Changes for page 3.3 Control

Last modified by Admin on 2025/05/30 16:50

From version 49.1
edited by Admin
on 2025/04/15 16:50
Change comment: There is no comment for this version
To version 43.3
edited by Admin
on 2025/04/15 16:42
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -241,7 +241,7 @@
241 241  
242 242  The battery discharge management is configured in the "Control → Discharge" section:
243 243  
244 -[[image:1744735777632-647.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="226" width="600"]]
244 +[[image:1742473693993-991.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="237" width="600"]]
245 245  
246 246  In this section:
247 247  
... ... @@ -311,8 +311,9 @@
311 311  
312 312  The charge/discharge contactor control is configured in the “Control → Charge/Discharge” section:
313 313  
314 -[[image:1744735816351-271.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="249" width="600"]]
315 315  
315 +[[image:1742475800208-207.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="237" width="600"]]
316 +
316 316  In this section:
317 317  
318 318  * Enable – a flag to enable battery charge/discharge controller;
... ... @@ -327,7 +327,7 @@
327 327  * Allowable battery current to rejoin modules – a battery current at which joining of battery modules is permitted, A;
328 328  * Allowable voltage difference to rejoin modules – a difference between the voltage of the disconnected module and the battery voltage at which its joining is permitted, V;
329 329  * Checking voltages time – a time of checking voltages of battery modules before starting joining modules, millisecond;
330 -* Module balancing time – a time of balancing battery modules after joining modules and before closing main charging/discharging contactor, millisecond;
331 +* Module balancing time – a time of balancing battery modules after joining modules and before closing main chardischarging contactor, millisecond;
331 331  * Interrupt balancing when modules are joined – a flag to break balancing time after all modules are joined;
332 332  * Control the precharging contactor – a flag to control the main precharging contactor;
333 333  * Canceling discharging time – a delay before opening the main discharging contactor, millisecond;
1744735701575-567.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.admin
Size
... ... @@ -1,1 +1,0 @@
1 -54.5 KB
Content
1744735777632-647.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.admin
Size
... ... @@ -1,1 +1,0 @@
1 -54.5 KB
Content
1744735816351-271.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.admin
Size
... ... @@ -1,1 +1,0 @@
1 -62.5 KB
Content