalance errors (Voltage unbalance (CH), Current unbalance (CH), Charging current unbalance) are cleared, go to step 2.
156 156  1. Checking the voltage unbalance of battery modules (the duration of the check is set in the settings). If there is no imbalance or errors are ignored (“Always on” and “Partially balanced”), go to step 3, otherwise open all charging contactors, and go to step 1.
... ... @@ -159,7 +159,7 @@
159 159  1. Checking intermodular balancing currents (the duration of the check is set in the settings). If there is no current unbalance (“Current unbalance (CH)”) or errors are ignored (“Always on”), go to step 6, otherwise open all charging contactors, and go to step 1.
160 160  1. The battery modules are joined. If the “Join to charge” request is cleared or the "Charging current unbalance" and "Critical error" errors occur, go to step 1.
161 161  
162 -The operation of the main charging contactor is described in the following steps:
162 +The operation of **closing the main charging contactor** is described in the following steps:
163 163  
164 164  1. The main charging contactor is open. When the “Charge request” is received, the voltage and current unbalance errors (“Voltage unbalance (CH)”, “Current unbalance (CH)”, “Charging current unbalance”) are cleared, and the battery modules are joined, go to step 2.
165 165  1. Closing the main precharging contactor (optional). Go to step 3.
... ... @@ -172,7 +172,7 @@
172 172  
173 173  The battery charge management is configured in the "Control - Charge" section:
174 174  
175 -[[image:1734356553573-447.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="146" width="600"]]
175 +[[image:1740750130950-113.png]]
176 176  
177 177  In this section: