Wiki source code of 2. Installation and connection

Version 6.1 by Admin on 2025/02/06 11:39

Show last authors
1 (% data-numbered-headings-start="2" style="--numbered-headings-start: 1;font-size: 0px;color: rgba(0, 0, 0, 0.0);margin-bottom: 0px; margin-top: 0px;" %)
2 = Installation and connection =
3
4 == Installation ==
5
6 The mounting area of the BMS Main X must be protected from mechanical particles (dust, dirt, large objects) and water.
7
8 The installation site must provide convenient access for subsequent connection to the device’s headers for connecting other system elements: contactors, temperature sensors, etc.
9
10 Overall and mounting dimensions of the BMS Main X are shown below.
11
12 [[image:1734355103230-973.png||data-xwiki-image-style-alignment="center" height="460" width="450"]]
13 [[image:1734355103237-284.png||data-xwiki-image-style-alignment="center" height="207" width="450"]]
14
15 |(((
16 **Parameter**
17 )))|**Value **
18 |(((
19 Overall dimensions (length × width × height), mm
20 )))|105 × 115 × 15
21 |Mounting dimensions (length × width), mm|99 × 109
22 |Mounting holes|M3
23 |Headers X1, X3-X8 type|Molex series Micro-Fit
24
25 == Connection ==
26
27 === Headers ===
28
29 There are names and locations of the BMS Main X headers in figure below.
30
31 [[image:1734355208744-833.png||data-xwiki-image-style-alignment="center" height="491" width="450"]]
32
33 === Х1 – header for power supply ===
34
35 [[image:1734355208747-667.png||data-xwiki-image-style-alignment="center"]]
36
37 |**Pin**|**Name**|**Description**
38 |**1**|**V+**|Supply voltage 18÷36V
39 |**2**|**GND**|Ground
40
41 === X2 – header for USB ===
42
43 === X3 – header for CAN (INT) interface ===
44
45 [[image:1734355229969-197.png||data-xwiki-image-style-alignment="center"]]
46
47 |**Pin**|**Name**|**Description**
48 |**1**|**СAN_INT_H**|CAN-H line of the internal CAN bus (communication with battery modules)
49 |**2**|**CAN_INT_L**|CAN-L line of the internal CAN bus (communication with battery modules)
50 |**3**|**CAN_INT_5V**|Isolated 5V power supply for internal devices, max 200 mA
51 |**4**|**CAN_INT_GND**|Isolated ground
52
53 === Х4 – header for RS-485 interface ===
54
55 [[image:1734355229969-197.png||data-xwiki-image-style-alignment="center"]]
56
57 |**Pin**|**Name**|**Description**
58 |**1**|**RS485_A**|A line of the external RS-485 bus
59 |**2**|**RS485_B**|B line of the external RS-485 bus
60 |**3**|**-**|-
61 |**4**|**RS485_GND**|Isolated ground
62
63 === J1 – jumper for switching RS-485 terminal resistor ===
64
65 To connect the terminal resistor between the** RS485_A** and **RS485_B** lines, install the jumper J1 according to the following figure:
66
67 [[image:1734355346488-798.png||data-xwiki-image-style-alignment="center"]]
68
69 === Х5 – header for CAN (EXT) interface ===
70
71 [[image:1734355229969-197.png||data-xwiki-image-style-alignment="center"]]
72
73 |**Pin**|**Name**|**Description**
74 |**1**|**СAN_EXT_H**|CAN-H line of the external CAN bus (communication with a top-level system)
75 |**2**|**CAN_EXT_L**|CAN-L line of the external CAN bus (communication with a top-level system)
76 |**3**|**CAN_EXT_5V**|Isolated 5V power supply for external devices, max 200 mA
77 |**4**|**CAN_EXT_GND**|Isolated ground
78
79 === J2 – jumper for switching CAN (EXT) terminal resistor ===
80
81 To connect the terminal resistor between the** CAN_EXT_H** and **CAN_EXT_L** lines, install the jumper J2 according to the following figure:
82
83 [[image:1734355346488-798.png||data-xwiki-image-style-alignment="center"]]
84
85 === Х6 – header for sold-state relays ===
86
87 [[image:1734355584041-898.jpeg||data-xwiki-image-style-alignment="center" height="65" width="90"]]
88
89 |**Pin**|**Name**|**Description**
90 |**1**|**NO1**|Normally open contact of the relay 1
91 |**2**|**NO2**|Normally open contact of the relay 2
92 |**3**|**NO3**|Normally open contact of the relay 3
93 |**4**|**COM1**|Common contact of the relay 1 (55V, 2A)
94 |**5**|**COM2**|Common contact of the relay 2 (55V, 2A)
95 |**6**|**COM3**|Common contact of the relay 3 (55V, 2A)
96
97 === X7 – header for discrete inputs/outputs ===
98
99 [[image:1734355584043-416.jpeg||data-xwiki-image-style-alignment="center" height="79" width="260"]]
100
101 |**Pin**|**Name**|**Description**
102 |**1**|**GND**|Discrete input 1 “dry contact” (ground)
103 |**2**|**GND**|Discrete input 2 “dry contact” (ground)
104 |**3**|**GND**|Discrete input 3 “dry contact” (ground)
105 |**4**|**GND**|Discrete input 4 “dry contact” (ground)
106 |**5**|**-**|-
107 |**6**|**GND**|Discrete output 1 (ground)
108 |**7**|**GND**|Discrete output 2 (ground)
109 |**8**|**GND**|Discrete output 3 (ground)
110 |**9**|**GND**|Discrete output 4 (ground)
111 |**10**|**D_IN1**|Discrete input 1 “dry contact” (+5V)
112 |**11**|**D_IN2**|Discrete input 2 “dry contact” (+5V)
113 |**12**|**D_IN3**|Discrete input 3 “dry contact” (+5V)
114 |**13**|**D_IN4**|Discrete input 4 “dry contact” (+5V)
115 |**14**|**-**|-
116 |**15**|**D_OUT1**|Discrete output 1 (+5V, 20mA)
117 |**16**|**D_OUT2**|Discrete output 2 (+5V, 20mA)
118 |**17**|**D_OUT3**|Discrete output 3 (+5V, 20mA)
119 |**18**|**D_OUT4**|Discrete output 4 (+5V, 20mA)
120
121 === Х8 – header for temperature sensors ===
122
123 [[image:1734355229969-197.png||data-xwiki-image-style-alignment="center"]]
124
125 |**Pin**|**Name**|**Description**
126 |**1**|**TEMPG1**|Ground of the thermistor 1
127 |**2**|**TEMPG2**|Ground of the thermistor 2
128 |**3**|**TEMP1**|Signal from the thermistor 1
129 |**4**|**TEMP2**|Signal from the thermistor 2
130
131