... ... @@ -26,7 +26,7 @@
26 26  
27 27  Each module in a battery must have a unique address. You can change the address in the battery module settings in the “Connectivity → CAN” section of the BMS Main 3 settings.
28 28  
29 -You can set up maximum number of found modules to finish initialization in corresponding section.
29 +In corresponding section you can set up maximum number of found modules to finish initialization.
30 30  
31 31  === Calculation of battery parameters ===
32 32  
... ... @@ -40,8 +40,8 @@
40 40  
41 41  * Minimal SOC – SOC of the modular battery is assumed to be the minimum SOC among the battery modules;
42 42  * Average SOC – SOC of the modular battery is taken equal to the arithmetic average of the SOC of the battery modules;
43 -* Min-Max SOC – SOC of the modular battery is calculated based on the minimal and maximum SOC of the battery modules (optimized for maximum health);
44 -* Max-Min SOC – SOC of the modular battery is calculated based on the minimal and maximum SOC of the battery modules (optimized for maximum capacity, recommended);
43 +* Min-Max SOC – the battery SOC is calculated based on the minimum and maximum SOC of the modules. Final SOC will be a) 100% if any module has 100% SOC, b) 0% if any module has 0% SOC;
44 +* Max-Min SOC – the battery SOC is calculated based on the minimum and maximum SOC of the modules. Final SOC will be a) 100% if all modules have 100% SOC, b) 0% if all modules have 0% SOC;
45 45  
46 46  Calculation of the battery state of health (SOH) is configured in the "Control → Calculation → Final SOH" section. The following battery SOH calculation methods are supported:
47 47  
... ... @@ -112,6 +112,7 @@
112 112  
113 113  In this section:
114 114  
115 +[[image:1739290619354-792.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="117" width="600"]]
115 115  
116 116  * Precharge current threshold to close the discharging contactor – a current value to ensure that precharge process has finished and it is allowed to close the discharging contactor, A;
117 117  * Check voltages before and after contactors to finish precharging – a flag to check the voltages before and after contactors to ensure that precharge process has finished and it is allowed to close the discharging contactor;
... ... @@ -124,14 +124,19 @@
124 124  * Maximum allowable power dissipated in the resistor, W;
125 125  * Delay before setting the "Precharge error" when checking power, millisecond;
126 126  * Delay before clearing the "Precharge error", second;
127 -* Lock the "Precharge error" – a flag to block the error until the device is restarted.
128 -* (((
129 -“Precharge error” generation conditions:
130 -)))
131 -* the precharge current does not decrease after "Number of precharging attempts";
132 -* voltages before and after contactors are not equal after "Number of precharging attempts";
128 +* Lock – a flag to block the error until the device is restarted.
129 +
130 +“Precharge error” generation conditions if any of the following is true:
131 +
132 +* the precharge current does not decrease during the "Precharge time" after "Number of precharging attempts";
133 +* voltages before and after contactors are not equal during the "Precharge time" after "Number of precharging attempts";
133 133  * power dissipated on the precharge resistor is above the maximum value during the “Delay before setting the 'Precharge error' when checking power” time.
134 134  
136 +(% class="box warningmessage" %)
137 +(((
138 +Behavior of contactors at “Precharge error” is configured in corresponding contactor settings!
139 +)))
140 +
135 135  === Charge ===
136 136  
137 137  The BMS Main 3X device manages the parallel connection of the battery modules and the connection of the battery to the charging circuit.
... ... @@ -169,7 +169,7 @@
169 169  
170 170  The battery charge management is configured in the "Control → Charge" section:
171 171  
172 -[[image:1734089684907-463.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="180" width="600"]]
178 +[[image:1738081025199-282.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="162" width="600"]]
173 173  
174 174  In this section:
175 175  
... ... @@ -181,17 +181,14 @@
181 181  * Minimum number of modules allowed to join – a minimum number of battery modules that can be connected in parallel;
182 182  * Allowable battery current to rejoin modules – a battery current at which joining of battery modules is permitted, A;
183 183  * Allowable voltage difference to rejoin modules – a difference between the voltage of the disconnected module and the battery voltage at which its joining is permitted, V;
184 -* Checking voltages time – a time of checking voltages of battery modules, millisecond;
185 -* Pre-balancing modules time – a time of pre-charging battery modules, millisecond;
186 -* Balancing modules time – a time of balancing battery modules, millisecond;
190 +* Checking voltages time – a time of checking voltages of battery modules before starting joining modules, millisecond;
191 +* Balancing modules time – a time of balancing battery modules after joining modules and before closing main charging contactor, millisecond;
187 187  * Control the precharging contactor – a flag to control the main precharging contactor;
188 -* Precharging time – a time of precharging, millisecond;
189 189  * Canceling charging time – a delay before opening the main charging contactor, ms;
190 -* Limit module current – a flag that allows to limit the charging current of a modular battery so that the current of each battery module does not exceed its maximum allowable charge current;
191 -* Slew rate – a rate of change of the charge current limit when the “Limit module current” flag is set, A/s;
192 192  * Disconnect modules that are not ready to charge – a flag for disconnecting modules that have the “Ready to charge” signal cleared.
193 193  * Disconnect all modules if one is not ready to charge – a flag for disconnecting all modules if any of the modules have the “Ready to charge” signal cleared;
194 194  * Join modules on the “Charge request” signal – a flag to enable automatic modules joining if “Charge request” signal appears;
197 +* Maximum CONTINUOUS charge current limit – a maximum continuous allowed charging current of all battery, A;
195 195  * Maximum charge current limit – a maximum allowed charging current of all battery, A;
196 196  * Errors 1 (2) to disconnect all battery modules – errors that cause all battery modules to be disconnected from the common bus;
197 197  * Errors 1 (2) to open the charging contactor – errors that cause the main charging contactor "Charging" to open;
... ... @@ -234,7 +234,7 @@
234 234  
235 235  The battery discharge management is configured in the "Control → Discharge" section:
236 236  
237 -[[image:1734089702987-534.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="179" width="600"]]
240 +[[image:1738081173083-894.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="162" width="600"]]
238 238  
239 239  In this section:
240 240  
... ... @@ -246,17 +246,14 @@
246 246  * Minimum number of modules allowed to join – a minimum number of battery modules that can be connected in parallel;
247 247  * Allowable battery current to rejoin modules – a battery current at which joining of battery modules is permitted, A;
248 248  * Allowable voltage difference to rejoin modules – a difference between the voltage of the disconnected module and the battery voltage at which its joining is permitted, V;
249 -* Checking voltages time – a time of checking voltages of battery modules, millisecond;
250 -* Pre-balancing modules time – a time of precharging battery modules, millisecond;
251 -* Balancing modules time – a time of balancing battery modules, millisecond;
252 +* Checking voltages time – a time of checking voltages of battery modules before starting joining modules, millisecond;
253 +* Balancing modules time – a time of balancing battery modules after joining modules and before closing main discharging contactor, millisecond;
252 252  * Control the precharging contactor – a flag to control the main precharging contactor;
253 -* Precharging time – a time of precharging, millisecond;
254 254  * Canceling discharging time – a delay before opening the main discharging contactor, millisecond;
255 -* Limit module current – a flag that allows to limit the discharging current of a modular battery so that the current of each battery module does not exceed its maximum allowable discharge current;
256 -* Slew rate – a rate of change of the discharge current limit when the “Limit module current” flag is set, A/s;
257 257  * Disconnect modules that are not ready to discharge – a flag for disconnecting modules that have the “Ready to discharge” signal cleared.
258 258  * Disconnect all modules if one is not ready to discharge – a flag for disconnecting all modules if one of the modules have the “Ready to discharge” signal cleared;
259 259  * Join modules on the “Discharge request” signal – a flag to enable automatic modules joining if “Discharge request” signal appears;
259 +* Maximum CONTINUOUS discharge current limit – a maximum allowed continuous discharging current of all the battery, A;
260 260  * Maximum discharge current limit – a maximum allowed discharging current of all the battery, A;
261 261  * Errors 1 (2) to disconnect all battery modules – errors that cause all battery modules to be disconnected from the common bus;
262 262  * Errors 1 (2) to open the discharging contactor – errors that cause the main discharging contactor "Discharging" to open,
... ... @@ -266,15 +266,66 @@
266 266  
267 267  The BMS Main 3X can control the charging/discharging contactor that is used to both charge and discharge the battery.
268 268  
269 -The charge/discharge contactor (“Charging/Discharging” signal) receives a “Charging” signal (generated by the charge controller) if a “Charge request” signal is received from the upper-level system. In all other cases, the "Discharging" signal is output to the contactor (generated by the discharge controller).
269 +Charge/Discharge contactor has two algorithms of operation:
270 270  
271 +* Dependent - Charge/Discharge contactor depends on Charge and Discharge algorithms and their signals and behaves as Charging contactor if "Charging" signal is set, otherwise – as Discharging contactor;
272 +* Independent - Charge/Discharge contactor is based on its own controller.
273 +
274 +The charging/discharging controller supports the following modes:
275 +
276 +1. Charging/Discharging is always allowed (Always on) – the device ignores voltage and current unbalance of the battery modules and commands to close the discharging contactors of the battery modules and the main discharging contactor.
277 +1. Charging/Discharging is allowed if all battery modules are balanced (Balanced).
278 +1. Charging/Discharging is allowed for most balanced battery modules (Partially balanced). Unbalanced modules are disconnected from the common bus and do not participate in the discharging.
279 +
280 +The device controls two processes: **joining battery modules** and **closing the main charging/discharging contactor**.
281 +
282 +The operation of the **joining battery modules** depends on the signal received:
283 +
284 +* If "Join to charge" is received, joining procedure is done as described in [[Charge>>doc:||anchor="HCharge"]] section;
285 +* If "Join to discharge" is received, joining procedure is done as described in [[Discharge>>doc:||anchor="HDischarge"]] section;
286 +* If both signals received, "Join to charge" has a priority.
287 +
288 +The operation of **closing main charging/discharging contactor **depends on the signal received:
289 +
290 +* If "Charge request" is received, procedure is done as described in [[Charge>>doc:||anchor="HCharge"]] section;
291 +* If "Discharge request" is received, procedure is done as described in [[Discharge>>doc:||anchor="HDischarge"]] section;
292 +* If both signals received, "Charge request" has a priority.
293 +
294 +
295 +In addition, the charge/discharge controller calculates and transmits to the upper-level system the maximum allowable current value with which the modular battery can be charged ("Charge current limit") and discharged ("Discharge current limit"), as well as the maximum regeneration current value with which the modular battery can be charged during operation under load ("Regeneration current limit"). The calculation of the charge, discharge and regeneration currents of the entire battery is performed based on the number of battery modules operating for charge or discharge and the maximum charge and discharge current values ​​transmitted by them:
296 +
297 +* "Charge current limit" and "Regeneration current limit" are calculated only if there is "Charge request";
298 +* "Discharge current limit" is calculated only if there is "Discharge request".
299 +
271 271  The charge/discharge contactor control is configured in the “Control → Charge/Discharge” section:
272 272  
273 -[[image:1734089702994-738.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="92" width="600"]]
302 +[[image:1739292809635-913.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="238" width="800"]]
274 274  
275 275  In this section:
276 276  
277 -* Enable – a flag to enable the charge/discharge controller.
306 +* Enable – a flag to enable battery charge/discharge controller;
307 +* Algorithm:
308 +** Always on – discharging is always allowed;
309 +** Balanced – discharging is allowed provided that all battery modules are balanced;
310 +** Partially balanced – discharging is allowed for most balanced battery modules;
311 +* Minimum number of modules allowed to join – a minimum number of battery modules that can be connected in parallel;
312 +* Allowable battery current to rejoin modules – a battery current at which joining of battery modules is permitted, A;
313 +* Allowable voltage difference to rejoin modules – a difference between the voltage of the disconnected module and the battery voltage at which its joining is permitted, V;
314 +* Checking voltages time – a time of checking voltages of battery modules before starting joining modules, millisecond;
315 +* Balancing modules time – a time of balancing battery modules after joining modules and before closing main discharging contactor, millisecond;
316 +* Control the precharging contactor – a flag to control the main precharging contactor;
317 +* Canceling discharging time – a delay before opening the main discharging contactor, millisecond;
318 +* Disconnect modules that are not ready to charge – a flag for disconnecting modules that have the “Ready to charge” signal cleared;
319 +* Disconnect modules that are not ready to discharge – a flag for disconnecting modules that have the “Ready to discharge” signal cleared;
320 +* Join modules on the “Charge request” signal – a flag to enable automatic modules joining if “Charge request” signal appears;
321 +* Join modules on the “Discharge request” signal – a flag to enable automatic modules joining if “Discharge request” signal appears;
322 +* Maximum CONTINUOUS charge current limit – a maximum allowed continuous charging current of all the battery, A;
323 +* Maximum charge current limit – a maximum allowed charging current of all the battery, A;
324 +* Maximum CONTINUOUS discharge current limit – a maximum allowed continuous discharging current of all the battery, A;
325 +* Maximum discharge current limit – a maximum allowed discharging current of all the battery, A;
326 +* Errors 1 (2) to disconnect all battery modules – errors that cause all battery modules to be disconnected from the common bus;
327 +* Errors 1 (2) to open the charging/discharging contactor – errors that cause the main charging/discharging contactor "Discharging" to open,
328 +* Switch of the charging/discharging contactor on errors without a delay – a flag that allows the main charging/discharging contactor to be opened without delay if errors are detected.
278 278  
279 279  === Module balancing ===
280 280  
1738081025199-282.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +48.3 KB
Content
1738081173083-894.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +49.1 KB
Content
1739290619354-792.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +41.2 KB
Content
1739292809635-913.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +60.7 KB
Content
1739970002016-142.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +41.2 KB
Content