2 | 11. | ||
3 | 111. General parameters | ||
4 | |||
5 | General parameters of BMS Main 3X are configured in the «Control → General» section: | ||
6 | |||
7 | [[image:1734023979572-693.png]] | ||
8 | |||
9 | * Initialization delay – a delay before processing functions after finishing device initialization (initialization includes current sensors calibration and battery modules search), millisecond. | ||
10 | |||
11 | |||
12 | 1. | ||
13 | 11. | ||
14 | 111. Battery modules | ||
15 | |||
16 | The BMS Main 3X allows up to 32 battery modules with BMS Main 3 onboard to be connected in parallel. | ||
17 | |||
18 | Flags for enabling battery modules are configured in the "Control → Modules → Enable (modules 1 to 8)" and "Control → Modules → Enable (modules 9 to 32)" section: | ||
19 | |||
20 | [[image:1734023979582-179.png]] | ||
21 | |||
22 | |||
23 | The network addresses of the battery modules are configured in the "Control → Modules → Node IDs (modules 1 to 8)” and "Control → Modules → Node IDs (modules 9 to 32)”: | ||
24 | |||
25 | [[image:1734023979583-589.png]] | ||
26 | |||
27 | |||
28 | Each module in a battery must have a unique address. You can change the address in the battery module settings in the “Connectivity → CAN” section of the BMS Main 3 settings. | ||
29 | |||
30 | |||
31 | 1. | ||
32 | 11. | ||
33 | 111. Calculation of battery parameters | ||
34 | |||
35 | The BMS Main 3X device calculates battery parameters based on user settings. | ||
36 | |||
37 | Calculation of the battery state of charge (SOC) is configured in the "Control → Calculation → Final SOC" section: | ||
38 | |||
39 | [[image:1734023979584-480.png]] | ||
40 | |||
41 | The following battery SOC calculation methods are supported: | ||
42 | |||
43 | * Minimal SOC – SOC of the modular battery is assumed to be the minimum SOC among the battery modules; | ||
44 | * Average SOC – SOC of the modular battery is taken equal to the arithmetic average of the SOC of the battery modules; | ||
45 | * Min-Max SOC – SOC of the modular battery is calculated based on the minimal and maximum SOC of the battery modules (recommended). | ||
46 | |||
47 | Calculation of the battery state of health (SOH) is configured in the "Control → Calculation → Final SOH" section. The following battery SOH calculation methods are supported: | ||
48 | |||
49 | * Minimal SOH – SOH of the modular battery is assumed to be the minimum SOH among the battery modules; | ||