Changes for page 3.3 Control
Last modified by Admin on 2025/05/30 16:50
Summary
-
Page properties (1 modified, 0 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -110,7 +110,7 @@ 110 110 111 111 To change the precharge parameters, select the section “Control → Precharge”: 112 112 113 - [[image:1738080762857-975.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="108" width="600"]]In this section:113 +In this section: 114 114 115 115 116 116 * Precharge current threshold to close the discharging contactor – a current value to ensure that precharge process has finished and it is allowed to close the discharging contactor, A; ... ... @@ -125,18 +125,13 @@ 125 125 * Delay before setting the "Precharge error" when checking power, millisecond; 126 126 * Delay before clearing the "Precharge error", second; 127 127 * Lock the "Precharge error" – a flag to block the error until the device is restarted. 128 - 128 +* ((( 129 129 “Precharge error” generation conditions: 130 - 130 +))) 131 131 * the precharge current does not decrease after "Number of precharging attempts"; 132 132 * voltages before and after contactors are not equal after "Number of precharging attempts"; 133 133 * power dissipated on the precharge resistor is above the maximum value during the “Delay before setting the 'Precharge error' when checking power” time. 134 134 135 -(% class="box warningmessage" %) 136 -((( 137 -Behavior of contactors at “Precharge error” is configured in corresponding contactor settings! 138 -))) 139 - 140 140 === Charge === 141 141 142 142 The BMS Main 3X device manages the parallel connection of the battery modules and the connection of the battery to the charging circuit.