... ... @@ -110,7 +110,7 @@
110 110  
111 111  To change the precharge parameters, select the section “Control → Precharge”:
112 112  
113 -In this section:
113 +[[image:1738080762857-975.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="108" width="600"]]In this section:
114 114  
115 115  
116 116  * Precharge current threshold to close the discharging contactor – a current value to ensure that precharge process has finished and it is allowed to close the discharging contactor, A;
... ... @@ -125,13 +125,18 @@
125 125  * Delay before setting the "Precharge error" when checking power, millisecond;
126 126  * Delay before clearing the "Precharge error", second;
127 127  * Lock the "Precharge error" – a flag to block the error until the device is restarted.
128 -* (((
128 +
129 129  “Precharge error” generation conditions:
130 -)))
130 +
131 131  * the precharge current does not decrease after "Number of precharging attempts";
132 132  * voltages before and after contactors are not equal after "Number of precharging attempts";
133 133  * power dissipated on the precharge resistor is above the maximum value during the “Delay before setting the 'Precharge error' when checking power” time.
134 134  
135 +(% class="box warningmessage" %)
136 +(((
137 +Behavior of contactors at “Precharge error” is configured in corresponding contactor settings!
138 +)))
139 +
135 135  === Charge ===
136 136  
137 137  The BMS Main 3X device manages the parallel connection of the battery modules and the connection of the battery to the charging circuit.