Changes for page 3.3 Control

Last modified by Admin on 2025/05/30 16:50

From version 6.2
edited by Admin
on 2024/12/13 12:40
Change comment: Update document after refactoring.
To version 4.1
edited by Admin
on 2024/12/13 11:41
Change comment: There is no comment for this version

Summary

Details

Page properties
Parent
... ... @@ -1,1 +1,1 @@
1 -Battery management systems.BMS Main 3X.3\. Configuration.WebHome
1 +drafts.BMS Main 3X.3\. Configuration.WebHome
Content
... ... @@ -26,6 +26,7 @@
26 26  
27 27  Each module in a battery must have a unique address. You can change the address in the battery module settings in the “Connectivity → CAN” section of the BMS Main 3 settings.
28 28  
29 +
29 29  === Calculation of battery parameters ===
30 30  
31 31  The BMS Main 3X device calculates battery parameters based on user settings.
... ... @@ -139,7 +139,7 @@
139 139  1. Checking intermodular balancing currents (the duration of the check is set in the settings). If there is no current unbalance (“Current unbalance (CH)”) or errors are ignored (“Always on”), go to step 6, otherwise open all charging contactors, and go to step 1.
140 140  1. The battery modules are joined. If the “Join to charge” request is cleared or the "Charging current unbalance" error occurs, go to step 1.
141 141  
142 -The operation of** closing main charging contactor** is described in the following steps:
143 +The operation of** closing main charging contactor** is described in the following steps:
143 143  
144 144  1. The main charging contactor “Charging” is open. When the “Charge request” is received, the voltage and current unbalance errors (“Voltage unbalance (CH)”, “Current unbalance (CH)”, “Charging current unbalance”) are cleared, and the battery modules are joined, go to step 2.
145 145  1. Closing the main precharging contactor “Precharging” (optional). Go to step 3.
... ... @@ -392,7 +392,7 @@
392 392  
393 393  To configure the parameters for counting the number of contactor openings, select the section “Control → Load open counter”:
394 394  
395 -[[image:1734089726360-887.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="83" width="600"]]
396 +[[image:1734089726360-887.png]]
396 396  
397 397  In this section:
398 398