Changes for page 3.3 Control
Last modified by Admin on 2025/05/30 16:50
Summary
-
Page properties (1 modified, 0 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -110,7 +110,7 @@ 110 110 111 111 To change the precharge parameters, select the section “Control → Precharge”: 112 112 113 -In this section: 113 +[[image:1738080762857-975.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="108" width="600"]]In this section: 114 114 115 115 116 116 * Precharge current threshold to close the discharging contactor – a current value to ensure that precharge process has finished and it is allowed to close the discharging contactor, A; ... ... @@ -125,13 +125,18 @@ 125 125 * Delay before setting the "Precharge error" when checking power, millisecond; 126 126 * Delay before clearing the "Precharge error", second; 127 127 * Lock the "Precharge error" – a flag to block the error until the device is restarted. 128 - * (((128 + 129 129 “Precharge error” generation conditions: 130 - )))130 + 131 131 * the precharge current does not decrease after "Number of precharging attempts"; 132 132 * voltages before and after contactors are not equal after "Number of precharging attempts"; 133 133 * power dissipated on the precharge resistor is above the maximum value during the “Delay before setting the 'Precharge error' when checking power” time. 134 134 135 +(% class="box warningmessage" %) 136 +((( 137 +Behavior of contactors at “Precharge error” is configured in corresponding contactor settings! 138 +))) 139 + 135 135 === Charge === 136 136 137 137 The BMS Main 3X device manages the parallel connection of the battery modules and the connection of the battery to the charging circuit.