... ... @@ -190,7 +190,7 @@
190 190  * Allowable voltage difference to rejoin modules – a difference between the voltage of the disconnected module and the battery voltage at which its joining is permitted, V;
191 191  * Checking voltages time – a time of checking voltages of battery modules before starting joining modules, millisecond;
192 192  * Module balancing time – a time of balancing battery modules after joining modules and before closing main charging contactor, millisecond;
193 -* Interrupt balancing when modules are joined – a flag to start closing main charging contactor after all modules are joined;
193 +* Interrupt balancing when modules are joined – a flag to start closing main charging
194 194  * Control the precharging contactor – a flag to control the main precharging contactor;
195 195  * Canceling charging time – a delay before opening the main charging contactor, ms;
196 196  * Disconnect modules that are not ready to charge – a flag for disconnecting modules that have the “Ready to charge” signal cleared.